9-64 Device Identification
Range:
Function:
0
*
[0 - 0 ] This parameter displays the device identification.
Please refer to the
Instruction Manual for Profibus,
MG.
33.CX.YY for further explanation.
9-65 Profile Number
Range:
Function:
0 N/A
*
[0 - 0 N/A] This parameter contains the profile identifi-
cation. Byte 1 contains the profile number
and byte 2 the version number of the profile.
NOTE!
This parameter is not visible via LCP.
9-67 Control Word 1
Range:
Function:
0
*
[0 - 65535 ] This parameter accepts the control word from a
Master Class 2 in the same format as PCD 1.
9-68 Status Word 1
Range:
Function:
0
*
[0 - 65535 ] This parameter delivers the status word for a
Master Class 2 in the same format as PCD 2.
9-70 Programming Set-up
Option:
Function:
Select the set-up to be edited.
[0]
Factory setup Uses default data. This option can be used as
a data source to return the other set-ups to a
known state.
[1]
Set-up 1
Edits Set-up 1.
[2]
Set-up 2
Edits Set-up 2.
[3]
Set-up 3
Edits Set-up 3.
[4]
Set-up 4
Edits Set-up 4.
[9]
*
Active Set-up Follows the active set-up selected in
0-10 Active Set-up
.
This parameter is unique to LCP and serial communication
busses. See also
0-11 Programming Set-up
.
9-71 Profibus Save Data Values
Option:
Function:
Parameter values changed via Profibus are not
automatically stored in non-volatile memory. Use
this parameter to activate a function that stores
parameter values in the EEPROM non-volatile
memory, so changed parameter values will be
retained at power-down.
[0]
*
Off
Deactivates the non-volatile storage function.
[1]
Store edit
setup
Stores all parameter values for all set-ups in the
non-volatile memory. The selection returns to
Off
[0] when all parameter values have been stored.
[2]
Store all
setups
Stores all parameter values for all set-ups in the
non-volatile memory. The selection returns to
Off
[0] when all parameter values have been stored.
9-72 ProfibusDriveReset
Option:
Function:
[0]
*
No action
[1]
Power-on
reset
Resets the adjustable frequency drive upon
power-up, as for power-cycle.
[3]
Comm option
reset
Resets the Profibus option only, useful after
changing certain settings in par. group 9-**,
e.g.,
When reset, the adjustable frequency drive
disappears from the serial communication
bus, which may cause a communication error
from the master.
9-75 DO Identification
Range:
Function:
0
*
[0 - 65535 ] Provides information about the DO (Drive
Object).
9-80 Defined Parameters (1)
Array [116]
No LCP access
Read only
Range:
Function:
0 N/A
*
[0 - 9999 N/A] This parameter displays a list of all the
defined adjustable frequency drive
parameters available for Profibus.
Parameter Descriptions
FC 300 Programming Guide
3-96
MG.33.MA.22 - VLT
®