background image

15

English

7.

FIELD WIRING

CAUTION

• All field wiring and components must be installed by a licensed 

electrician and must comply with relevant local and national reg-
ulations.

• Be sure to use a dedicated power circuit. Never use a power sup-

ply shared by another appliance.

• Never install a phase advancing capacitor. As this unit is equipped 

with an inverter, installing a phase advancing capacitor will not only 
deteriorate power factor improvement effect, but may also cause 
abnormal heating of the capacitor due to high-frequency waves.

• Only proceed with wiring work after blocking off all power.
• Always ground wires in accordance with relevant local and 

national regulations.

• This machine includes an inverter device. Connect earth and 

leave charge to eliminate the impact on other devices by reducing 
noise generated from the inverter device and to prevent leaked 
current from being charged in the outer hull of the product.

• Do not connect the ground wire to gas pipes, sewage pipes, light-

ning rods, or telephone ground wires.

Gas pipes:

 can explode or catch fire if there is a gas leak.

Sewage pipes:

 no grounding effect is possible if hard plastic pip-

ing is used.

Telephone ground wires and lightning rods:

 dangerous when 

struck by lightning due to abnormal rise in electrical potential in 
the grounding.

• Be sure to install an earth leakage circuit breaker.

This unit uses an inverter, so install the earth leakage circuit 
breaker that be capable of handling high harmonics in order to 
prevent malfunctioning of the earth leakage circuit breaker itself.

• Earth leakage circuit breaker which are especially for protecting 

ground-faults should be used in conjunction with main switch or 
fuse for use with wiring.

Note

• Electrical wiring must be done in accordance with the wiring dia-

grams and the description herein.

• Do not operate until refrigerant piping work is completed.

(If operated before complete the piping work, the compressor may 
be broken down.)

• Never remove thermistor, sensor or etc. when connecting power 

wiring and transmission wiring.
(If operated with thermistor, sensor or etc. removed, the compres-
sor may be broken down.)

• This product have reversed phase protection detector that only 

works when the power is turned on. If there exists black out or the 
power is turned on and off which the product is operating, attach 
a reversed phase protection circuit locally. Running the product in 
reversed phase may break the compressor and other parts.

• Attach the power wire securely. Introducing power with a missing 

N-phase or with a mistaken N-phase will break the unit.

• Never connect the power supply in reversed phase. 

The unit can not operate normally in reversed phase.
If you connect in reversed phase, replace two of the three phases.

• Make sure the electrical unbalance ratio is no greater than 2%. If 

it is larger than this, the unit’s lifespan will be reduced.
If the ratio exceeds 4%, the unit will shut down and an malfunction 
code will be displayed on the indoor remote controller.

• Connect the wire securely using designated wire and fix it with 

attached clamp without applying external pressure on the termi-
nal parts (terminal for power wiring, terminal for transmission wir-
ing and earth terminal). 

7-1 Power circuit, safety device, and cable 

requirements

• A power circuit (see the following table) must be provided for con-

nection of the unit. This circuit must be protected with the required 
safety devices, i.e. a main switch, a slow blow fuse on each phase 
and an earth leakage circuit breaker.

• When using residual current operated circuit breakers, be sure to 

use a high-speed type (1 second or less) 200mA rated residual 
operating current.

• Use copper conductors only.
• Use insulated wire for the power cord.
• Select the power supply cable type and size in accordance with 

relevant local and national regulations.

• Specifications for local wiring are in compliance with IEC60245.
• Use wire type H05VV when protected pipes are used.

Use wire type H07RN-F when protected pipes are not used.

Note

The above table indicates power specifications for standard combi-
nations (see 2. INTRODUCTION).

Point for attention regarding quality of the public electric power 
supply.

This equipment complies with respectively:

• EN/IEC 61000-3-11

*(1)

 provided that the system impedance Z

sys

 

is less than or equal to Z

max

 and

• EN/IEC 61000-3-12

*(2)

 provided that the short-circuit power S

sc

 is 

greater than or equal to the minimum S

sc

 value at the interface 

point between the user's supply and the public system. It is the 
responsibility of the installer or user of the equipment to ensure, 
by consultation with the distribution network operator if necessary, 
that the equipment is connected only to a supply with respec-
tively:

*(1) European/International Technical Standard setting the limits 

for voltage changes, voltage fluctuations and flicker in public 
low-voltage supply systems for equipment with rated current 
=75 A.

*(2) European/International Technical Standard setting the limits 

for harmonic currents produced by equipment connected to 
public low-voltage systems with input current >16 A and =75 
A per phase.

• Z

sys

 less than or equal to Z

max

 and

• S

sc

 greater than or equal to the minimum S

sc

 value.

• Heat Pump series (RQ(C)YQ)

Phase and

frequency

Voltage

Minimum

circuit amp.

Recom-

mended

fuses

RQYQ140PY1

φ

 3, 50Hz

380-415V

11.9A

15A

RQYQ180PY1

φ

 3, 50Hz

380-415V

17.2A

20A

RQCYQ280PY1

φ

 3, 50Hz

380-415V

23.8A

30A

RQCYQ360PY1

φ

 3, 50Hz

380-415V

34.5A

40A

RQCYQ460PY1

φ

 3, 50Hz

380-415V

41.0A

50A

RQCYQ500PY1

φ

 3, 50Hz

380-415V

46.4A

60A

RQCYQ540PY1

φ

 3, 50Hz

380-415V

51.7A

60A

RQCEQ280PY13

φ

 3, 50Hz

380-415V

23.8A

30A

RQCEQ360PY13

φ

 3, 50Hz

380-415V

34.5A

40A

RQCEQ460PY13

φ

 3, 50Hz

380-415V

41.0A

50A

RQCEQ500PY13

φ

 3, 50Hz

380-415V

46.4A

60A

RQCEQ540PY13

φ

 3, 50Hz

380-415V

51.7A

60A

RQCEQ636PY13

φ

 3, 50Hz

380-415V

55.5A

70A

RQCEQ712PY13

φ

 3, 50Hz

380-415V

64.9A

80A

RQCEQ744PY13

φ

 3, 50Hz

380-415V

66.1A

80A

RQCEQ816PY13

φ

 3, 50Hz

380-415V

72.7A

90A

RQCEQ848PY13

φ

 3, 50Hz

380-415V

74.0A

90A

Z

max

 (

)

Minimum 
S

sc

 value

RQYQ140

No requirements

906902

RQYQ180

No requirements 1179734

RQCYQ280=RQYQ140

No requirements 1813804

RQCYQ360=RQYQ180

No requirements 2359468

RQCYQ460=RQYQ180

No requirements 2993538

RQCYQ500=RQYQ180

No requirements 3266370

RQCYQ540=RQYQ180

No requirements 3539202

01_EN_3P226891-14T.fm  Page 15  Tuesday, September 30, 2014  7:48 PM

Summary of Contents for VRV III-Q RQYQ140PY1

Page 1: ...Manuale di installazione Condizionatore d aria a sistema VRVIII VRVIII Installatiehandleiding Airconditioner met VRVIII Systeem Manual de instala o Ar condicionado VRVIII System VRVIII Montaj elkitab...

Page 2: ...10 300 300 500 500 500 500 100 100 100 100 300 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 If installed as a serial installation 1 4 3 4 3 4 3 4 3 1 2 1 1 1 200 30...

Page 3: ...4 7 6 8 2 3 4 7 8 9 6 1 1 2 3 4 5 2 1 2 10 9 8 7 5 6 3 4 11 12 8 12 13 1 2 3 4 5 6 7 8 A BC A F1 F2 F1 F2 Q1 Q2 B C 3 1 1 A5P A1P TO IN D UNIT TO OUT D UNIT TO MULTI UNIT F1 F2 F1 F2 F1 F2 TO IN D UN...

Page 4: ...figure 30 2 1 1 1 7 3 4 4 5 5 10 9 9 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 6 6 8 2 1 2 A1P A5P A5P 1 2 3 4 5 1 2 3 4 5 6 7 4 8 8 L1 L2 L3 N 1 2 3 4 5 4 4 6 3 4 5 6 7 8 10 11 9 1 2 1 3 2 5 6 4 1 2 3 6 4 5 1 2...

Page 5: ...1 figure 31 2 figure 32 figure 33 1 2 3 12 13 14 4 5 11 9 8 7 6 10 10 10 10 8 8 8 7 6 5 4 9 10 2 3 1 9 9 9 8 7 6 5 10 4 1 11 3 2 1 5 6 7 3 1 2 3 4 1 2 3 4 5 00_CV_3P226891 14T fm Page 5 Tuesday Septe...

Page 6: ...hese instructions properly may result in personal injury or loss of life CAUTION Failure to observe these instructions properly may result in property damage or personal injury which may be serious de...

Page 7: ...stem clean dry and tightly sealed Read the chapter REFRIGERANT PIPING carefully and follow these procedures correctly A Clean and dry Strict measures must be taken to keep impurities including fluid d...

Page 8: ...Y13 14 0 36 4 16 units RQCEQ360PY13 17 8 46 2 20 units RQCEQ460PY13 22 5 58 5 26 units RQCEQ500PY13 25 0 65 0 29 units RQCEQ540PY13 28 0 72 8 33 units RQCEQ636PY13 30 8 80 0 36 units RQCEQ712PY13 34 5...

Page 9: ...h the unit s operation If necessary install some kind of obstruction to block the wind 6 The space around the unit is adequate for servicing and the min imum space for air inlet and air outlet is avai...

