FC 302
N560
N630
N710
- Mains with contactor [mm
2
(AWG)]
4x127 (4x250 mcm) 4x185 (4x350 mcm) 4x185 (4x350 mcm)
- Motor [mm
2
(AWG)]
4x127 (4x250 mcm) 4x185 (4x350 mcm) 4x185 (4x350 mcm)
Drive module power loss at 600 V [W]
(1)(2)(3)
8069
9208
8543
10346
10319
12723
Drive module power loss at 690 V [W]
(1)(2)(3)
7848
8921
8363
10066
10060
12321
Drive efficiency
(2)
0.98
0.98
0.98
Output frequency [Hz]
(4)
0–590
0–590
0–590
Heat sink overtemperature trip [°C (°F)]
110 (230)
110 (230)
110 (230)
Control card overtemperature trip [°C (°F)]
80 (176)
80 (176)
80 (176)
PHF overtemperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
Line reactor overtemperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
dU/dt filter overtemperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
Sine-wave filter overtemperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
1
Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions.) These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies to dimension-
ing of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power
consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-efficiency-direc-
tive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each
add only 4 W.
2
Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficien-
cy class, see the
Ambient Conditions
section. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
3
See also
Input Power Option Losses
section.
4
If using an output filter, the output frequency is limited further. See
.
10.2 Mains Supply
The unit is suitable for use on a circuit capable of delivering not more than 65 kA short circuit current rating (SCCR) at 480/600 V.
Supply terminals
L1, L2, L3
Supply voltage
(1)
380–480/500 V ±10%, 525–690 V ±10%
Supply frequency
50/60 Hz ±5%
Maximum imbalance temporary between mains phases
3.0% of rated supply voltage
(2)
True power factor (λ)
≥0.9 nominal at rated load
Displacement power factor (cos Φ)
Near unity (>0.98)
Switching on the input supply L1, L2, and L3 (power-ups)
Maximum 1 time/2 minutes
Environment according to EN 60664-1
Overvoltage category III/pollution degree 2
1
Mains voltage low/mains dropout: During low mains voltage or a mains dropout, the drive continues until the DC-link voltage drops below the
minimum stop level, which corresponds typically to 15% below the drive's lowest rated supply voltage. Power-up and full torque cannot be expec-
ted at mains voltage lower than 10% below the drive's lowest rated supply voltage.
2
Calculations based on UL/IEC 61800-3.
10.3 Motor Output and Motor Data
10.3.1 Motor Output (U, V, W)
Output voltage
0–100% of supply voltage
AQ262139143212en-000301 / 130R0879 | 171
Danfoss A/S © 2021.10
Specifications
VLT® AutomationDrive FC 302
Operating Guide