Table 155: Power Losses for Line Reactor Option, 525–690 V
Model
525–550 V [W]
551–690 V [W]
–
NO
HO
NO
HO
N90K
395
270
360
245
N110
552
395
504
360
N132
845
552
776
504
N160
817
511
745
470
N200
1170
817
1069
745
N250
1366
967
1250
883
N315
1842
1366
1681
1250
N355
1409
996
1293
919
N400
1744
1171
1595
1071
N500
2491
1921
2279
1757
N560
2786
2491
2786
2279
N630
2472
1845
2268
1686
N710
3361
2472
3069
2268
11.6.7 dU/dt Filter Losses
Table 156: Power Losses for dU/dt Filter Option, 380–500 V
Model
380–440 V [W]
441–500 V [W]
–
NO
HO
NO
HO
N90K
350
244
281
199
N110
526
350
448
281
N132
327
223
300
190
N160
514
327
429
300
N200
834
565
710
472
N250
1251
834
1036
710
N315
713
593
573
480
N355
914
713
757
573
N400
1054
795
878
757
N450
1402
1158
1101
964
N500
1774
1402
1434
1101
AQ262139143212en-000301 / 130R0879 | 203
Danfoss A/S © 2021.10
Appendix
VLT® AutomationDrive FC 302
Operating Guide
Summary of Contents for D9h