Page 10: ...method and work more than 4 per sons Refer to figure 5 1 Fork 2 Hole large 3 Transportation clasp yellow 4 Fixed screws of transportation clasp Refer to figure 6 1 Belt sling 2 Board 3 Hole large Ref...

Page 11: ...ipes The local interunit piping can be connected either forward or to the sides taken out through the bottom as shown in the figure 12 When passing out through the bottom use the knock hole in the bot...

Page 12: ...to use the accessory piping Make sure the onsite piping does not come into contact with other piping or the bottom frame or side panels of the unit Multi Systems RQEQ series cannot be used as an indep...

Page 13: ...ntil the split of the joint without wrapping any onsite piping around this area Over 500 mm of straight area can be maintained by connect ing at least 120 mm of onsite pipe straight to the joint Refer...

Page 14: ...ed with R410A How to select the REFNET joint When using REFNET joint at the first branch counted from the outdoor unit side Choose from the following table in accordance with the outdoor unit capacity...

Page 15: ...nt branching kit and indoor unit Section E Piping between refrigerant branching kit and indoor unit Section E Piping between outdoor unit and refrigerant branching kit Section A Piping between outdoor...

Page 16: ...liquid piping size at 6 4 Total length m of liquid piping size at 9 5 How to calculate the additional refrigerant to be charged Additional refrigerant to be charged R kg R should be rounded off in uni...

Page 17: ...ranch kit selection Refrigerant branch kit must be used to prescribed kit Use this table for kit selection How to select the REFNET joint How to select the REFNET header When using REFNET joint at the...

Page 18: ...from the following table in accordance with the total capacity of all the outdoor units connected upstream Indoor capacity index 56 kW 56 kW x 112 kW 112 kW x 160 kW 160 kW x 180 kW 180 kW x 224 kW 22...

Page 19: ...5 10m i 9 5 10m j 9 5 10m k 9 5 20m l 9 5 20m m 9 5 20m n 9 5 10m o 6 4 10m p 6 4 10m r 9 5 1m s 9 5 1m t 9 5 1m u 9 5 3m v 15 9 3m w 12 7 3m a b v w c n r u o p RQCEQ848PY13 112 8 915 8 9 kg Round of...

Page 20: ...t applying external pressure on the termi nal parts terminal for power wiring terminal for transmission wir ing and earth terminal 7 1 Power circuit safety device and cable requirements A power circui...

Page 21: ...tem only multi system or to COOL HEAT selector Heat Pump series RQ C YQ Refer to figure 21 1 1 Connection example for single system 2 Outdoor unit 3 COOL HEAT selector 4 To outdoor unit of other syste...

Page 22: ...then secure to prevent outside pressure being exerted on the ter minal board Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will strip the head and m...

Page 23: ...uum for an hour and make sure the pressure does not rise by monitoring with a vacuum gauge 9 PIPE INSULATION Insulation of pipes should be done after performing 8 AIR TIGHT TEST AND VACUUM DRYING Espe...

Page 24: ...e sure to use the correct tools The shutoff valve is not a back seat type If forced open it might break the valve body When using a service port use the charge hose After tightening the cap make sure...

Page 25: ...H2P will be lit on and the compressor will not operate In order to ensure uniform refrigerant distribution it may take up to around 10 minutes for the compressor to start up after the unit starting o...

Page 26: ...efrigerant is not need by calculation addi tional refrigerant charging operation will be need according to the installation conditions 11 2 2 Check operation Be sure to perform check operation after i...

Page 27: ...Suction gas side shutoff valve 7 HP LP gas side shutoff valve 8 Refrigerant charge port 9 Outdoor unit 10 To indoor unit 11 Field piping 2 If additional charging is required from the refrigerant tank...

Page 28: ...4 for longer than 5 seconds after connection of the refrigerant tank LED change indications then re start Use a refrigerant cylin der with sufficient amount of refrigerant The system stop operation fo...

Page 29: ...tops and a indoor remote controller indicates any defect repair the defect part according to Remote controller displays malfunction code Test operate again after the repair To test operate again press...

Page 30: ...eration manual of outdoor unit A3 Drain level error of BS unit Check the drain pump connected to BS unit E3 F4 F3 UF The shutoff valve of the outdoor unit is left closed Open the shutoff valve U1 The...

Page 31: ...of time before restarting the operation Once stopping the compressor will not restart in about 5 minutes even if the On Off button of the remote controller is pushed When the system operation is stopp...

Page 32: ...me of A B as a sin gle room or as the smallest room A Where there are no smaller room divisions B Where there is a room division but there is an opening between the rooms sufficiently large to permit...

Page 33: ...3P226891 14T EM14A007 1410 HT 00_CV_3P226891 14T fm Page 6 Tuesday September 16 2014 9 50 AM...

Reviews: