![Danfoss D9h Operating Manual Download Page 163](http://html2.mh-extra.com/html/danfoss/d9h/d9h_operating-manual_5121583163.webp)
FC 302
N160
N200
N250
- Mains with disconnect [mm
2
(AWG)]
2x185 (2x350 mcm) 2x185 (2x350 mcm) 2x185 (2x350 mcm)
- Mains with fusible disconnect [mm
2
(AWG)]
2x185 (2x350 mcm) 2x185 (2x350 mcm) 2x185 (2x350 mcm)
- Mains with contactor [mm
2
(AWG)]
2x185 (2x350 mcm) 2x185 (2x350 mcm) 2x185 (2x350 mcm)
- Mains [mm
2
(AWG)]
2x185 (2x350 mcm) 2x185 (2x350 mcm) 2x185 (2x350 mcm)
Drive module power loss at 400 V [W]
(1)(2)(3)
3093
4116
4039
5137
5005
6674
Drive module power loss at 460 V [W]
(1)(2)(3)
2872
3569
3575
4566
4458
5714
Drive efficiency
(2)
0.98
0.98
0.98
Output frequency [Hz]
(4)
0–590
0–590
0–590
Heat sink overtemperature trip [°C (°F)]
110 (230)
110 (230)
110 (230)
Control card overtemperature trip [°C (°F)]
80 (176)
80 (176)
80 (176)
PHF overtemperature trip [°C (°F)]
145 (293)
145 (293)
145 (293)
Line reactor overtemperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
dU/dt filter overtemperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
Sine-wave filter overtemperature trip [°C (°F)]
150 (302)
150 (302)
150 (302)
1
Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions.) These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies to dimension-
ing of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power
consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-efficiency-direc-
tive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each
add only 4 W.
2
Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficien-
cy class, see the
Ambient Conditions
section. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
3
See also
Input Power Option Losses
section.
4
If using an output filter, the output frequency is limited further. See
.
Table 103: Electrical Data, Mains Supply 3x380–500 V AC
FC 302
N315
N355
N400
High/normal overload
High overload=150% or 160% torque for a duration of 60 s.
Normal overload=110% torque for a duration of 60 s.
HO
NO
HO
NO
HO
NO
Typical shaft output at 400 V [kW]
315
355
355
400
400
450
Typical shaft output at 460 V [hp]
450
500
500
600
550
600
Typical shaft output at 500 V [kW]
355
400
400
500
500
530
Enclosure size
E5h
E5h
E5h
Output current (3-phase)
Continuous (at 400 V) [A]
600
658
658
745
695
800
Intermittent (60 s overload) (at 400 V) [A]
900
724
987
820
1043
880
Continuous (at 460/500 V) [A]
540
590
590
678
678
730
AQ262139143212en-000301 / 130R0879 | 163
Danfoss A/S © 2021.10
Specifications
VLT® AutomationDrive FC 302
Operating Guide
Summary of Contents for D9h
Page 2: ......