10-12 Process Data Config Read
Select the process read data for I/O assembly instances 101/151.
Elements [2] and [3] of this array can be selected. Elements [0] and
[1] of the array are fixed.
Option:
Function:
[1679]
Analog Out X45/3 [mA]
[1684]
Comm. Option Status
[1690]
Alarm Word
[1691]
Alarm word 2
[1692]
Warning Word
[1693]
Warning word 2
[1694]
Ext. Status Word
[1860]
Digital Input 2
[3421]
PCD 1 Read from MCO
[3422]
PCD 2 Read from MCO
[3423]
PCD 3 Read from MCO
[3424]
PCD 4 Read from MCO
[3425]
PCD 5 Read from MCO
[3426]
PCD 6 Read from MCO
[3427]
PCD 7 Read from MCO
[3428]
PCD 8 Read from MCO
[3429]
PCD 9 Read from MCO
[3430]
PCD 10 Read from MCO
[3440]
Digital Inputs
[3441]
Digital Outputs
[3450]
Actual Position
[3451]
Commanded Position
[3452]
Actual Master Position
[3453]
Slave Index Position
[3454]
Master Index Position
[3455]
Curve Position
[3456]
Track Error
[3457]
Synchronizing Error
[3458]
Actual Velocity
[3459]
Actual Master Velocity
[3460]
Synchronizing Status
[3461]
Axis Status
[3462]
Program Status
[3464]
MCO 302 Status
[3465]
MCO 302 Control
[3470]
MCO Alarm Word 1
[3471]
MCO Alarm Word 2
10-13 Warning Parameter
Range:
Function:
0
*
[0 -
65535 ]
View a DeviceNet-specific warning word. One bit is
assigned to every warning. Please refer to the
DeviceNet Instruction Manual (MG.33.DX.YY) for
further information.
Bit:
Meaning:
0
BusNetwork not active
1
Explicit connection timeout
2
I/O connection
3
Retry limit reached
4
Actual is not updated
5
CAN bus off
6
I/O send error
7
Initialization error
8
No bus supply
9
Bus off
10
Error passive
11
Error warning
12
Duplicate MAC ID Error
13
RX queue overrun
14
TX queue overrun
15
CAN overrun
10-14 Net Reference
Read only from LCP
Option:
Function:
Select the reference source in instance 21/71 and 20/70.
[0]
*
Off
Enables reference via analog/digital inputs.
[1]
On
Enables reference via the serial communication bus.
10-15 Net Control
Read only from LCP
Option:
Function:
Select the control source in Instance 21/71 and 20/70.
[0]
*
Off Enables control via analog/digital inputs.
[1]
On Enable control via the serial communication bus.
Parameter Descriptions
FC 300 Programming Guide
3-100
MG.33.MA.22 - VLT
®
is a registered Danfoss trademark
3