background image

5

English

If the height is exceeded the above, calculate h1 and h2 shown 
in the figure below, and add h1/2 to the service space of front 
side and h2/2 to the service space of suction side.

Note

1.

An inverter air conditioner may cause electronic noise gener-
ated from AM broadcasting. Examine where to install the main 
air conditioner and electric wires, keeping proper distances 
away from stereo equipment, personal computers, etc. 
Particularly for locations with weak reception, ensure there is 
a distance of at least 3 meters for indoor remote controllers, 
place power wiring and transmission wiring in conduits, and 
ground the conduits.

 (Refer to figure 4)

1.

Indoor unit

2.

Branch switch, overcurrent breaker, earth leakage circuit 
breaker

3.

Remote controller

4.

COOL/HEAT selector

5.

Personal computer or radio

2.

When installing in a locations where there is heavy snowfall, 
implement the following snow measures.
• Ensure the base is high enough that intakes are not clogged 

by snow.

• Remove the rear intake grille to prevent snow from accumu-

lating on the fins.

3.

If condensate may drip downstairs (or walkway) depending on 
the floor condition, take a measure such as the installation of 
central drain pan kit (sold separately).

4.

The refrigerant R410A itself is nontoxic, nonflammable and is 
safe. If the refrigerant should leak however, its concentration 
may exceed the allowable limit depending on room size. Due to 
this it could be necessary to take measures against leakage. 
See “14. CAUTION FOR REFRIGERANT LEAKS” for details.

4.

INSPECTING AND HANDLING THE UNIT

• At delivery, the package should be checked and any damage 

should be reported immediately to the carrier claims agent.

• When handling the unit, take into account the following:

1.

Fragile, handle the unit with care.

Keep the unit upright in order to avoid compressor damage.

2.

Decide on the transportation route.

3.

If a forklift is to be used, pass the forklift arms through the large 
openings on the bottom of the unit. 

(Refer to figure 5)

4.

If hanging the unit, use a cloth sling to prevent damaging the unit. 
Keeping the following points in mind, hang the unit following the 
procedure shown in figure 6.

Use a sling sufficiently strong to hold the mass of the unit.

Use 2 belts of at least 8m long.

Place extra cloth or boards in the locations where the casing 
comes in contact with the sling to prevent damage. 

Hoist the unit making sure it is being lifted at its center of gravity.

5.

After installation, remove the transportation clasp attached to the 
large openings. 

(Refer to figure 6)

6.

If carrying baggage the unit, hold hand top rear handle product 
and basic front lower leg product, carry as shown in figure 7.

Because the equipment break, the product do not slant than 
60 degree.

Regularly wear glove to work.

Obey local law about work method, and work more than 4 per-
sons.

(Refer to figure 5)

1.

Fork

2.

Hole (large)

3.

Transportation clasp (yellow)

4.

Fixed screws of transportation clasp

(Refer to figure 6)

1.

Belt sling

2.

Board

3.

Hole (large)

(Refer to figure 7)

1.

Cushion plate

2.

Foundation leg

3.

Hanger

Note

Apply a filler cloth on a fork to prevent coating of the bottom frame 
from coming off and rust from occurring when bringing in the unit with 
anti-corrosion treatment type using a forklift.

5.

PLACING THE UNIT

• Make sure the unit is installed level on a sufficiently strong base to 

prevent vibration and noise. 

(Refer to figure 8)

• The base should be bigger around than the width of the unit’s legs 

(66 mm), and should support the unit. 

(Refer to figure 9)

If protective rubber is to be attached, attach it to the whole face of 
the base.

• The height of the base should be at least 150mm from the floor.
• Secure the unit to its base using foundation bolts. (Use four com-

mercially available M12-type foundation bolts, nuts, and washers.)

• The foundation bolts should be inserted 20 mm.

(Refer to figure 8)

1.

The product can be supported with 
four corners

(Refer to figure 9)

1.

Foundation bolt point (

φ

15 dia. : 4 positions)

2.

Depth of product

Note

• There are restrictions on the refrigerant pipe connecting order 

between outdoor unit in the case of the multi system.
See the Note in “2-1 Combination” for detail.

• When installing on a roof, make sure the roof floor is strong 

enough and be sure to water-proof all work.

• Make sure the area around the machine drains properly by setting 

up drainage grooves around the foundation.
Drain water is sometimes discharged from the outdoor unit when 
it is running.

• For anti-corrosion type use nuts with resin washers. If the paint on 

nut connections comes off, the anti-corrosion effect may 
decrease.

6.

REFRIGERANT PIPING

Note

• All field piping must be installed by a licensed refrigeration tech-

nician and must comply with relevant local and national regula-
tions.

• After piping work is complete, do not under any circumstances 

open the shutoff valve until “7. FIELD WIRING” and “10. CHECK-
ING OF DEVICE AND INSTALLATION CONDITIONS” are com-
plete.

• Do not use flux when brazing the refrigerant piping. Use the phos-

phor copper brazing filler metal (BCuP-2: JIS Z 3264/B-Cu93P-
710/795: ISO 3677) which does not require flux.
(Flux has extremely harmful influence on refrigerant piping sys-
tems. For instance, if chlorine based flux is used, it will cause 
pipe corrosion or, in particular, if the flux contains fluorine, it will 
damage the refrigerant oil.)

6-1 Selection of piping material and Refrigerant

branching kit

• Use only pipes which are clean inside and outside and do not 

accumulate harmful sulfur, oxidants, dirt, cutting oils, moisture, or 
other contamination. (Foreign materials inside pipes including oils 
for fabrication must be 30mg/10m or less.) 

1500

500

h1

h2

Front side

Suction side

B

A

h1 = A (Actual height) – 1500
h2 = B (Actual height) – 500

20

Resin washers

01_EN_3P226891-14T.fm  Page 5  Tuesday, September 30, 2014  7:48 PM

Summary of Contents for VRV III-Q RQYQ140PY1

Page 1: ...Manuale di installazione Condizionatore d aria a sistema VRVIII VRVIII Installatiehandleiding Airconditioner met VRVIII Systeem Manual de instala o Ar condicionado VRVIII System VRVIII Montaj elkitab...

Page 2: ...10 300 300 500 500 500 500 100 100 100 100 300 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 If installed as a serial installation 1 4 3 4 3 4 3 4 3 1 2 1 1 1 200 30...

Page 3: ...4 7 6 8 2 3 4 7 8 9 6 1 1 2 3 4 5 2 1 2 10 9 8 7 5 6 3 4 11 12 8 12 13 1 2 3 4 5 6 7 8 A BC A F1 F2 F1 F2 Q1 Q2 B C 3 1 1 A5P A1P TO IN D UNIT TO OUT D UNIT TO MULTI UNIT F1 F2 F1 F2 F1 F2 TO IN D UN...

Page 4: ...figure 30 2 1 1 1 7 3 4 4 5 5 10 9 9 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 6 6 8 2 1 2 A1P A5P A5P 1 2 3 4 5 1 2 3 4 5 6 7 4 8 8 L1 L2 L3 N 1 2 3 4 5 4 4 6 3 4 5 6 7 8 10 11 9 1 2 1 3 2 5 6 4 1 2 3 6 4 5 1 2...

Page 5: ...1 figure 31 2 figure 32 figure 33 1 2 3 12 13 14 4 5 11 9 8 7 6 10 10 10 10 8 8 8 7 6 5 4 9 10 2 3 1 9 9 9 8 7 6 5 10 4 1 11 3 2 1 5 6 7 3 1 2 3 4 1 2 3 4 5 00_CV_3P226891 14T fm Page 5 Tuesday Septe...

Page 6: ...hese instructions properly may result in personal injury or loss of life CAUTION Failure to observe these instructions properly may result in property damage or personal injury which may be serious de...

Page 7: ...stem clean dry and tightly sealed Read the chapter REFRIGERANT PIPING carefully and follow these procedures correctly A Clean and dry Strict measures must be taken to keep impurities including fluid d...

Page 8: ...Y13 14 0 36 4 16 units RQCEQ360PY13 17 8 46 2 20 units RQCEQ460PY13 22 5 58 5 26 units RQCEQ500PY13 25 0 65 0 29 units RQCEQ540PY13 28 0 72 8 33 units RQCEQ636PY13 30 8 80 0 36 units RQCEQ712PY13 34 5...

Page 9: ...h the unit s operation If necessary install some kind of obstruction to block the wind 6 The space around the unit is adequate for servicing and the min imum space for air inlet and air outlet is avai...

Page 10: ...method and work more than 4 per sons Refer to figure 5 1 Fork 2 Hole large 3 Transportation clasp yellow 4 Fixed screws of transportation clasp Refer to figure 6 1 Belt sling 2 Board 3 Hole large Ref...

