VLT 5000 series
FC 302 series
Parameter
211 Jog ramp time
3-80 Jog Ramp Time
Range
0.05 – 3600.00 s
0.01 – 3600.00 s
Table 5.64 Conversion of Parameter 211
VLT 5000 series
FC 302 series
Parameter 212 Quick stop ramp
time
3-81 Quick Stop Ramp
Time
Range
0.05 – 3600.00 s
0.01 – 3600.00 s
Table 5.65 Conversion of Parameter 212
VLT 5000 series
FC 302 series
Parameter
213 Jog Frequency
3-11 Jog Speed [Hz]
Range
0.0 – par. 202
0.0 – par. 4-14
Table 5.66 Conversion of Parameter 213
VLT 5000 series
FC 302 series
Parameter 214 Reference function
3-04 Reference Function
Options
[0] Sum
[0] Sum
[1] Relative
See comment below*
[2] External/Preset
[2] External/Preset
Table 5.67 Conversion of Parameter 214
*= Relative reference is added to the MRV from PROFIBUS.
VLT 5000 series
FC 302 series
Parameter
215 Preset Reference 1
3-10 Preset Reference
Range
-100.00 – 100.00%
-100.00 – 100.00%
Table 5.68 Conversion of Parameter 215
VLT 5000 series
FC 302 series
Parameter
216 Preset Reference 2
3-10 Preset Reference
Range
-100.00 – 100.00%
-100.00 – 100.00%
Table 5.69 Conversion of Parameter 216
VLT 5000 series
FC 302 series
Parameter
217 Preset Reference 3
3-10 Preset Reference
Range
-100.00 – 100.00%
-100.00 – 100.00%
Table 5.70 Conversion of Parameter 217
VLT 5000 series
FC 302 series
Parameter
218 Preset Reference 4
3-10 Preset Reference
Range
-100,00 - 100,00%
-100,00 - 100,00%
Table 5.71 Conversion of Parameter 218
VLT 5000 series
FC 302 series
Parameter 219 Catch up/slow
down value
3-12 Catch up/slow Down
Value
Range
0.00 – 100%
0.00 – 100%
Table 5.72 Conversion of Parameter 219
VLT 5000 series
FC 302 series
Parameter 221 Torque limit for
motor mode
4-16 Torque Limit Motor
Mode
Range
0.0 – Max. torque %
0.0 – Max. torque %
Table 5.73 Conversion of Parameter 221
VLT 5000 series
FC 302 series
Parameter 222 Torque limit for
generating mode
4-17 Torque Limit
Generator Mode
Range
0.0 – Max. torque %
0.0 – Max. torque %
Table 5.74 Conversion of Parameter 222
VLT 5000 series
FC 302 series
Parameter 223 Warning: Current
Low
4-50 Warning Current Low
2-20 Release Brake Current
Range
0.0 – par. 2-24 Current
High
0.00 – par. 4-51
Table 5.75 Conversion of Parameter 223
VLT 5000 series
FC 302 series
Parameter 224 Warning: Current
High
4-51 Warning Current
High
Range
Power Unit dependable
Power Unit dependable
Table 5.76 Conversion of Parameter 224
VLT 5000 series
FC 302 series
Parameter 225 Warning Low
Frequency
4-52 Warning Speed Low
2-22 Activate Brake Speed
[Hz]
Range
0,0 – par. 226
0,0 – Par. 4-53
Table 5.77 Conversion of Parameter 225
VLT 5000 series
FC 302 series
Parameter 226 Warning High
Frequency
4-53 Warning Speed High
Range
par. 2-25 – par. 202
Par. 4-52 – par. 4-13
Table 5.78 Conversion of Parameter 226
VLT 5000 series
FC 302 series
Parameter 227 Warning Low
Feedback
4-56 Warning Feedback
Low
Range
-100,000.000 – par. 228
-999,999.999 – par. 4-57
Table 5.79 Conversion of Parameter 227
VLT 5000 series
FC 302 series
Parameter 228 Warning High
Feedback
4-57 Warning Feedback
High
Range
par. 227 – 100,000.000
Par. 4-56 – 999,999.999
Table 5.80 Conversion of Parameter 228
Parameter Mapping Lists
Operating Instructions
MG37E102