Character posi-
tion
Code Description
AH
AC cabinet light + extended I/O ter cabinet motor heater control
AI
AC cabinet light + extended I/O ter cabinet insulation monitor
AK
AC cabinet light + extended I/O ter cabinet motor heater c insula-
tion monitor
AL
AC cabinet light + cabinet motor heater control
AM
AC cabinet light + cabinet insulation monitor
AN
AC cabinet light + cabinet motor heater c insulation monitor
AP
Extended I/O ter cabinet heater
AS
Extended I/O ter cabinet motor heater control
AT
Extended I/O ter cabinet insulation monitor
AU
Extended I/O ter cabinet motor heater c insulation monitor
AW
Cabinet motor heater control
A8
Cabinet insulation monitor
AY
Cabinet motor heater c insulation monitor
The cabinet heater option increases the inside temperature of the cabinet above the ambient temperature, preventing condensa-
tion in the cabinet. Each cabinet has 1 cabinet heater. The heater element is self regulating. The external supply is connected to
terminal -XD1.1. When the drive is not in run state, the control relay -QAM changes the supply to the output terminals (-XD4). When
the drive is in run state, the control relay disconnects the supply to the cabinet heater. The function is disabled when MCB –FCE is
open.
e3
0b
u1
89
.1
0
-XD1
-FCE
-QAM
1
-XD4
6 A
N
L
-EB1.4
-EB1.3
-EB1.2
-EB1.1
-XD4
Illustration 53: Cabinet Heater Terminals
AQ262139143212en-000301 / 130R0879 | 95
Danfoss A/S © 2021.10
Electrical Installation
VLT® AutomationDrive FC 302
Operating Guide