Page 11: ...ipes The local interunit piping can be connected either forward or to the sides taken out through the bottom as shown in the figure 12 When passing out through the bottom use the knock hole in the bot...

Page 12: ...to use the accessory piping Make sure the onsite piping does not come into contact with other piping or the bottom frame or side panels of the unit Multi Systems RQEQ series cannot be used as an indep...

Page 13: ...ntil the split of the joint without wrapping any onsite piping around this area Over 500 mm of straight area can be maintained by connect ing at least 120 mm of onsite pipe straight to the joint Refer...

Page 14: ...ed with R410A How to select the REFNET joint When using REFNET joint at the first branch counted from the outdoor unit side Choose from the following table in accordance with the outdoor unit capacity...

Page 15: ...nt branching kit and indoor unit Section E Piping between refrigerant branching kit and indoor unit Section E Piping between outdoor unit and refrigerant branching kit Section A Piping between outdoor...

Page 16: ...liquid piping size at 6 4 Total length m of liquid piping size at 9 5 How to calculate the additional refrigerant to be charged Additional refrigerant to be charged R kg R should be rounded off in uni...

Page 17: ...ranch kit selection Refrigerant branch kit must be used to prescribed kit Use this table for kit selection How to select the REFNET joint How to select the REFNET header When using REFNET joint at the...

Page 18: ...from the following table in accordance with the total capacity of all the outdoor units connected upstream Indoor capacity index 56 kW 56 kW x 112 kW 112 kW x 160 kW 160 kW x 180 kW 180 kW x 224 kW 22...

Page 19: ...5 10m i 9 5 10m j 9 5 10m k 9 5 20m l 9 5 20m m 9 5 20m n 9 5 10m o 6 4 10m p 6 4 10m r 9 5 1m s 9 5 1m t 9 5 1m u 9 5 3m v 15 9 3m w 12 7 3m a b v w c n r u o p RQCEQ848PY13 112 8 915 8 9 kg Round of...

Page 20: ...t applying external pressure on the termi nal parts terminal for power wiring terminal for transmission wir ing and earth terminal 7 1 Power circuit safety device and cable requirements A power circui...

Page 21: ...tem only multi system or to COOL HEAT selector Heat Pump series RQ C YQ Refer to figure 21 1 1 Connection example for single system 2 Outdoor unit 3 COOL HEAT selector 4 To outdoor unit of other syste...

Page 22: ...then secure to prevent outside pressure being exerted on the ter minal board Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will strip the head and m...

Page 23: ...uum for an hour and make sure the pressure does not rise by monitoring with a vacuum gauge 9 PIPE INSULATION Insulation of pipes should be done after performing 8 AIR TIGHT TEST AND VACUUM DRYING Espe...

Page 24: ...e sure to use the correct tools The shutoff valve is not a back seat type If forced open it might break the valve body When using a service port use the charge hose After tightening the cap make sure...

Page 25: ...H2P will be lit on and the compressor will not operate In order to ensure uniform refrigerant distribution it may take up to around 10 minutes for the compressor to start up after the unit starting o...

Page 26: ...efrigerant is not need by calculation addi tional refrigerant charging operation will be need according to the installation conditions 11 2 2 Check operation Be sure to perform check operation after i...

Page 27: ...Suction gas side shutoff valve 7 HP LP gas side shutoff valve 8 Refrigerant charge port 9 Outdoor unit 10 To indoor unit 11 Field piping 2 If additional charging is required from the refrigerant tank...

Page 28: ...4 for longer than 5 seconds after connection of the refrigerant tank LED change indications then re start Use a refrigerant cylin der with sufficient amount of refrigerant The system stop operation fo...

Page 29: ...tops and a indoor remote controller indicates any defect repair the defect part according to Remote controller displays malfunction code Test operate again after the repair To test operate again press...

Page 30: ...eration manual of outdoor unit A3 Drain level error of BS unit Check the drain pump connected to BS unit E3 F4 F3 UF The shutoff valve of the outdoor unit is left closed Open the shutoff valve U1 The...

Page 31: ...of time before restarting the operation Once stopping the compressor will not restart in about 5 minutes even if the On Off button of the remote controller is pushed When the system operation is stopp...

Page 32: ...me of A B as a sin gle room or as the smallest room A Where there are no smaller room divisions B Where there is a room division but there is an opening between the rooms sufficiently large to permit...

Page 33: ...3P226891 14T EM14A007 1410 HT 00_CV_3P226891 14T fm Page 6 Tuesday September 16 2014 9 50 AM...

Reviews: