8-05 End-of-Timeout Function
Option:
Function:
Select the action after receiving a valid control
word following a timeout. This parameter is
active only when
8-04 Control Timeout Function
is set to [Set-up 1-4].
[0]
Hold set-up
Retains the set-up selected in
8-04 Control
Timeout Function
and displays a warning, until
8-06 Reset Control Timeout
toggles. Then the
adjustable frequency drive resumes its original
set-up.
[1]
*
Resume set-
up
Resumes the set-up active prior to the timeout.
8-06 Reset Control Word Timeout
This parameter is active only when
Hold set-up
[0] has been
selected in
Option:
Function:
[0]
*
Do not reset Retains the set-up specified in
, following a control
word timeout.
[1]
Do reset
Returns the adjustable frequency drive to the
original set-up following a control word
timeout. The adjustable frequency drive
performs the reset and then immediately
reverts to the
Do not reset
[0] setting
8-07 Diagnosis Trigger
Option:
Function:
This parameter enables and controls the
adjustable frequency drive diagnosis function and
permits expansion of the diagnosis data to 24
bytes.
NOTE!
This is only valid for Profibus.
-
Disable
[0]: Do not send extended
diagnosis data even if they appear in the
adjustable frequency drive.
-
Trigger on alarms
[1]: Send extended
diagnosis data when one or more alarms
appear in alarm
16-90 Alarm Word
or
-
Trigger alarms/warn.
[2]: Send extended
diagnosis data if one or more alarms or
warnings appear in alarm
16-90 Alarm
Word
,
, or
warning
16-92 Warning Word
.
The content of the extended diagnosis frame is as
follows:
8-07 Diagnosis Trigger
Option:
Function:
Byte
Content
Description
0 - 5
Standard DP
Diagnose
Data
Standard DP Diagnose
Data
6
PDU length xx Header of extended
diagnostic data
7
Status type =
0x81
Header of extended
diagnostic data
8
Slot = 0
Header of extended
diagnostic data
9
Status info =
0
Header of extended
diagnostic data
10 - 13 VLT
16-92 Warning
Word
VLT warning word
VLT status word
18 - 21 VLT
16-90 Alarm
Word
VLT alarm word
Communication
warning word (Profibus)
Enabling diagnosis may cause increased bus
traffic. Diagnosis functions are not supported by
all serial communication bus types.
[0]
*
Disable
[1]
Trigger
on
alarms
[2]
Trigger
alarm/
warn.
Parameter Descriptions
FC 300 Programming Guide
3-82
MG.33.MA.22 - VLT
®
is a registered Danfoss trademark