background image

English

26

If any malfunction codes other than the above are displayed, check 
the service manual for how to respond. 

12. ONSITE SETTINGS

Note

In the case of a multi system, all onsite settings should be made 
on the master unit. Settings made on sub units are invalid.
The outdoor unit to which the indoor unit transmission wire are 
connected is the master unit, and all other units are sub units.

12-1 Onsite Settings With the Power Off

If the COOL/HEAT selector was connected to the outdoor unit in  “

7. 

FIELD WIRING

”, set the dip switch (DS1) on the outdoor unit PC-

board (A1P) to “ON” (it is set to “OFF” when shipped from the fac-
tory).
For the position of the dip switch (DS1), see the “Service Precaution” 
label (see at the figure below) which is attached to the EL. COMPO. 
BOX lid.

WARNING

ELECTRIC SHOCK WARNING

Never perform with the power on.
There is a serious risk of electric shock if any live part is touched.

12-2 Onsite Settings With the Power On

Use the push button switches (BS1 through BS5) on the outdoor unit 
PC-board (A1P) to make the necessary onsite settings.
See the “Service Precaution” label on the EL. CONPO. BOX lid for 
details on the positions and operating method of the push button 
switches and on the onsite setting.
Make sure to record the setting on the accessory “REQUEST FOR 
THE INDICATION” label.

WARNING

ELECTRIC SHOCK WARNING

Use an insulated rod to operate the push buttons via the inspection 
door of EL. COMPO. BOX lid.
There is a risk of electric shock if you touch any live parts, since this 
operation must be performed with the power on.

13. TEST RUN

13-1 Before test run

• Make sure the following works are completed in accordance with 

the installation manual.

„

Piping work

„

Wiring work

„

Air tight test

„

Vacuum drying

„

Additional refrigerant charge

• Check that all work for the indoor unit are finished and there are 

no danger to operate.

13-2 Test Run

After check operation is completed, operate the unit normally and 
check the following.

(1)

Make sure the indoor and outdoor units are operating normally.

(2)

Operate each indoor unit one by one and make sure the corre-
sponding outdoor unit is also operating.

(3)

Check to see if cold (or hot) air is coming out from the indoor unit.

(4)

Push the fan direction and strength buttons on the remote control-
ler to see if they operate properly.

Note

• Heating is not possible if the outdoor temperature is 24°C or 

higher. Refer to the Operation manual.

• If a knocking sound can be heard in the liquid compression of the 

compressor, stop the unit immediately and then energize the 
crank case heater for a sufficient length of time before restarting 
the operation.

• Once stopping, the compressor will not restart in about 5 minutes 

even if the On/Off button of the remote controller is pushed.

• When the system operation is stopped by the remote controller, 

the outdoor units may continue operating for further 5 minutes at 
maximum.

• The outdoor unit fan may rotate at low speeds if the Night-time low 

noise setting or the External low noise level setting is made, but 
this is not a malfunction.

13-3 Checks After Test Run

Perform the following checks after the test run is complete.

• Record the contents of field setting.

Record them on the accessory “REQUEST FOR THE INDI-
CATION” label.
And attach the label on the back side of the front panel.

• Record the installation date.

Record the installation date on the accessory “REQUEST 
FOR THE INDICATION” label in accordance with the 
IEC60335-2-40.
And attach the label on the back side of the front panel.

Note

After the test run, when handing the unit over to the customer, make 
sure the EL.COMPO.BOX lid, the inspection door, and the unit casing 
are all attached.

14. CAUTION FOR REFRIGERANT LEAKS

(Points to note in connection with refrigerant leaks)
Introduction
The installer and system specialist shall secure safety against 
leakage according to local regulations or standards. The follow-
ing standards may be applicable if local regulations are not 
available.

The VRV System, like other air conditioning systems, uses R410A as 
refrigerant. R410A itself is an entirely safe non-toxic, non-combusti-
ble refrigerant. Nevertheless care must be taken to ensure that air 
conditioning facilities are installed in a room which is sufficiently 
large. This assures that the maximum concentration level of refriger-
ant gas is not exceeded, in the unlikely event of major leak in the sys-
tem and this in accordance to the local applicable regulations and 
standards.

P2

Check operation can-
not be continued by the 
low pressure drops.

Check the following.
• All shutoff valves are open.
• Refrigerant tank is connected.
• Valve of refrigerant tank is open.
• Inlet or outlet of indoor unit are not 

closed due to a foreign object.

P8
PA

Instruction to perform addi-
tional refrigerant charging 
during check operation 
(not a malfunction).

Make the check operation by 
"

11-2 Procedure of check oper-

ation

".

E2, E3

E3 is activated, so On/Off 
button is pressed on the 
remote controller, but this 
does not turn E3 off. Or E2 
is activated.
In case of above, there is a 
malfunction of the com-
pressor in the outdoor unit.

Measure the insulation resis-
tance of the compressor to check 
the condition of the compressor.

Malfunction 

code

Installation error

Remedial action

Inspection door

[Service Precaution] label

EL. COMPO BOX lid

01_EN_3P226891-14T.fm  Page 26  Tuesday, September 30, 2014  7:48 PM

Summary of Contents for VRV III-Q RQYQ140PY1

Page 1: ...Manuale di installazione Condizionatore d aria a sistema VRVIII VRVIII Installatiehandleiding Airconditioner met VRVIII Systeem Manual de instala o Ar condicionado VRVIII System VRVIII Montaj elkitab...

Page 2: ...10 300 300 500 500 500 500 100 100 100 100 300 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 If installed as a serial installation 1 4 3 4 3 4 3 4 3 1 2 1 1 1 200 30...

Page 3: ...4 7 6 8 2 3 4 7 8 9 6 1 1 2 3 4 5 2 1 2 10 9 8 7 5 6 3 4 11 12 8 12 13 1 2 3 4 5 6 7 8 A BC A F1 F2 F1 F2 Q1 Q2 B C 3 1 1 A5P A1P TO IN D UNIT TO OUT D UNIT TO MULTI UNIT F1 F2 F1 F2 F1 F2 TO IN D UN...

Page 4: ...figure 30 2 1 1 1 7 3 4 4 5 5 10 9 9 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 6 6 8 2 1 2 A1P A5P A5P 1 2 3 4 5 1 2 3 4 5 6 7 4 8 8 L1 L2 L3 N 1 2 3 4 5 4 4 6 3 4 5 6 7 8 10 11 9 1 2 1 3 2 5 6 4 1 2 3 6 4 5 1 2...

Page 5: ...1 figure 31 2 figure 32 figure 33 1 2 3 12 13 14 4 5 11 9 8 7 6 10 10 10 10 8 8 8 7 6 5 4 9 10 2 3 1 9 9 9 8 7 6 5 10 4 1 11 3 2 1 5 6 7 3 1 2 3 4 1 2 3 4 5 00_CV_3P226891 14T fm Page 5 Tuesday Septe...

Page 6: ...hese instructions properly may result in personal injury or loss of life CAUTION Failure to observe these instructions properly may result in property damage or personal injury which may be serious de...

Page 7: ...stem clean dry and tightly sealed Read the chapter REFRIGERANT PIPING carefully and follow these procedures correctly A Clean and dry Strict measures must be taken to keep impurities including fluid d...

Page 8: ...Y13 14 0 36 4 16 units RQCEQ360PY13 17 8 46 2 20 units RQCEQ460PY13 22 5 58 5 26 units RQCEQ500PY13 25 0 65 0 29 units RQCEQ540PY13 28 0 72 8 33 units RQCEQ636PY13 30 8 80 0 36 units RQCEQ712PY13 34 5...

Page 9: ...h the unit s operation If necessary install some kind of obstruction to block the wind 6 The space around the unit is adequate for servicing and the min imum space for air inlet and air outlet is avai...

Page 10: ...method and work more than 4 per sons Refer to figure 5 1 Fork 2 Hole large 3 Transportation clasp yellow 4 Fixed screws of transportation clasp Refer to figure 6 1 Belt sling 2 Board 3 Hole large Ref...

Page 11: ...ipes The local interunit piping can be connected either forward or to the sides taken out through the bottom as shown in the figure 12 When passing out through the bottom use the knock hole in the bot...

Page 12: ...to use the accessory piping Make sure the onsite piping does not come into contact with other piping or the bottom frame or side panels of the unit Multi Systems RQEQ series cannot be used as an indep...

Page 13: ...ntil the split of the joint without wrapping any onsite piping around this area Over 500 mm of straight area can be maintained by connect ing at least 120 mm of onsite pipe straight to the joint Refer...

Page 14: ...ed with R410A How to select the REFNET joint When using REFNET joint at the first branch counted from the outdoor unit side Choose from the following table in accordance with the outdoor unit capacity...

Page 15: ...nt branching kit and indoor unit Section E Piping between refrigerant branching kit and indoor unit Section E Piping between outdoor unit and refrigerant branching kit Section A Piping between outdoor...

Page 16: ...liquid piping size at 6 4 Total length m of liquid piping size at 9 5 How to calculate the additional refrigerant to be charged Additional refrigerant to be charged R kg R should be rounded off in uni...

Page 17: ...ranch kit selection Refrigerant branch kit must be used to prescribed kit Use this table for kit selection How to select the REFNET joint How to select the REFNET header When using REFNET joint at the...

Page 18: ...from the following table in accordance with the total capacity of all the outdoor units connected upstream Indoor capacity index 56 kW 56 kW x 112 kW 112 kW x 160 kW 160 kW x 180 kW 180 kW x 224 kW 22...

Page 19: ...5 10m i 9 5 10m j 9 5 10m k 9 5 20m l 9 5 20m m 9 5 20m n 9 5 10m o 6 4 10m p 6 4 10m r 9 5 1m s 9 5 1m t 9 5 1m u 9 5 3m v 15 9 3m w 12 7 3m a b v w c n r u o p RQCEQ848PY13 112 8 915 8 9 kg Round of...

Page 20: ...t applying external pressure on the termi nal parts terminal for power wiring terminal for transmission wir ing and earth terminal 7 1 Power circuit safety device and cable requirements A power circui...

Page 21: ...tem only multi system or to COOL HEAT selector Heat Pump series RQ C YQ Refer to figure 21 1 1 Connection example for single system 2 Outdoor unit 3 COOL HEAT selector 4 To outdoor unit of other syste...

Page 22: ...then secure to prevent outside pressure being exerted on the ter minal board Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will strip the head and m...

Page 23: ...uum for an hour and make sure the pressure does not rise by monitoring with a vacuum gauge 9 PIPE INSULATION Insulation of pipes should be done after performing 8 AIR TIGHT TEST AND VACUUM DRYING Espe...

Page 24: ...e sure to use the correct tools The shutoff valve is not a back seat type If forced open it might break the valve body When using a service port use the charge hose After tightening the cap make sure...

Page 25: ...H2P will be lit on and the compressor will not operate In order to ensure uniform refrigerant distribution it may take up to around 10 minutes for the compressor to start up after the unit starting o...

Page 26: ...efrigerant is not need by calculation addi tional refrigerant charging operation will be need according to the installation conditions 11 2 2 Check operation Be sure to perform check operation after i...

Page 27: ...Suction gas side shutoff valve 7 HP LP gas side shutoff valve 8 Refrigerant charge port 9 Outdoor unit 10 To indoor unit 11 Field piping 2 If additional charging is required from the refrigerant tank...

Page 28: ...4 for longer than 5 seconds after connection of the refrigerant tank LED change indications then re start Use a refrigerant cylin der with sufficient amount of refrigerant The system stop operation fo...

Page 29: ...tops and a indoor remote controller indicates any defect repair the defect part according to Remote controller displays malfunction code Test operate again after the repair To test operate again press...

Page 30: ...eration manual of outdoor unit A3 Drain level error of BS unit Check the drain pump connected to BS unit E3 F4 F3 UF The shutoff valve of the outdoor unit is left closed Open the shutoff valve U1 The...

Page 31: ...of time before restarting the operation Once stopping the compressor will not restart in about 5 minutes even if the On Off button of the remote controller is pushed When the system operation is stopp...

Page 32: ...me of A B as a sin gle room or as the smallest room A Where there are no smaller room divisions B Where there is a room division but there is an opening between the rooms sufficiently large to permit...

Page 33: ...3P226891 14T EM14A007 1410 HT 00_CV_3P226891 14T fm Page 6 Tuesday September 16 2014 9 50 AM...

Reviews: