![Danfoss D9h Operating Manual Download Page 200](http://html2.mh-extra.com/html/danfoss/d9h/d9h_operating-manual_5121583200.webp)
Table 149: Power Losses for Non-fusible Disconnect Option, 525–690
Model
525–550 V [W]
551–690 V [W]
–
NO
HO
NO
HO
N90K
4
2
3
2
N110
5
4
5
3
N132
8
5
7
5
N160
12
8
11
7
N200
17
12
16
11
N250
24
17
22
16
N315
33
24
30
22
N355
42
29
38
27
N400
52
35
47
32
N500
20
16
19
14
N560
23
20
23
19
N630
32
24
30
22
N710
44
32
40
30
11.6.4 Molded-case Circuit Breaker (MCCB) Losses
Table 150: Power Losses for MCCB Option, 380–500 V
Model
380–440 V [W]
441–500 V [W]
–
NO
HO
NO
HO
N90K
25
18
20
14
N110
38
25
32
20
N132
56
38
51
32
N160
54
35
45
32
N200
80
54
68
45
N250
120
80
100
68
N315
62
52
50
42
N355
80
62
66
50
N400
92
70
77
66
N450
112
92
88
77
N500
92
73
74
57
AQ262139143212en-000301 / 130R0879
200 | Danfoss A/S © 2021.10
Appendix
VLT® AutomationDrive FC 302
Operating Guide
Summary of Contents for D9h
Page 2: ......