Arize
®
Life
2
Installation Guide
7
Inside the junction box, connect
the line and neutral wires of the
AC supply source to the line
(black or brown) and neutral
(white or blue) wires of the
leader cable using suitable wire
nuts. If 0-10V dimming will not
be used, cap the dimming wires
(purple and pink*) with suitable
wire nuts. Do not connect the
dimming wires together or to
line, neutral, or ground. If 0-10V
dimming will be used, proceed
to Step 4.
Connect the DIM + (purple) to
the incoming dimmer c.
Connect the Dim – (pink*) to the
incoming dimmer circuit –.
Warning:
The class 2 0-10V
dimming circuit must be separated
from the AC circuit as required by
the applicable electric code.
Strain relief
0-10V conduit
AC conduit
Insert lead wire into junction box.
Insert the female connector of the leader cable so that it fully engages
the male connector of the first luminaire in the run as indicated by
hearing a click.
NOTE: the male connector can be cut off if there is no leader cable.
See Multiple Bar Installation Details to not exceed maximum run
length for one leader.
To avoid damage, do not bend or otherwise exert excessive force
on the connector during installation.
See Components Required on page 3 for leader cable part number.
4
2
1
3
METHOD 3
Wiring Connections
Leader cable
to luminaire(s)
Purple (Dim+)
Pink (Dim-)
Black or brown (L)
White or blue (N)
0-10V
Dimmer
120-277V
AC Supply
CLICK!
IMPORTANT GUIDELINES / CONSEILS IMPORTANTS
• Cables shall not be concealed or extended through a
wall, floor, ceiling, or other parts of the building structure;
located above a suspended ceiling or dropped ceiling;
permanently affixed to the building structure.
• Cables shall be routed so that they are not subject to strain
and are protected from physical damage; visible over their
entire length; and used within their rated ampacity as
determined for the maximum temperature of the installed
environment specified in the instructions.
• Before applying power, ensure that any open female
connectors in the installation are sealed with an end cap.
(see Method 1, step 4)
• Les câbles ne doivent pas être cachés à l’intérieur ou passer
à travers un mur, un plancher, un plafond ou d’autres
parties de la structure du bâtiment; ne doivent pas être
placés au-dessus d’un plafond suspendu; ne doivent pas
faire partie intégrante de la structure du bâtiment.
• Les câbles doivent être installés de façon à être protégés
contre l’étirement et tout autre dommage; être visibles sur
toute leur longueur; utilisés dans la limite de leur capacité
électrique, déterminée pour les limites de température de
l’environnement spécifiée dans ce document.
• Avant de mettre sous tension, assurez-vous que les
connecteurs femelles ouverts du système sont scellés avec
une butée de gaine. (consulter méthode 1, étape 4).
For UL Only
* 2021 and earlier: purple and gray
2022 and later: purple and pink