![Danfoss D9h Operating Manual Download Page 52](http://html2.mh-extra.com/html/danfoss/d9h/d9h_operating-manual_5121583052.webp)
1
Programmable logic controller (PLC)
2
Minimum 16 mm
2
(6 AWG) equalizing cable
3
Control cables
4
Minimum 200 mm (7.9 in) between control cables,
motor cables, and mains cables
5
Mains supply
6
Bare (unpainted) surface
7
Star washers
8
Brake cable (shielded)
9
Motor cable (shielded)
10
Mains cable (unshielded)
11
Output contactor, and so on.
12
Cable insulation stripped
13
Common ground busbar. Follow local and national
requirements for cabinet grounding.
14
Brake resistor
15
Metal box
16
Connection to motor
17
Motor
18
EMC cable gland
AQ262139143212en-000301 / 130R0879
52 | Danfoss A/S © 2021.10
Electrical Installation
VLT® AutomationDrive FC 302
Operating Guide
Summary of Contents for D9h