background image

17

English

• Outside the units, the transmission wiring must be finished simul-

taneously with the local refrigerant piping, and wound with tape 
(field supply) as shown in figure 25.

Heat Pump series (RQ(C)YQ)

(Refer to figure 25.1)

1.

Liquid pipe

2.

Gas pipe

3.

Transmission wiring

4.

Insulation material

5.

Finishing tape

Heat Recovery series (RQCEQ)

(Refer to figure 25.2)

1.

Suction gas pipe

2.

HP/LP gas pipe

3.

Liquid pipe

4.

Insulation material

5.

Finishing tape

6.

Transmission wiring

• For multi system:

1. Transmission wiring between outdoor units in the same piping 

system must be connected to terminals Q1 and Q2 (TO MULTI 
UNIT).
Connecting the wires to the F1, F2 (TO OUT/D UNIT) termi-
nals results in system malfunction.

2. Wiring to other systems should be connected to terminals F1 

and F2 (TO OUT/D UNIT) on the PC-board of the master unit. 
The outdoor unit that connected transmission wiring to indoor 
unit is the master unit. The others are sub units.

CAUTION

• Do not connect the power wiring to terminals for the transmission 

wiring. Doing so would destroy the entire system.

• When connecting wires to the terminal block on the PC-board, too 

much heat or tightening could damage the PC-board. Attach with 
care.
See the table below for the tightening torque of the transmission 
wiring terminals.

7-5 Power Wiring Connection Procedure

Be sure to connect the power supply wiring to the power supply ter-
minal block and hold it in place using the included clamp as shown in 
the figure 26.

(Refer to figure 26)

1.

Power supply (3N~50Hz 380-415V)

2.

Earth leakage circuit breaker

3.

Branch switch, Overcurrent breaker

4.

Ground wire

5.

Attach insulation sleeves

6.

Power supply terminal block

7.

Ground terminal

8.

Clamp (2) (accessory)

• The L1, L2, L3 and N phases of the power wiring should be 

secured separately to the hook using the included clamp (2).

• The ground wiring should be bound to the power wiring using the 

included clamp (2) to prevent outside force from being applied to 
the terminal area.

• Wire so that the ground wiring does not come into contact with the 

compressor lead wiring. If they touch, this may have an adverse 
effect on other devices.

CAUTION

• Be sure to use crimp-style terminal with insulating sleeves for 

connections. (See the figure below.)

• For wiring, use the designated power wire and connect firmly, 

then secure to prevent outside pressure being exerted on the ter-
minal board.

• Use an appropriate screwdriver for tightening the terminal screws. 

A screwdriver with a small head will strip the head and make 
proper tightening impossible.

• Over-tightening the terminal screws may break them.

See the following table for the tightening torque of the terminal 
screws.

• When pulling the ground wire out, wire it so that it comes through 

the cut out section of the cup washer. (See the figure below.) An 
improper ground connection may prevent a good ground from 
being achieved.

• When two wires are connected to a single terminal, connect them 

so that the rear sides of the crimp contacts face each other. Also, 
make sure the thinner wire is on top, securing the two wires simul-
taneously to the resin hook using the included clamp (2).

7-6 Procedure for Wiring Inside Units

• Refer to figure 27 for routing guide for power supply and transmis-

sion wiring.

(Refer to figure 27)

1.

Electric conduit

2.

When routing out the power/ground wires from the left 
side

3.

When routing out the transmission wiring from the open-
ing for piping

4.

When routing out the power/ground wires from the front

5.

Leave at least 50 mm clearance

6.

When routing out the transmission wiring from the 
knockout hole

7.

Retain to the back of the column support with the acces-
sory clamp (3)

8.

When routing out the power/ground wires from the right 
side

9.

Power wiring

10.

Transmission wiring

11.

Ground wire

• Secure wiring using the included clamp (1) as necessary.

CAUTION

• The transmission wiring must be at least 50 mm away from the 

power wiring.

• Make sure all wiring do not contact to the pipes (hatching parts in 

the figure 27).

• After wiring work is completed, check to make sure there are no 

loose connections among the electrical parts in the 
EL.COMPO.BOX.

8.

AIR TIGHT TEST AND VACUUM DRY-
ING

Note

• Always use nitrogen gas for the airtightness test.
• Absolutely do not open the shutoff valve until the main power cir-

cuit insulation measurement has been completed. (measuring 
after the shutoff valve is opened will cause the insulation value to 
drop.)

Screw size

Tightening torque (N · m)

M3 (A5P)

0.53 - 0.63

M3.5 (A1P)

0.80 - 0.96

Power wire

Crimp-style terminal

Insulating sleeve

Screw size

Tightening torque 

(N·m)

M8 Power terminal

5.5 ~7.2

M8 Ground terminal

9.7~11.7

Crimp-style terminal

Cup washer

Cut out section 

Terminal 
block

Crisp style 
terminal

Wire: narrow

Wire: thick

Resin hook

01_EN_3P226891-14T.fm  Page 17  Tuesday, September 30, 2014  7:48 PM

Summary of Contents for VRV III-Q RQYQ140PY1

Page 1: ...Manuale di installazione Condizionatore d aria a sistema VRVIII VRVIII Installatiehandleiding Airconditioner met VRVIII Systeem Manual de instala o Ar condicionado VRVIII System VRVIII Montaj elkitab...

Page 2: ...10 300 300 500 500 500 500 100 100 100 100 300 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 If installed as a serial installation 1 4 3 4 3 4 3 4 3 1 2 1 1 1 200 30...

Page 3: ...4 7 6 8 2 3 4 7 8 9 6 1 1 2 3 4 5 2 1 2 10 9 8 7 5 6 3 4 11 12 8 12 13 1 2 3 4 5 6 7 8 A BC A F1 F2 F1 F2 Q1 Q2 B C 3 1 1 A5P A1P TO IN D UNIT TO OUT D UNIT TO MULTI UNIT F1 F2 F1 F2 F1 F2 TO IN D UN...

Page 4: ...figure 30 2 1 1 1 7 3 4 4 5 5 10 9 9 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 6 6 8 2 1 2 A1P A5P A5P 1 2 3 4 5 1 2 3 4 5 6 7 4 8 8 L1 L2 L3 N 1 2 3 4 5 4 4 6 3 4 5 6 7 8 10 11 9 1 2 1 3 2 5 6 4 1 2 3 6 4 5 1 2...

Page 5: ...1 figure 31 2 figure 32 figure 33 1 2 3 12 13 14 4 5 11 9 8 7 6 10 10 10 10 8 8 8 7 6 5 4 9 10 2 3 1 9 9 9 8 7 6 5 10 4 1 11 3 2 1 5 6 7 3 1 2 3 4 1 2 3 4 5 00_CV_3P226891 14T fm Page 5 Tuesday Septe...

Page 6: ...hese instructions properly may result in personal injury or loss of life CAUTION Failure to observe these instructions properly may result in property damage or personal injury which may be serious de...

Page 7: ...stem clean dry and tightly sealed Read the chapter REFRIGERANT PIPING carefully and follow these procedures correctly A Clean and dry Strict measures must be taken to keep impurities including fluid d...

Page 8: ...Y13 14 0 36 4 16 units RQCEQ360PY13 17 8 46 2 20 units RQCEQ460PY13 22 5 58 5 26 units RQCEQ500PY13 25 0 65 0 29 units RQCEQ540PY13 28 0 72 8 33 units RQCEQ636PY13 30 8 80 0 36 units RQCEQ712PY13 34 5...

Page 9: ...h the unit s operation If necessary install some kind of obstruction to block the wind 6 The space around the unit is adequate for servicing and the min imum space for air inlet and air outlet is avai...

Page 10: ...method and work more than 4 per sons Refer to figure 5 1 Fork 2 Hole large 3 Transportation clasp yellow 4 Fixed screws of transportation clasp Refer to figure 6 1 Belt sling 2 Board 3 Hole large Ref...

Page 11: ...ipes The local interunit piping can be connected either forward or to the sides taken out through the bottom as shown in the figure 12 When passing out through the bottom use the knock hole in the bot...

Page 12: ...to use the accessory piping Make sure the onsite piping does not come into contact with other piping or the bottom frame or side panels of the unit Multi Systems RQEQ series cannot be used as an indep...

Page 13: ...ntil the split of the joint without wrapping any onsite piping around this area Over 500 mm of straight area can be maintained by connect ing at least 120 mm of onsite pipe straight to the joint Refer...

Page 14: ...ed with R410A How to select the REFNET joint When using REFNET joint at the first branch counted from the outdoor unit side Choose from the following table in accordance with the outdoor unit capacity...

Page 15: ...nt branching kit and indoor unit Section E Piping between refrigerant branching kit and indoor unit Section E Piping between outdoor unit and refrigerant branching kit Section A Piping between outdoor...

Page 16: ...liquid piping size at 6 4 Total length m of liquid piping size at 9 5 How to calculate the additional refrigerant to be charged Additional refrigerant to be charged R kg R should be rounded off in uni...

Page 17: ...ranch kit selection Refrigerant branch kit must be used to prescribed kit Use this table for kit selection How to select the REFNET joint How to select the REFNET header When using REFNET joint at the...

Page 18: ...from the following table in accordance with the total capacity of all the outdoor units connected upstream Indoor capacity index 56 kW 56 kW x 112 kW 112 kW x 160 kW 160 kW x 180 kW 180 kW x 224 kW 22...

Page 19: ...5 10m i 9 5 10m j 9 5 10m k 9 5 20m l 9 5 20m m 9 5 20m n 9 5 10m o 6 4 10m p 6 4 10m r 9 5 1m s 9 5 1m t 9 5 1m u 9 5 3m v 15 9 3m w 12 7 3m a b v w c n r u o p RQCEQ848PY13 112 8 915 8 9 kg Round of...

Page 20: ...t applying external pressure on the termi nal parts terminal for power wiring terminal for transmission wir ing and earth terminal 7 1 Power circuit safety device and cable requirements A power circui...

Page 21: ...tem only multi system or to COOL HEAT selector Heat Pump series RQ C YQ Refer to figure 21 1 1 Connection example for single system 2 Outdoor unit 3 COOL HEAT selector 4 To outdoor unit of other syste...

Page 22: ...then secure to prevent outside pressure being exerted on the ter minal board Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will strip the head and m...

Page 23: ...uum for an hour and make sure the pressure does not rise by monitoring with a vacuum gauge 9 PIPE INSULATION Insulation of pipes should be done after performing 8 AIR TIGHT TEST AND VACUUM DRYING Espe...

Page 24: ...e sure to use the correct tools The shutoff valve is not a back seat type If forced open it might break the valve body When using a service port use the charge hose After tightening the cap make sure...

Page 25: ...H2P will be lit on and the compressor will not operate In order to ensure uniform refrigerant distribution it may take up to around 10 minutes for the compressor to start up after the unit starting o...

Page 26: ...efrigerant is not need by calculation addi tional refrigerant charging operation will be need according to the installation conditions 11 2 2 Check operation Be sure to perform check operation after i...

Page 27: ...Suction gas side shutoff valve 7 HP LP gas side shutoff valve 8 Refrigerant charge port 9 Outdoor unit 10 To indoor unit 11 Field piping 2 If additional charging is required from the refrigerant tank...

Page 28: ...4 for longer than 5 seconds after connection of the refrigerant tank LED change indications then re start Use a refrigerant cylin der with sufficient amount of refrigerant The system stop operation fo...

Page 29: ...tops and a indoor remote controller indicates any defect repair the defect part according to Remote controller displays malfunction code Test operate again after the repair To test operate again press...

Page 30: ...eration manual of outdoor unit A3 Drain level error of BS unit Check the drain pump connected to BS unit E3 F4 F3 UF The shutoff valve of the outdoor unit is left closed Open the shutoff valve U1 The...

Page 31: ...of time before restarting the operation Once stopping the compressor will not restart in about 5 minutes even if the On Off button of the remote controller is pushed When the system operation is stopp...

Page 32: ...me of A B as a sin gle room or as the smallest room A Where there are no smaller room divisions B Where there is a room division but there is an opening between the rooms sufficiently large to permit...

Page 33: ...3P226891 14T EM14A007 1410 HT 00_CV_3P226891 14T fm Page 6 Tuesday September 16 2014 9 50 AM...

Reviews: