FC 302
N450
N500
Line reactor overtemperature trip [°C (°F)]
150 (302)
150 (302)
dU/dt filter overtemperature trip [°C (°F)]
150 (302)
150 (302)
Sine-wave filter overtemperature trip [°C (°F)]
150 (302)
150 (302)
1
Typical power loss is at normal conditions and expected to be within ±15% (tolerance relates to variety in voltage and cable conditions.) These
values are based on a typical motor efficiency (IE/IE3 border line). Lower efficiency motors add to the power loss in the drive. Applies to dimension-
ing of drive cooling. If the switching frequency is higher than the default setting, the power losses can increase. LCP and typical control card power
consumptions are included. For power loss data according to EN 50598-2, refer to drives.danfoss.com/knowledge-center/energy-efficiency-direc-
tive/#/. Options and customer load can add up to 30 W to the losses, though usually a fully loaded control card and options for slots A and B each
add only 4 W.
2
Measured using 5 m (16.4 ft) shielded motor cables at rated load and rated frequency. Efficiency measured at nominal current. For energy efficien-
cy class, see the
Ambient Conditions
section. For part load losses, see drives.danfoss.com/knowledge-center/energy-efficiency-directive/#/.
3
See also
Input Power Option Losses
section.
4
If using an output filter, the output frequency is limited further. See
10.1.2 Electrical Data, 525–690 V AC
Table 105: Electrical Data, Mains Supply 3x525–690 V AC
FC 302
N90K
N110
N132
N160
High/normal overload
High overload=150% or 160% torque for a
duration of 60 s. Normal overload=110% tor-
que for a duration of 60 s.
HO
NO
HO
NO
HO
NO
HO
NO
Typical shaft output at 550 V [kW]
75
90
90
110
110
132
132
160
Typical shaft output at 575 V [hp]
100
125
125
150
150
200
200
250
Typical shaft output at 690 V [kW]
90
110
110
132
132
160
160
200
Enclosure size
D9h
D9h
D9h
D10h
Output current (3-phase)
Continuous (at 550 V) [A]
113
137
137
162
162
201
201
253
Intermittent (60 s overload) (at 550 V) [A]
170
151
206
178
243
221
301
278
Continuous (at 575/690 V) [A]
108
131
131
155
155
192
192
242
Intermittent (60 s overload) (at 575/690 V) [A]
162
144
197
171
233
211
288
266
Continuous kVA (at 550 V) [kVA]
103
125
125
147
147
183
183
230
Continuous kVA (at 575 V) [kVA]
108
131
131
154
154
191
191
241
Continuous kVA (at 690 V) [kVA]
129
157
157
185
185
230
229
289
Maximum input current
Continuous (at 525 V) [A]
109
132
132
156
156
193
193
244
Continuous (at 575/690 V) [A]
104
126
126
149
149
185
185
233
Maximum number and size of cables per phase
- Mains [mm
2
(AWG)]
2x95 (2x3/0 mcm) 2x95 (2x3/0 mcm) 2x95 (2x3/0 mcm) 2x185 (2x350 mcm)
AQ262139143212en-000301 / 130R0879