Table 147: Power Losses for Fusible Disconnect Option, 525–690 V
Model
525–550 V [W]
551–690 V [W]
–
NO
HO
NO
HO
N90K
29
20
27
18
N110
41
29
37
27
N132
63
41
57
37
N160
71
45
65
41
N200
101
70
92
64
N250
118
84
108
77
N315
151
112
138
102
N355
191
135
175
125
N400
134
90
123
83
N500
154
119
141
109
N560
173
154
173
141
N630
208
155
190
142
N710
282
208
258
190
11.6.3 Non-fusible Disconnect Losses
Table 148: Power Losses for Non-fusible Disconnect Option, 380–500 V
Model
380–440 V [W]
441–500 V [W]
–
NO
HO
NO
HO
N90K
8
6
7
5
N110
13
8
11
7
N132
19
13
17
11
N160
29
19
25
17
N200
44
29
37
25
N250
65
44
54
37
N315
25
21
20
17
N355
32
25
26
20
N400
36
27
30
26
N450
43
36
34
30
N500
55
43
44
34
AQ262139143212en-000301 / 130R0879 | 199