10.7 Filter Specifications
10.7.1 Passive Harmonic Filter Specifications
Phase imbalance
Maximum of 3%
Voltage variation
+10%–15%
Nominal frequency
-2%, +2% (of 50 Hz or 60 Hz) when PHF is installed
Overload capability
150% for 60 s in a period of 10 minutes
Maximum inrush current, drive side
Maximum 5xI
nom drive
Maximum inrush current, PHF input side
Maximum 2xI
nom drive
Power derating
Same as drive
Table 109: Displacement Power Factor (Cos Phi)
Load [%]
Automatic capacitor control [p.u.]
(1)(2)
Capacitor always connected [p.u.]
(1)
Capacitor always open [p.u.]
(1)
10
1.000
-0.790
1.000
25
-0.830
-0.830
0.990
50
-0.996
-0.996
0.950
75
0.997
0.997
0.930
100
0.986
0.986
0.920
160
0.980
0.980
0.910
1
Positive numbers indicate lagging reactive currents. Negative numbers indicate leading currents.
2
The capacitor connecting contactor switches at 20% load.
10.7.2 Line Reactor Specifications
All line reactors are equipped with thermal switches and are looped to the enclosed drive for overtemperature protection. For more
details, refer to the
Control Compartment
section. The line reactor configuration varies depending on the enclosure and voltage re-
quired.
Table 110: Line Reactor Configuration for D9h–D10h and E5h–E6h Enclosures, 380–500 V
Enclosure
Model
Impedance [%]
D9h
N90K
2.70
D9h
N110
3.22
D9h
N132
2.87
D10h
N160
3.47
D10h
N200
3.01
D10h
N250
3.65
E5h
N315
3.30
E5h
N355
3.62
E5h
N400
3.83
E6h
N450
2.94
E6h
N500
3.23
AQ262139143212en-000301 / 130R0879 | 177
Danfoss A/S © 2021.10
Specifications
VLT® AutomationDrive FC 302
Operating Guide