background image

English

2

• For wiring, use the specified wires and connect and fasten them 

firmly so that no external force from the wires may be applied to 
the terminal connections.
If the wires are not firmly connected and fastened, it may cause 
heating, fire or the like.

• When wiring the power supply and connecting the remote control-

ler wiring and transmission wiring, position the wires so that the 
EL.COMPO.BOX lid can be securely fastened.
Improper positioning of the EL.COMPO.BOX lid may result in 
electric shocks, fire or the terminals overheating.

• If refrigerant gas leaks during installation, ventilate the area 

immediately. 
Toxic gas may be produced if the refrigerant comes into contact 
with fire.

• After completing installation, check for refrigerant gas leakage. 

Toxic gas may be produced if the refrigerant gas leaks into the 
room and comes into contact with a source of fire, such as a fan 
heater, stove or cooker.

• Do not directly touch refrigerant that has leaked from refrigerant 

pipes or other areas, as there is a danger of frostbite.

• Do not allow children to climb on the outdoor unit and avoid plac-

ing objects on the unit. 
Injury may result if the unit becomes loose and falls.

CAUTION

• Carry out drain piping properly following this installation manual 

and insulate the pipe to prevent condensation.
Improper drain piping may result in indoor water leakage and 
property damage.

• Install the indoor, BS and outdoor units, power cord and connect-

ing wires at least 1 meter away from televisions or radios to pre-
vent picture interference and noise.
(Depending on the incoming signal strength, a distance of 1 meter 
may not be sufficient to eliminate noise.)

• Install the indoor unit and BS unit as far as possible from fluores-

cent lamps.
If a wireless kit is installed in a room where the electronic lighting 
type (inverter or rapid start types) fluorescent lamps exist, the 
transmitting distance of a remote controller may be shorter.

• Make sure to provide for adequate measures in order to prevent 

that the outdoor unit be used as a shelter by small animals. 
Small animals making contact with electrical parts can cause mal-
functions, smoke or fire. 
Please instruct the customer to keep the area around the unit 
clean.

• Do not install the air conditioner in the following locations: 

1. Where there is a high concentration of mineral oil spray or 

vapour (e.g. a kitchen). 
Plastic parts may deteriorate and cause parts to fall off or 
water to leak.

2. Where corrosive gas, such as sulphurous acid gas, is pro-

duced. 
Corrosion of copper pipes or brazed parts may occur and 
cause refrigerant leakage.

3. Where there is a machine that generates electromagnetic 

wave and where voltage fluctuation often occurs such as a fac-
tory.
Control system may malfunction and as a result the unit may 
not properly operate.

4. Where flammable gas may leak, where carbon fibre or ignit-

able dust is suspending in the air, or where volatile flammables 
such as paint thinner or gasoline are handled.
Operating the unit in such conditions may result in fire.

• The air conditioner is not intended for use in a potentially explo-

sive atmosphere.

1-2 Special notice of product

[CLASSIFICATION]

This air conditioner comes under the term “appliances not accessible 
to the general public”.

[EMC CHARACTERISTICS]

VRV

III

 System is a class A product. In a domestic environment this 

product may cause radio interference in which case the user may be 
required to take adequate measures.

[REFRIGERANT]
 VRV

III

 System use R410A refrigerant.

• The refrigerant R410A requires that strict precautions be 

observed for keeping the system clean, dry and tightly sealed. 
Read the chapter “REFRIGERANT PIPING” carefully and follow 
these procedures correctly.

A.Clean and dry

Strict measures must be taken to keep impurities (including 
fluid, dirt and dust) out of the system. 

B.Tightly sealed 

R410A contains no chlorine, does not destroy the ozone layer 
and so does not reduce the earth’s protection against harmful 
ultraviolet radiation. R410A will contribute only slightly to the 
greenhouse effect if released into the atmosphere. Therefore, 
sealing tightness is particularly important in installation. Care-
fully read the chapter “REFRIGERANT PIPING” and strictly 
observe the correct procedures.

• As the design pressure for local connection piping (suction·HP/LP 

gas pipe, gas pipe, and liquid pipe) is at least 3.3 MPa, it is possi-
ble to use existing piping (design pressure of at least 3.3 MPa,) 
but refer to "6. REFRIGERANT PIPING" and check that existing 
piping (including branch piping) is compatible with this unit in 
terms of materials and thickness and that it does not appear to be 
corroded.
Air tight test (3.3 MPa 24/h) to check the strength of existing piping 
and that it has no gas leaks.
If it is not possible to perform a pressure test, replace existing pip-
ing with piping rated at least 3.3 MPa. 

• Check that there has not been compressor malfunction, gas sup-

ply exhaustion, or similar issues that could be attributable to pipe 
problems in the past. If there have been any such problems, 
check that appropriate repairs were made, and if not, implement 
such repairs.

• Existing power supply and transmission wiring is also designed to 

be used with existing wiring, but check that specifications match 
and that parts (especially terminals) do not appear to have aged, 
and implement appropriate procedures (e.g. replacement).

• Since R410A is a mixed refrigerant, the required additional refrig-

erant must be charged in its liquid state. (If the system is charged 
with refrigerant in its gaseous state, due to composition change, 
the system will not function normally).

• The indoor unit is designed for R410A use. See the catalogue for 

indoor unit models that can be connected. (Normal operation is 
not possible when connecting units that are originally designed for 
other refrigerants.)

• The Heat Recovery Series (RQCEQ) cannot be connected to 

older BS units (BSVQ-M Type).

Total maximum refrigerant charge limits.

The total maximum refrigerant charge of a VRV

III

 system must be 

below 100kg, this to be in accordance with CE requirement 
(EN60335-2-40 standard).
This means that in case the total maximum refrigerant charge of the 
system (factory and additional charge) is equal to or more than 100kg 
you must divide your multiple outdoor system into smaller indepen-
dent systems, each containing less than 100kg refrigerant charge.
For factory charge, refer to the unit name plate.

Important information regarding the refrigerant used.

This product contains fluorinated greenhouse gases covered by the 
Kyoto Protocol. Do not vent gases into the atmosphere.
Refrigerant type : R410A

GWP 

(1)

 value :      1975

(1)

 GWP = global warming potential

Please fill in with indelible ink,

„

the factory refrigerant charge of the product,

„

the additional refrigerant amount charged onsite and

„

+

the total refrigerant charge on the refrigerant charge label

    supplied with the product.
     The filled out label must be adhered in the proximity of the product
    charging port (e.g. onto the inside of the service cover).

3

5

6

2

1

4

1

factory refrigerant charge of 
the product : see unit name 
plate

 (2)

2

additional refrigerant amount 
charged in the field

3 total refrigerant charge

4

Contains fluorinated green-
house gases covered by the 
Kyoto Protocol

5 outdoor unit

6

refrigerant cylinder and man-
ifold for charging

01_EN_3P226891-14T.fm  Page 2  Tuesday, September 30, 2014  7:48 PM

Summary of Contents for VRV III-Q RQYQ140PY1

Page 1: ...Manuale di installazione Condizionatore d aria a sistema VRVIII VRVIII Installatiehandleiding Airconditioner met VRVIII Systeem Manual de instala o Ar condicionado VRVIII System VRVIII Montaj elkitab...

Page 2: ...10 300 300 500 500 500 500 100 100 100 100 300 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 If installed as a serial installation 1 4 3 4 3 4 3 4 3 1 2 1 1 1 200 30...

Page 3: ...4 7 6 8 2 3 4 7 8 9 6 1 1 2 3 4 5 2 1 2 10 9 8 7 5 6 3 4 11 12 8 12 13 1 2 3 4 5 6 7 8 A BC A F1 F2 F1 F2 Q1 Q2 B C 3 1 1 A5P A1P TO IN D UNIT TO OUT D UNIT TO MULTI UNIT F1 F2 F1 F2 F1 F2 TO IN D UN...

Page 4: ...figure 30 2 1 1 1 7 3 4 4 5 5 10 9 9 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 6 6 8 2 1 2 A1P A5P A5P 1 2 3 4 5 1 2 3 4 5 6 7 4 8 8 L1 L2 L3 N 1 2 3 4 5 4 4 6 3 4 5 6 7 8 10 11 9 1 2 1 3 2 5 6 4 1 2 3 6 4 5 1 2...

Page 5: ...1 figure 31 2 figure 32 figure 33 1 2 3 12 13 14 4 5 11 9 8 7 6 10 10 10 10 8 8 8 7 6 5 4 9 10 2 3 1 9 9 9 8 7 6 5 10 4 1 11 3 2 1 5 6 7 3 1 2 3 4 1 2 3 4 5 00_CV_3P226891 14T fm Page 5 Tuesday Septe...

Page 6: ...hese instructions properly may result in personal injury or loss of life CAUTION Failure to observe these instructions properly may result in property damage or personal injury which may be serious de...

Page 7: ...stem clean dry and tightly sealed Read the chapter REFRIGERANT PIPING carefully and follow these procedures correctly A Clean and dry Strict measures must be taken to keep impurities including fluid d...

Page 8: ...Y13 14 0 36 4 16 units RQCEQ360PY13 17 8 46 2 20 units RQCEQ460PY13 22 5 58 5 26 units RQCEQ500PY13 25 0 65 0 29 units RQCEQ540PY13 28 0 72 8 33 units RQCEQ636PY13 30 8 80 0 36 units RQCEQ712PY13 34 5...

Page 9: ...h the unit s operation If necessary install some kind of obstruction to block the wind 6 The space around the unit is adequate for servicing and the min imum space for air inlet and air outlet is avai...

Page 10: ...method and work more than 4 per sons Refer to figure 5 1 Fork 2 Hole large 3 Transportation clasp yellow 4 Fixed screws of transportation clasp Refer to figure 6 1 Belt sling 2 Board 3 Hole large Ref...

Page 11: ...ipes The local interunit piping can be connected either forward or to the sides taken out through the bottom as shown in the figure 12 When passing out through the bottom use the knock hole in the bot...

Page 12: ...to use the accessory piping Make sure the onsite piping does not come into contact with other piping or the bottom frame or side panels of the unit Multi Systems RQEQ series cannot be used as an indep...

Page 13: ...ntil the split of the joint without wrapping any onsite piping around this area Over 500 mm of straight area can be maintained by connect ing at least 120 mm of onsite pipe straight to the joint Refer...

Page 14: ...ed with R410A How to select the REFNET joint When using REFNET joint at the first branch counted from the outdoor unit side Choose from the following table in accordance with the outdoor unit capacity...

Page 15: ...nt branching kit and indoor unit Section E Piping between refrigerant branching kit and indoor unit Section E Piping between outdoor unit and refrigerant branching kit Section A Piping between outdoor...

Page 16: ...liquid piping size at 6 4 Total length m of liquid piping size at 9 5 How to calculate the additional refrigerant to be charged Additional refrigerant to be charged R kg R should be rounded off in uni...

Page 17: ...ranch kit selection Refrigerant branch kit must be used to prescribed kit Use this table for kit selection How to select the REFNET joint How to select the REFNET header When using REFNET joint at the...

Page 18: ...from the following table in accordance with the total capacity of all the outdoor units connected upstream Indoor capacity index 56 kW 56 kW x 112 kW 112 kW x 160 kW 160 kW x 180 kW 180 kW x 224 kW 22...

Page 19: ...5 10m i 9 5 10m j 9 5 10m k 9 5 20m l 9 5 20m m 9 5 20m n 9 5 10m o 6 4 10m p 6 4 10m r 9 5 1m s 9 5 1m t 9 5 1m u 9 5 3m v 15 9 3m w 12 7 3m a b v w c n r u o p RQCEQ848PY13 112 8 915 8 9 kg Round of...

Page 20: ...t applying external pressure on the termi nal parts terminal for power wiring terminal for transmission wir ing and earth terminal 7 1 Power circuit safety device and cable requirements A power circui...

Page 21: ...tem only multi system or to COOL HEAT selector Heat Pump series RQ C YQ Refer to figure 21 1 1 Connection example for single system 2 Outdoor unit 3 COOL HEAT selector 4 To outdoor unit of other syste...

Page 22: ...then secure to prevent outside pressure being exerted on the ter minal board Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will strip the head and m...

Page 23: ...uum for an hour and make sure the pressure does not rise by monitoring with a vacuum gauge 9 PIPE INSULATION Insulation of pipes should be done after performing 8 AIR TIGHT TEST AND VACUUM DRYING Espe...

Page 24: ...e sure to use the correct tools The shutoff valve is not a back seat type If forced open it might break the valve body When using a service port use the charge hose After tightening the cap make sure...

Page 25: ...H2P will be lit on and the compressor will not operate In order to ensure uniform refrigerant distribution it may take up to around 10 minutes for the compressor to start up after the unit starting o...

Page 26: ...efrigerant is not need by calculation addi tional refrigerant charging operation will be need according to the installation conditions 11 2 2 Check operation Be sure to perform check operation after i...

Page 27: ...Suction gas side shutoff valve 7 HP LP gas side shutoff valve 8 Refrigerant charge port 9 Outdoor unit 10 To indoor unit 11 Field piping 2 If additional charging is required from the refrigerant tank...

Page 28: ...4 for longer than 5 seconds after connection of the refrigerant tank LED change indications then re start Use a refrigerant cylin der with sufficient amount of refrigerant The system stop operation fo...

Page 29: ...tops and a indoor remote controller indicates any defect repair the defect part according to Remote controller displays malfunction code Test operate again after the repair To test operate again press...

Page 30: ...eration manual of outdoor unit A3 Drain level error of BS unit Check the drain pump connected to BS unit E3 F4 F3 UF The shutoff valve of the outdoor unit is left closed Open the shutoff valve U1 The...

Page 31: ...of time before restarting the operation Once stopping the compressor will not restart in about 5 minutes even if the On Off button of the remote controller is pushed When the system operation is stopp...

Page 32: ...me of A B as a sin gle room or as the smallest room A Where there are no smaller room divisions B Where there is a room division but there is an opening between the rooms sufficiently large to permit...

Page 33: ...3P226891 14T EM14A007 1410 HT 00_CV_3P226891 14T fm Page 6 Tuesday September 16 2014 9 50 AM...

Reviews: