3
English
(2)
In case of multiple outdoor systems, only 1 label must be adhered,
mentioning the total factory refrigerant charge of all outdoor units
connected on the refrigerant system.
[DESIGN PRESSURE]
• As the design pressure for local connection piping (suction·HP/LP
gas pipe, gas pipe, and liquid pipe) is at least 3.3 MPa, it is possi-
ble to use existing piping (design pressure of at least 3.3 MPa) but
refer to "6. REFRIGERANT PIPING" and check that existing pip-
ing (including branch piping) is compatible with this unit in terms
of materials and thickness and that it does not appear to be cor-
roded.
Air tight test (3.3 MPa 24/h) to check the strength of existing piping
and that it has no gas leaks.
If it is not possible to perform a pressure test, place existing piping
with piping rated at least 3.3 MPa.
• Check that there has been no compressor malfunction, gas sup-
ply exhaustion, or similar issues that could be attributable to pipe
problems in the past. If there have been any such problems,
check that appropriate repairs were made, and if not, implement
such repairs.
1-3 Disposal requirements
Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with relevant local and national
legislation.
2.
INTRODUCTION
• VRV
III
-Q series are designed for outdoor installation and used for
cooling and heat pump applications. Outdoor units come in three
standard sizes, and with a single system through a multi system
combining up to three outdoor units (Heat Pump series), and up
to four outdoor units (Heat Recovery series). Rated capacity is
below.
RQ(C)YQ: Cooling 14.0~54.0 kW, Heating 16.0~60.0 kW
RQCEQ: Cooling 28.0~84.8 kW, Heating 32.0~89.6 kW
• The BS units that combined with RQCEQ system for changing the
refrigerant flow to indoor units are A type (BSQ-AV1, BS1Q-
A7V1B, BS-Q14AV1) and P type (BSVQ-P, BSV-Q100P) only.
Combination with A type and P type cause malfunction.
• The VRV units can be combined with Daikin VRV series indoor
units for air conditioning purposes. Always use appropriate indoor
units compatible with R410A. To learn which models of indoor
units are compatible with R410A, refer to the product catalogs.
Combination with other indoor refrigerant units will cause malfunc-
tion.
2-1 Combination
The indoor units can be installed in the following range.
• Heat Pump series (RQ(C)YQ)
<Outdoor unit>
<Total capacity of indoor units>
<Total quantity of indoor units>
RQYQ140PY1 ....................7.0 ~ 18.2
8 units
RQYQ180PY1 ....................9.0 ~ 23.4
10 units
RQCYQ280PY1............... 14.0 ~ 36.4
16 units
RQCYQ360PY1................17.8 ~ 46.2
20 units
RQCYQ460PY1................22.5 ~ 58.5
26 units
RQCYQ500PY1................25.0 ~ 65.0
29 units
RQCYQ540PY1................28.0 ~ 72.8
33 units
• Heat Recovery series (RQCEQ)
<Outdoor unit>
<Total capacity of indoor units>
<Total quantity of indoor units>
RQCEQ280PY13..............14.0 ~ 36.4
16 units
RQCEQ360PY13..............17.8 ~ 46.2
20 units
RQCEQ460PY13..............22.5 ~ 58.5
26 units
RQCEQ500PY13..............25.0 ~ 65.0
29 units
RQCEQ540PY13..............28.0 ~ 72.8
33 units
RQCEQ636PY13..............30.8 ~ 80.0
36 units
RQCEQ712PY13..............34.5 ~ 89.7
40 units
RQCEQ744PY13..............36.5 ~ 94.9
43 units
RQCEQ816PY13..............40.0 ~ 104
47 units
RQCEQ848PY13..............42.5 ~ 111
50 units
Note
• Be sure to connect an R410A indoor unit.
See the catalog for indoor unit models which can be connected.
• Above is the total capacity and total number of units of the indoor
units when configured in a standard combination. See the techni-
cal reference for details on total capacity and total number of
indoor units when using a configuration other than the standard
combination. The standard combinations are as follows.
• Heat Pump series (RQ(C)YQ)
<Combination unit>
<Independent unit>
RQYQ140PY1
RQYQ140PY1
RQYQ180PY1
RQYQ180PY1
RQCYQ280PY1
RQYRQYQ140PY1
RQCYQ360PY1
RQYRQYQ180PY1
RQCYQ460PY1
RQYRQYRQYQ140PY1
RQCYQ500PY1
RQYRQYRQYQ140PY1
RQCYQ540PY1
RQYRQYRQYQ180PY1
• Heat Recovery series (RQCEQ)
<Combination unit> <Independent unit>
RQCEQ280PY13
RQEQRQEQ140PY13
RQCEQ360PY13
RQEQRQEQ180PY13
RQCEQ460PY13
RQEQRQEQRQEQ140PY13
RQCEQ500PY13
RQEQRQEQRQEQ140PY13
RQCEQ540PY13
RQEQRQEQRQEQ180PY13
RQCEQ636PY13
RQEQRQEQRQEQ212PY13
RQCEQ712PY13
RQEQRQEQRQEQRQEQ140PY13
RQCEQ744PY13
RQEQRQEQRQEQRQEQ140PY13
RQCEQ816PY13
RQEQRQEQRQEQRQEQ180PY13
RQCEQ848PY13
RQEQRQEQRQEQRQEQ212PY13
Note
• Combinations other than those above are prohibited.
• If the total capacity of the connected indoor units exceeds the
capacity of the outdoor unit, cooling and heating performance
may drop when running the indoor units. See the capacity table in
the Engineering Data Book for details.
• There are restrictions on the refrigerant pipe connecting order
between outdoor unit in the case of the multi system.
Install so that the following restrictions are satisfied.
<Restrictions>
The capacities of outdoor units A and B must fulfill the following
conditions.
A
≥
B
2-2 Standard supplied accessories
The following accessories are included. The storage location of the
accessories is shown in figure 1.
• Heat Pump series (RQYQ)
Name
Gas side
accessory
pipe (1)
Gas side
accessory
pipe (2)
Liquid side
accessory
pipe (1)
Liquid side
accessory
pipe (2)
L type
accessory
joint
Quantity
1 pc.
1 pc.
1 pc.
1 pc.
1 pc.
Shape
(Long)
(Short)
Name
Clamp (1) Clamp (2) Clamp (3)
Others
Quantity
1 pc.
8 pcs.
1 pc.
1 pc. each item
Shape
(Large)
(Small)
• Operation manual
• Installation manual
• Declaration confor-
mity (PED, EMC, MD)
• “REQUEST FOR
THE INDICATION”
label (Installation
records)
• “ADDITIONAL REF.
CHARGE” label
to indoor unit
Outdoor
unit A
Outdoor
unit B
Outdoor unit multi
connection
piping kit
01_EN_3P226891-14T.fm Page 3 Tuesday, September 30, 2014 7:48 PM