background image

English

4

• Heat Recovery series (RQEQ)

(Refer to figure 1)

1.

Clamps, Operation manual, etc.

2.

Accessory pipes

3.

Installation manual

Note

Do not throw away any of the accessories until installation is com-
plete.

2-3 Option accessory

To install the outdoor units, the following optional parts are also 
required. To select an optimum kit, refer to “

6-5 Example of connec-

tion

”.

• Refrigerant branching kit

If it is not possible to use existing branch piping or if it is necessary to 
install new piping when installing refrigerant piping to BS/indoor 
units, the following parts are required. (Be sure to use branch piping 
of at least the design pressure of 3.3 MPa.)

• Heat Pump series (RQ(C)YQ)

• Heat Recovery series (RQCEQ)

• Outdoor unit multi connection piping kit

• Heat Pump series (RQ(C)YQ)

• Heat Recovery series (RQCEQ)

Note

Make sure that any separately purchased accessories are designed 
for use with R410A.

2-4 Technical and Electrical specifications

Refer to the Engineering Data Book for the complete list of specifica-
tions.

2-5 Main components

For main components and function of the main components, refer to 
the Engineering Data Book.

2-6 Installation Process

Figure 2 shows the installation process. Install in the order of the 
steps shown.

(Refer to figure 2)

1.

“3. SELECTION OF LOCATION”

2.

“4. INSPECTING AND HANDLING THE UNIT”

3.

“5. PLACING THE UNIT”

4.

“6. REFRIGERANT PIPING”

5.

“7. FIELD WIRING”

6.

“8. AIR TIGHT TEST AND VACUUM DRYING”

7.

“9. PIPE INSULATION”

8.

“10. CHECKING OF DEVICE AND INSTALLATION 
CONDITIONS”

9.

“11. ADDITIONAL REFRIGERANT CHARGE AND 
CHECK OPERATION”

10.

“13. TEST RUN”

11.

Operations which require the power to be turned on

3.

SELECTION OF LOCATION

Select a location for installation that meets the following conditions. 
Get the customer’s permission.

1.

There is no danger of fire due to leakage of flammable gas.

2.

Select the location of the unit in such a way that neither the dis-
charged air nor the sound generated by the unit disturb anyone.

3.

The foundation is strong enough to support the weight of the unit 
and the floor is flat to prevent vibration and noise generation.

4.

The piping length between the outdoor unit and the indoor unit 
may not exceed the allowable piping length. (Refer to

 

“6. REFRIGERANT PIPING”

)

5.

Locations where the unit’s suction vent and outlet vent do not 
directly face the wind. 
Wind blowing directly into the suction or outlet vents will interfere 
with the unit’s operation.
If necessary, install some kind of obstruction to block the wind.

6.

The space around the unit is adequate for servicing and the min-
imum space for air inlet and air outlet is available. 
(See the “Installation Space Examples” for the minimum space 
requirements.)

Installation Space Examples.

• The installation space requirement shown in figure 3 is a refer-

ence for cooling operation when the outdoor temperature is 35°C. 
If the design outdoor temperature exceeds 35°C or the heat load 
exceeds maximum capacity in all the outdoor unit, take an even 
large space on the intake shown in figure 3.

• During installation, install the units using the most appropriate of 

the patterns shown in figure 3 for the location in question, taking 
into consideration human traffic and wind.

• If the number of units installed is more than that is shown in the 

pattern in figure 3, install the units so there are no short circuits.

• As regards space in front of the unit, consider the space needed 

for the local refrigerant piping when installing the units. 

• If the work conditions in figure 3 do not apply, contact your dealer 

or Daikin directly.

(Refer to figure 3)

1.

Front side

2.

No limit to wall height

3.

Service space of front side

4.

Service space of suction side

For Patterns 1 and 2 in figure 3:

Wall height for the front side should be no higher than 1500 
mm.

Wall height for the suction side should be no higher than 500 
mm.

Wall height for the sides – no limit.

Name

Suction 

gas side 

accessory 

pipe (1)

Suction 

gas side 

accessory 

pipe (2)

HP/LP

gas side 

accessory 

pipe (1)

HP/LP

gas side 

accessory 

pipe (2)

Liquid side 

accessory 

pipe (1)

Liquid side 

accessory 

pipe (2)

Quantity

1 pc.

1 pc.

1 pc.

1 pc.

1 pc.

1 pc.

Shape

Q140 type: 

φ

15.9,

Q180·212 type: 

φ

19.1

Q140 type: 

φ

12.7,

Q180·212 type: 

φ

15.9

Name

L type 

accessory 

joint

Clamp (1) Clamp (2) Clamp (3)

Others

Quantity

2 pcs.

1 pc.

8 pcs.

1 pc.

1 pc. each item

Shape

(Large)

(Small)

• Operation manual
• Installation manual
• Declaration con-

formity (PED, 
EMC, MD)

• “REQUEST FOR 

THE INDICATION” 
label (Installation 
records)

• “ADDITIONAL 

REF. CHARGE” 
label

REFNET header KHRP26M22H KHRP26M33H KHRP26M72H KHRP26M73H
REFNET joint

KHRP26A22T KHRP26A33T KHRP26A72T KHRP26A73T

for 3 piping

for 2 piping

REFNET header

-

KHRP25M33H KHRP26M22H KHRP26M33H

KHRP25M72H KHRP25M73H KHRP26M72H KHRP26M73H

REFNET joint

KHRP25A22T KHRP25A33T KHRP26A22T KHRP26A33T
KHRP25A72T KHRP25A73T KHRP26A72T KHRP26A73T

Kit name

2 units

BHFP22P36C

3 units

BHFP22P54C

Kit name

2 units

BHFP26P36C

3 units

BHFP26P63C

4 units

BHFP26P84C

01_EN_3P226891-14T.fm  Page 4  Tuesday, September 30, 2014  7:48 PM

Summary of Contents for VRV III-Q RQYQ140PY1

Page 1: ...Manuale di installazione Condizionatore d aria a sistema VRVIII VRVIII Installatiehandleiding Airconditioner met VRVIII Systeem Manual de instala o Ar condicionado VRVIII System VRVIII Montaj elkitab...

Page 2: ...10 300 300 500 500 500 500 100 100 100 100 300 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 If installed as a serial installation 1 4 3 4 3 4 3 4 3 1 2 1 1 1 200 30...

Page 3: ...4 7 6 8 2 3 4 7 8 9 6 1 1 2 3 4 5 2 1 2 10 9 8 7 5 6 3 4 11 12 8 12 13 1 2 3 4 5 6 7 8 A BC A F1 F2 F1 F2 Q1 Q2 B C 3 1 1 A5P A1P TO IN D UNIT TO OUT D UNIT TO MULTI UNIT F1 F2 F1 F2 F1 F2 TO IN D UN...

Page 4: ...figure 30 2 1 1 1 7 3 4 4 5 5 10 9 9 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 6 6 8 2 1 2 A1P A5P A5P 1 2 3 4 5 1 2 3 4 5 6 7 4 8 8 L1 L2 L3 N 1 2 3 4 5 4 4 6 3 4 5 6 7 8 10 11 9 1 2 1 3 2 5 6 4 1 2 3 6 4 5 1 2...

Page 5: ...1 figure 31 2 figure 32 figure 33 1 2 3 12 13 14 4 5 11 9 8 7 6 10 10 10 10 8 8 8 7 6 5 4 9 10 2 3 1 9 9 9 8 7 6 5 10 4 1 11 3 2 1 5 6 7 3 1 2 3 4 1 2 3 4 5 00_CV_3P226891 14T fm Page 5 Tuesday Septe...

Page 6: ...hese instructions properly may result in personal injury or loss of life CAUTION Failure to observe these instructions properly may result in property damage or personal injury which may be serious de...

Page 7: ...stem clean dry and tightly sealed Read the chapter REFRIGERANT PIPING carefully and follow these procedures correctly A Clean and dry Strict measures must be taken to keep impurities including fluid d...

Page 8: ...Y13 14 0 36 4 16 units RQCEQ360PY13 17 8 46 2 20 units RQCEQ460PY13 22 5 58 5 26 units RQCEQ500PY13 25 0 65 0 29 units RQCEQ540PY13 28 0 72 8 33 units RQCEQ636PY13 30 8 80 0 36 units RQCEQ712PY13 34 5...

Page 9: ...h the unit s operation If necessary install some kind of obstruction to block the wind 6 The space around the unit is adequate for servicing and the min imum space for air inlet and air outlet is avai...

Page 10: ...method and work more than 4 per sons Refer to figure 5 1 Fork 2 Hole large 3 Transportation clasp yellow 4 Fixed screws of transportation clasp Refer to figure 6 1 Belt sling 2 Board 3 Hole large Ref...

Page 11: ...ipes The local interunit piping can be connected either forward or to the sides taken out through the bottom as shown in the figure 12 When passing out through the bottom use the knock hole in the bot...

Page 12: ...to use the accessory piping Make sure the onsite piping does not come into contact with other piping or the bottom frame or side panels of the unit Multi Systems RQEQ series cannot be used as an indep...

Page 13: ...ntil the split of the joint without wrapping any onsite piping around this area Over 500 mm of straight area can be maintained by connect ing at least 120 mm of onsite pipe straight to the joint Refer...

Page 14: ...ed with R410A How to select the REFNET joint When using REFNET joint at the first branch counted from the outdoor unit side Choose from the following table in accordance with the outdoor unit capacity...

Page 15: ...nt branching kit and indoor unit Section E Piping between refrigerant branching kit and indoor unit Section E Piping between outdoor unit and refrigerant branching kit Section A Piping between outdoor...

Page 16: ...liquid piping size at 6 4 Total length m of liquid piping size at 9 5 How to calculate the additional refrigerant to be charged Additional refrigerant to be charged R kg R should be rounded off in uni...

Page 17: ...ranch kit selection Refrigerant branch kit must be used to prescribed kit Use this table for kit selection How to select the REFNET joint How to select the REFNET header When using REFNET joint at the...

Page 18: ...from the following table in accordance with the total capacity of all the outdoor units connected upstream Indoor capacity index 56 kW 56 kW x 112 kW 112 kW x 160 kW 160 kW x 180 kW 180 kW x 224 kW 22...

Page 19: ...5 10m i 9 5 10m j 9 5 10m k 9 5 20m l 9 5 20m m 9 5 20m n 9 5 10m o 6 4 10m p 6 4 10m r 9 5 1m s 9 5 1m t 9 5 1m u 9 5 3m v 15 9 3m w 12 7 3m a b v w c n r u o p RQCEQ848PY13 112 8 915 8 9 kg Round of...

Page 20: ...t applying external pressure on the termi nal parts terminal for power wiring terminal for transmission wir ing and earth terminal 7 1 Power circuit safety device and cable requirements A power circui...

Page 21: ...tem only multi system or to COOL HEAT selector Heat Pump series RQ C YQ Refer to figure 21 1 1 Connection example for single system 2 Outdoor unit 3 COOL HEAT selector 4 To outdoor unit of other syste...

Page 22: ...then secure to prevent outside pressure being exerted on the ter minal board Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will strip the head and m...

Page 23: ...uum for an hour and make sure the pressure does not rise by monitoring with a vacuum gauge 9 PIPE INSULATION Insulation of pipes should be done after performing 8 AIR TIGHT TEST AND VACUUM DRYING Espe...

Page 24: ...e sure to use the correct tools The shutoff valve is not a back seat type If forced open it might break the valve body When using a service port use the charge hose After tightening the cap make sure...

Page 25: ...H2P will be lit on and the compressor will not operate In order to ensure uniform refrigerant distribution it may take up to around 10 minutes for the compressor to start up after the unit starting o...

Page 26: ...efrigerant is not need by calculation addi tional refrigerant charging operation will be need according to the installation conditions 11 2 2 Check operation Be sure to perform check operation after i...

Page 27: ...Suction gas side shutoff valve 7 HP LP gas side shutoff valve 8 Refrigerant charge port 9 Outdoor unit 10 To indoor unit 11 Field piping 2 If additional charging is required from the refrigerant tank...

Page 28: ...4 for longer than 5 seconds after connection of the refrigerant tank LED change indications then re start Use a refrigerant cylin der with sufficient amount of refrigerant The system stop operation fo...

Page 29: ...tops and a indoor remote controller indicates any defect repair the defect part according to Remote controller displays malfunction code Test operate again after the repair To test operate again press...

Page 30: ...eration manual of outdoor unit A3 Drain level error of BS unit Check the drain pump connected to BS unit E3 F4 F3 UF The shutoff valve of the outdoor unit is left closed Open the shutoff valve U1 The...

Page 31: ...of time before restarting the operation Once stopping the compressor will not restart in about 5 minutes even if the On Off button of the remote controller is pushed When the system operation is stopp...

Page 32: ...me of A B as a sin gle room or as the smallest room A Where there are no smaller room divisions B Where there is a room division but there is an opening between the rooms sufficiently large to permit...

Page 33: ...3P226891 14T EM14A007 1410 HT 00_CV_3P226891 14T fm Page 6 Tuesday September 16 2014 9 50 AM...

Reviews: