background image

English

18

8-1 Preparations

<Required tools>

 <The system for air tight test and vacuum drying>

• Referring to figure 28.1 and 28.2, connect on nitrogen tank and a 

vacuum pump to the outdoor unit.

Heat Pump series (RQ(C)YQ)

(Refer to figure 28.1)

1.

Gauge manifold

2.

Nitrogen

3.

Vacuum pump

4.

Charge hose

5.

Valve A

6.

Liquid side shutoff valve

7.

Gas side shutoff valve

8.

Refrigerant charge port

9.

Outdoor unit

10.

To indoor unit

11.

Interunit piping

12.

Flow of the gas

13.

Service port

Heat Recovery series (RQCEQ)

(Refer to figure 28.2)

1.

Gauge manifold

2.

Nitrogen

3.

Vacuum pump

4.

Charge hose

5.

Valve A

6.

Liquid side shutoff valve

7.

Suction gas side shutoff valve

8.

HP/LP gas side shutoff valve

9.

Refrigerant charge port

10.

Outdoor unit

11.

To indoor unit

12.

Interunit piping

13.

Flow of the gas

14.

Service port

Note

• The airtightness test and vacuum drying 

should be done using the liquid side and 
gas side shutoff valve service ports.
See the [R410A] Label attached to the front 
plate of the outdoor unit for details on the 
location of the service port (see figure at 
right).

• See 

[Shutoff valve operation procedure] 

in 

“11-1 Before working” for details on handling 
the shutoff valve.

• The refrigerant charge port is connected to 

unit pipe.
When shipped, the unit contains the refrigerant, so use caution 
when attaching the charge hose.

8-2 Air tight test and vacuum drying method

 After finished piping work, carry out air tight test and vacuum drying.

<Air tight test>

Pressurize the liquid and gas pipes to 3.3MPa (33bar) (do not 
pressurize more than 3.3MPa (33bar)). If the pressure does not 
drop within 24 hours, the system passes the test.
If there is a pressure drop, check for leaks, make repairs and per-
form the airtight test again.

<Vacuum drying>

Evacuate the system from the liquid and gas pipes by using a vac-
uum pump for more than 2 hours and bring the system to 
–100.7kPa or less. After keeping the system under that condition 
for more than 1 hour, check if the vacuum gauge rises or not. If it 
rises, the system may either contain moisture inside or have 
leaks.

Note

If moisture might enter the piping, follow belows.
(I.e., if doing work during the rainy season, if the actual work 
takes long enough that condensation may form on the inside of 
the pipes, if rain might enter the pipes during work, etc.)

(1) After performing the vacuum drying for two hours, pressurize to 

0.05 MPa (i.e., vacuum breakdown) with nitrogen gas, then 
depressurize down to –100.7 kPa for an hour using the vacuum 
pump (vacuum drying). 

(2) If the pressure does not reach –100.7 kPa even after depressur-

ization for at least two hours, repeat the vacuum breakdown - vac-
uum drying process.

After vacuum drying, maintain the vacuum for an hour and make sure 
the pressure does not rise by monitoring with a vacuum gauge.

9.

PIPE INSULATION

• Insulation of pipes should be done after performing “

8. AIR TIGHT 

TEST AND VACUUM DRYING

”. 

• Especially the HP/LP gas side piping is required to be insulated 

as suction gas side piping in cooling operation. (Heat Recovery 
series.)

• Always insulate the liquid side piping, gas side piping, HP/LP gas 

side piping and suction gas piping in the interunit piping and 
refrigerant branching kit. Failing to insulate the pipes could cause 
leaking or burns. (The HP/LP gas side and gas side piping can 
reach temperatures of 120°C. Be sure the insulation used can 
withstand such temperatures.)

• Reinforce the insulation on the refrigerant piping according to the 

installation environment. Condensation might form on the surface 
of the insulation.

„

Ambient temperature: 30°C, humidity: 75% to 80% RH: min. 
thickness: 15 mm.

„

If the ambient temperature exceeds 30°C and the humidity 
80% RH, then the min. thickness is 20 mm.

• If there is a possibility that condensation on the shutoff valve 

might drip down into the indoor unit through gaps in the insulation 
and piping because the outdoor unit is located higher than the 
indoor unit, etc., this must be prevented by caulking the connec-
tions, etc. 

(Refer to figure 29.1, 29.2)

• The piping lead-out hole lid should be attached after opening a 

knock hole. 

(Refer to figure 30)

• If small animals and the like might enter the unit through the pip-

ing lead-out hole, close the hole with blocking material (procured 
onsite) after completion of “

11. ADDITIONAL REFRIGERANT 

CHARGE AND CHECK OPERATION

”. 

(Refer to figure 30)

Heat Pump series (RQ(C)YQ)

(Refer to figure 29.1)

1.

Gas side shutoff valve

2. RQYQ is not used
3.

Liquid side shutoff valve

4.

Indoor interunit piping

5.

Insulation material

6.

Use caulking or similar sealant

Heat Recovery series (RQCEQ)

(Refer to figure 29.2)

1.

HP/LP gas side shutoff valve

2.

Suction gas side shutoff valve

3.

Liquid side shutoff valve

4.

Indoor interunit piping

5.

Insulation material

6.

Use caulking or similar sealant

(Refer to figure 30)

1.

Piping lead-out hole lid

2.

Open a knock hole at “

3.

Block  “

Note

• After knocking out the holes, we recommend you remove burrs in 

the knock holes (see figure 30) and paint the edges and areas 
around the edges using the repair paint.

Gauge manifold, 
Charge hose 
valve

• To prevent entry of any impurities and insure suffi-

cient pressure resistance, always use the special 
tools dedicated for R410A.

• Use a charge hose that has pushing stick for con-

necting to service port of shutoff valves or refriger-
ant charge port.

Vacuum pump

• The vacuum pump for vacuum drying should be 

able to lower the pressure to –100.7kPa 
(5 Torr –755mm Hg).

• Take care the pump oil never flow backward into the 

refrigerant pipe during the pump stops.

[R410A] Label

01_EN_3P226891-14T.fm  Page 18  Tuesday, September 30, 2014  7:48 PM

Summary of Contents for VRV III-Q RQYQ140PY1

Page 1: ...Manuale di installazione Condizionatore d aria a sistema VRVIII VRVIII Installatiehandleiding Airconditioner met VRVIII Systeem Manual de instala o Ar condicionado VRVIII System VRVIII Montaj elkitab...

Page 2: ...10 300 300 500 500 500 500 100 100 100 100 300 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 If installed as a serial installation 1 4 3 4 3 4 3 4 3 1 2 1 1 1 200 30...

Page 3: ...4 7 6 8 2 3 4 7 8 9 6 1 1 2 3 4 5 2 1 2 10 9 8 7 5 6 3 4 11 12 8 12 13 1 2 3 4 5 6 7 8 A BC A F1 F2 F1 F2 Q1 Q2 B C 3 1 1 A5P A1P TO IN D UNIT TO OUT D UNIT TO MULTI UNIT F1 F2 F1 F2 F1 F2 TO IN D UN...

Page 4: ...figure 30 2 1 1 1 7 3 4 4 5 5 10 9 9 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 6 6 8 2 1 2 A1P A5P A5P 1 2 3 4 5 1 2 3 4 5 6 7 4 8 8 L1 L2 L3 N 1 2 3 4 5 4 4 6 3 4 5 6 7 8 10 11 9 1 2 1 3 2 5 6 4 1 2 3 6 4 5 1 2...

Page 5: ...1 figure 31 2 figure 32 figure 33 1 2 3 12 13 14 4 5 11 9 8 7 6 10 10 10 10 8 8 8 7 6 5 4 9 10 2 3 1 9 9 9 8 7 6 5 10 4 1 11 3 2 1 5 6 7 3 1 2 3 4 1 2 3 4 5 00_CV_3P226891 14T fm Page 5 Tuesday Septe...

Page 6: ...hese instructions properly may result in personal injury or loss of life CAUTION Failure to observe these instructions properly may result in property damage or personal injury which may be serious de...

Page 7: ...stem clean dry and tightly sealed Read the chapter REFRIGERANT PIPING carefully and follow these procedures correctly A Clean and dry Strict measures must be taken to keep impurities including fluid d...

Page 8: ...Y13 14 0 36 4 16 units RQCEQ360PY13 17 8 46 2 20 units RQCEQ460PY13 22 5 58 5 26 units RQCEQ500PY13 25 0 65 0 29 units RQCEQ540PY13 28 0 72 8 33 units RQCEQ636PY13 30 8 80 0 36 units RQCEQ712PY13 34 5...

Page 9: ...h the unit s operation If necessary install some kind of obstruction to block the wind 6 The space around the unit is adequate for servicing and the min imum space for air inlet and air outlet is avai...

Page 10: ...method and work more than 4 per sons Refer to figure 5 1 Fork 2 Hole large 3 Transportation clasp yellow 4 Fixed screws of transportation clasp Refer to figure 6 1 Belt sling 2 Board 3 Hole large Ref...

Page 11: ...ipes The local interunit piping can be connected either forward or to the sides taken out through the bottom as shown in the figure 12 When passing out through the bottom use the knock hole in the bot...

Page 12: ...to use the accessory piping Make sure the onsite piping does not come into contact with other piping or the bottom frame or side panels of the unit Multi Systems RQEQ series cannot be used as an indep...

Page 13: ...ntil the split of the joint without wrapping any onsite piping around this area Over 500 mm of straight area can be maintained by connect ing at least 120 mm of onsite pipe straight to the joint Refer...

Page 14: ...ed with R410A How to select the REFNET joint When using REFNET joint at the first branch counted from the outdoor unit side Choose from the following table in accordance with the outdoor unit capacity...

Page 15: ...nt branching kit and indoor unit Section E Piping between refrigerant branching kit and indoor unit Section E Piping between outdoor unit and refrigerant branching kit Section A Piping between outdoor...

Page 16: ...liquid piping size at 6 4 Total length m of liquid piping size at 9 5 How to calculate the additional refrigerant to be charged Additional refrigerant to be charged R kg R should be rounded off in uni...

Page 17: ...ranch kit selection Refrigerant branch kit must be used to prescribed kit Use this table for kit selection How to select the REFNET joint How to select the REFNET header When using REFNET joint at the...

Page 18: ...from the following table in accordance with the total capacity of all the outdoor units connected upstream Indoor capacity index 56 kW 56 kW x 112 kW 112 kW x 160 kW 160 kW x 180 kW 180 kW x 224 kW 22...

Page 19: ...5 10m i 9 5 10m j 9 5 10m k 9 5 20m l 9 5 20m m 9 5 20m n 9 5 10m o 6 4 10m p 6 4 10m r 9 5 1m s 9 5 1m t 9 5 1m u 9 5 3m v 15 9 3m w 12 7 3m a b v w c n r u o p RQCEQ848PY13 112 8 915 8 9 kg Round of...

Page 20: ...t applying external pressure on the termi nal parts terminal for power wiring terminal for transmission wir ing and earth terminal 7 1 Power circuit safety device and cable requirements A power circui...

Page 21: ...tem only multi system or to COOL HEAT selector Heat Pump series RQ C YQ Refer to figure 21 1 1 Connection example for single system 2 Outdoor unit 3 COOL HEAT selector 4 To outdoor unit of other syste...

Page 22: ...then secure to prevent outside pressure being exerted on the ter minal board Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will strip the head and m...

Page 23: ...uum for an hour and make sure the pressure does not rise by monitoring with a vacuum gauge 9 PIPE INSULATION Insulation of pipes should be done after performing 8 AIR TIGHT TEST AND VACUUM DRYING Espe...

Page 24: ...e sure to use the correct tools The shutoff valve is not a back seat type If forced open it might break the valve body When using a service port use the charge hose After tightening the cap make sure...

Page 25: ...H2P will be lit on and the compressor will not operate In order to ensure uniform refrigerant distribution it may take up to around 10 minutes for the compressor to start up after the unit starting o...

Page 26: ...efrigerant is not need by calculation addi tional refrigerant charging operation will be need according to the installation conditions 11 2 2 Check operation Be sure to perform check operation after i...

Page 27: ...Suction gas side shutoff valve 7 HP LP gas side shutoff valve 8 Refrigerant charge port 9 Outdoor unit 10 To indoor unit 11 Field piping 2 If additional charging is required from the refrigerant tank...

Page 28: ...4 for longer than 5 seconds after connection of the refrigerant tank LED change indications then re start Use a refrigerant cylin der with sufficient amount of refrigerant The system stop operation fo...

Page 29: ...tops and a indoor remote controller indicates any defect repair the defect part according to Remote controller displays malfunction code Test operate again after the repair To test operate again press...

Page 30: ...eration manual of outdoor unit A3 Drain level error of BS unit Check the drain pump connected to BS unit E3 F4 F3 UF The shutoff valve of the outdoor unit is left closed Open the shutoff valve U1 The...

Page 31: ...of time before restarting the operation Once stopping the compressor will not restart in about 5 minutes even if the On Off button of the remote controller is pushed When the system operation is stopp...

Page 32: ...me of A B as a sin gle room or as the smallest room A Where there are no smaller room divisions B Where there is a room division but there is an opening between the rooms sufficiently large to permit...

Page 33: ...3P226891 14T EM14A007 1410 HT 00_CV_3P226891 14T fm Page 6 Tuesday September 16 2014 9 50 AM...

Reviews: