3.2.5 0-4* LCP Keypad
Enable, disable and password protect individual keys on the
LCP.
0-40 [Hand on] Key on LCP
Option:
Function:
[0]
Disabled
No effect when [Hand on] is pressed. Select
[0] Disabled to avoid accidental start of the
drive in
Hand on
mode.
[1]
*
Enabled
The LCP switches to
Hand on
mode directly
when [Hand on] is pressed.
[2]
Password
After pressing [Hand on], a password is
required. If par. 0-40 is included in
My
Personal Menu
, define the password in par.
0-65,
Personal Menu Password
. Otherwise,
define the password in par. 0-60, Main Menu
Password
[3]
Hand Off/On
When [Hand on] is pressed once, the LCP
switches to
Off
mode. When pressed again,
the LCP switches to
Hand on
mode.
[4]
H off/on w.
passw.
Same as [3] but a password is required (see
[2]).
0-41 [Off] Key on LCP
Option:
Function:
[0]
*
Disabled
Avoids accidental stop of the adjustable frequency
drive.
[1]
*
Enabled
[2]
Password Avoids unauthorized stop. If
is
included in the quick menu, then define the
password in
0-42 [Auto on] Key on LCP
Option:
Function:
[0]
*
Disabled
Avoid accidental start of the adjustable frequency
drive in auto mode.
[1]
*
Enabled
[2]
Password Avoids unauthorized start in auto mode. If
is included in the quick
menu, then define the password in
.
0-43 [Reset] Key on LCP
Option:
Function:
[0]
*
Disabled
No effect when [Reset] is pressed. Avoids
accidental alarm reset.
[1]
*
Enabled
[2]
Password
Avoids unauthorized resetting. If
is included in the
quick menu, then define the password in
.
[7]
Enabled
without OFF
Resets the drive without setting it in
Off
mode.
[8]
Password
without OFF
Resets the drive without setting it in
Off
mode. A password is required when
pressing [Reset] (see [2]).
3.2.6 0-5* Copy/Save
Copy parameter settings between set-ups and to/from the
LCP.
0-50 LCP Copy
Option:
Function:
[0]
*
No copy
[1]
All to LCP
Copies all parameters in all set-ups from
the adjustable frequency drive memory
to the LCP memory.
[2]
All from LCP
Copies all parameters in all set-ups from
the LCP memory to the adjustable
frequency drive memory.
[3]
Size indep. of LCP
Copy only the parameters that are
independent of the motor size. The
latter selection can be used to program
several adjustable frequency drives with
the same function without disturbing
motor data.
[4]
File from MCO to
LCP
[5]
File from LCP to
MCO
[6]
Data from DYN to
LCP
[7]
Data from LCP to
DYN
This parameter cannot be adjusted while the motor is
running.