FC 302
N450
N500
High overload=150% or 160% torque for a duration of 60 s. Normal overload=110%
torque for a duration of 60 s.
Typical shaft output at 400 V [kW]
450
500
500
560
Typical shaft output at 460 V [hp]
600
650
650
750
Typical shaft output at 500 V [kW]
530
560
560
630
Enclosure size
E6h
E6h
Output current (3-phase)
Continuous (at 400 V) [A]
800
880
880
990
Intermittent (60 s overload) (at 400 V) [A]
1200
968
1320
1089
Continuous (at 460/500 V) [A]
730
780
780
890
Intermittent (60 s overload) (at 460/500 V) [A]
1095
858
1170
979
Continuous kVA (at 400 V) [kVA]
554
610
610
686
Continuous kVA (at 460 V) [kVA]
582
621
621
709
Continuous kVA (at 500 V) [kVA]
632
675
675
771
Maximum input current
Continuous (at 400 V) [A]
771
848
848
954
Continuous (at 460/500 V) [A]
704
752
752
858
Maximum number and size of cables per phase
- Mains [mm
2
(AWG)]
4x185 (4x350 mcm) 4x185 (4x350 mcm)
- Mains with disconnect [mm
2
(AWG)]
4x185 (4x350 mcm) 4x185 (4x350 mcm)
- Mains with fusible disconnect [mm
2
(AWG)]
4x185 (4x350 mcm) 4x185 (4x350 mcm)
- Mains with contactor [mm
2
(AWG)]
4x185 (4x350 mcm) 4x185 (4x350 mcm)
- Motor [mm
2
(AWG)]
4x185 (4x350 mcm) 4x185 (4x350 mcm)
Drive module power loss at 400 V [W]
(1)(2)(3)
8352
9473
9449
11102
Estimated power loss at 460 V [W]
(1)(2)(3)
7182
7809
7771
9236
Drive efficiency
(2)
0.98
0.98
Output frequency [Hz]
(4)
0–590
0–590
Heat sink overtemperature trip [°C (°F)]
110 (230)
100 (212)
Control card overtemperature trip [°C (°F)]
80 (176)
80 (176)
PHF overtemperature trip [°C (°F)]
150 (302)
150 (302)
AQ262139143212en-000301 / 130R0879 | 165
Danfoss A/S © 2021.10
Specifications
VLT® AutomationDrive FC 302
Operating Guide