Piping between outdoor unit (*2) and refrigerant branch kit (part A).

Choose from the following table in accordance with the outdoor unit system capacity type.

Piping between refrigerant branch kits.

Piping between refrigerant branch kit and BS unit.

Piping between BS unit and refrigerant branch kit.

Choose from the following table in accordance with the total capacity type of all the

indoor units connected downstream.

*1 Connection piping must not exceed the refrigerant piping size between outdoor

     unit and refrigerant branch kit (part A).

*2 When selecting 2 pipes line (gas pipe and liquid pipe), use suction gas pipe

     column for gas pipe and liquid pipe column for liquid pipe.

Piping between refrigerant branch kit, BS unit and indoor unit.

Match to the size of the connection piping on the indoor unit.

Pipe size selection

Piping between outdoor unit

multi connection piping kit

and outdoor unit (part C)

Piping between outdoor unit multi 

connection piping kits (part B)

Piping between outdoor unit and 

refrigerant branch kit (part A)

Refer to the diagram below and select the appropriate 

piping from the tables on the right.

Independent

unit 1

Independent

unit 2

Independent

unit 3

Independent

unit 4

Piping between outdoor unit multi connection piping kit and outdoor unit (part C).

Choose from the following table in accordance with the capacity type of

the outdoor unit connected.

Piping between outdoor unit multi connection piping kits (part B).

Choose from the following table in accordance with the total capacity of all

the outdoor units connected upstream.

Indoor capacity 

index

< 56 kW

  56 kW 

≤ 

x< 112 kW

112 kW 

≤ 

x< 160 kW

160 kW 

≤ 

x< 180 kW

180 kW 

≤ 

x< 224 kW

224 kW 

≤ 

x< 330 kW

330 kW 

≤ 

x< 370 kW

370 kW 

≤ 

x< 470 kW

470 kW 

≤ 

x< 530 kW

530 kW 

≤ 

x< 710 kW

710 kW 

≤ 

x< 784 kW

784 kW 

≤ 

x< 1010 kW

1010 kW 

φ

12.7

φ

15.9

φ

19.1

φ

22.2

φ

25.4

φ

28.6

φ

34.9

φ

15.9

φ

19.1

φ

25.4

φ

28.6

φ

34.9

φ

41.3

φ

9.5

φ

12.7

φ

15.9

φ

19.4

φ

25.4

φ

28.6

φ

12.7

φ

15.9

φ

19.1

φ

22.2

φ

25.4

φ

28.6

φ

6.4

φ

9.5

φ

12.7

φ

15.9

φ

19.1

φ

9.5

φ

12.7

φ

15.9

φ

19.1

φ

22.2

Standard 

size

Maximum 

size

Maximum 

size

Standard 

size

Maximum 

size

Standard 

size

Suction gas pipe

HP/LP gas pipe

Liquid pipe

Indoor capacity 

index

Q20

Q25

Q32

Q40

Q50

Q63

Q80

Q100

Q125

Q200

Q250

φ

12.7

φ

15.9

φ

19.1

φ

22.2

φ

15.9

φ

19.1

φ

25.4

φ

28.6

φ

6.4

φ

9.5

φ

9.5

φ

12.7

φ

15.9

Standard size

Maximum 

size

Standard size

Maximum 

size

Suction gas pipe

Liquid pipe

Piping size (O.D.)

Piping size (O.D.)

Q280 type

Q360 type

Q460 type

Q500 type

Q540 type

Q636 type

Q712 type

Q744 type

Q816 type

Q848 type

Outdoor unit

capacity type

Q140 type

Q180·212 type

Model name of

outdoor unit

system

Piping size (O. D.)

φ

22.2

φ

25.4

φ

28.6

φ

34.9

φ

9.5

φ

12.7

φ

15.9

φ

19.1

φ

12.7

φ

15.9

φ

19.1

φ

22.2

φ

28.6

φ

34.9

φ

41.3

φ

19.1

φ

22.2

φ

25.4

φ

28.6

φ

22.2

φ

25.4

φ

28.6

Suction gas pipe

Standard

size

Maximum

size

Standard

size

Maximum

size

Standard

size

Maximum

size

HP/LP gas pipe

Liquid pipe

Outdoor unit

capacity type

280·320

360~392

424

500~532

604~636

Piping size (O. D.)

Suction gas pipe

φ

22.2

φ

25.4

φ

28.6

HP/LP gas pipe

φ

19.1

φ

22.2

φ

25.4

Liquid pipe

φ

9.5

φ

12.7

φ

15.9

Piping size (O. D.)

Suction gas pipe

φ

15.9

φ

19.1

HP/LP gas pipe

φ

12.7

φ

15.9

Liquid pipe

φ

9.5

 (unit : mm)

 (unit : mm)

 (unit : mm)

 (unit : mm)

01_EN_3P226891-14T.fm  Page 13  Tuesday, September 30, 2014  7:48 PM

Summary of Contents for VRV III-Q RQYQ140PY1

Page 1: ...Manuale di installazione Condizionatore d aria a sistema VRVIII VRVIII Installatiehandleiding Airconditioner met VRVIII Systeem Manual de instala o Ar condicionado VRVIII System VRVIII Montaj elkitab...

Page 2: ...10 300 300 500 500 500 500 100 100 100 100 300 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 If installed as a serial installation 1 4 3 4 3 4 3 4 3 1 2 1 1 1 200 30...

Page 3: ...4 7 6 8 2 3 4 7 8 9 6 1 1 2 3 4 5 2 1 2 10 9 8 7 5 6 3 4 11 12 8 12 13 1 2 3 4 5 6 7 8 A BC A F1 F2 F1 F2 Q1 Q2 B C 3 1 1 A5P A1P TO IN D UNIT TO OUT D UNIT TO MULTI UNIT F1 F2 F1 F2 F1 F2 TO IN D UN...

Page 4: ...figure 30 2 1 1 1 7 3 4 4 5 5 10 9 9 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 6 6 8 2 1 2 A1P A5P A5P 1 2 3 4 5 1 2 3 4 5 6 7 4 8 8 L1 L2 L3 N 1 2 3 4 5 4 4 6 3 4 5 6 7 8 10 11 9 1 2 1 3 2 5 6 4 1 2 3 6 4 5 1 2...

Page 5: ...1 figure 31 2 figure 32 figure 33 1 2 3 12 13 14 4 5 11 9 8 7 6 10 10 10 10 8 8 8 7 6 5 4 9 10 2 3 1 9 9 9 8 7 6 5 10 4 1 11 3 2 1 5 6 7 3 1 2 3 4 1 2 3 4 5 00_CV_3P226891 14T fm Page 5 Tuesday Septe...

Page 6: ...hese instructions properly may result in personal injury or loss of life CAUTION Failure to observe these instructions properly may result in property damage or personal injury which may be serious de...

Page 7: ...stem clean dry and tightly sealed Read the chapter REFRIGERANT PIPING carefully and follow these procedures correctly A Clean and dry Strict measures must be taken to keep impurities including fluid d...

Page 8: ...Y13 14 0 36 4 16 units RQCEQ360PY13 17 8 46 2 20 units RQCEQ460PY13 22 5 58 5 26 units RQCEQ500PY13 25 0 65 0 29 units RQCEQ540PY13 28 0 72 8 33 units RQCEQ636PY13 30 8 80 0 36 units RQCEQ712PY13 34 5...

Page 9: ...h the unit s operation If necessary install some kind of obstruction to block the wind 6 The space around the unit is adequate for servicing and the min imum space for air inlet and air outlet is avai...

Page 10: ...method and work more than 4 per sons Refer to figure 5 1 Fork 2 Hole large 3 Transportation clasp yellow 4 Fixed screws of transportation clasp Refer to figure 6 1 Belt sling 2 Board 3 Hole large Ref...

Page 11: ...ipes The local interunit piping can be connected either forward or to the sides taken out through the bottom as shown in the figure 12 When passing out through the bottom use the knock hole in the bot...

Page 12: ...to use the accessory piping Make sure the onsite piping does not come into contact with other piping or the bottom frame or side panels of the unit Multi Systems RQEQ series cannot be used as an indep...

Page 13: ...ntil the split of the joint without wrapping any onsite piping around this area Over 500 mm of straight area can be maintained by connect ing at least 120 mm of onsite pipe straight to the joint Refer...

Page 14: ...ed with R410A How to select the REFNET joint When using REFNET joint at the first branch counted from the outdoor unit side Choose from the following table in accordance with the outdoor unit capacity...

Page 15: ...nt branching kit and indoor unit Section E Piping between refrigerant branching kit and indoor unit Section E Piping between outdoor unit and refrigerant branching kit Section A Piping between outdoor...

Page 16: ...liquid piping size at 6 4 Total length m of liquid piping size at 9 5 How to calculate the additional refrigerant to be charged Additional refrigerant to be charged R kg R should be rounded off in uni...

Page 17: ...ranch kit selection Refrigerant branch kit must be used to prescribed kit Use this table for kit selection How to select the REFNET joint How to select the REFNET header When using REFNET joint at the...

Page 18: ...from the following table in accordance with the total capacity of all the outdoor units connected upstream Indoor capacity index 56 kW 56 kW x 112 kW 112 kW x 160 kW 160 kW x 180 kW 180 kW x 224 kW 22...

Page 19: ...5 10m i 9 5 10m j 9 5 10m k 9 5 20m l 9 5 20m m 9 5 20m n 9 5 10m o 6 4 10m p 6 4 10m r 9 5 1m s 9 5 1m t 9 5 1m u 9 5 3m v 15 9 3m w 12 7 3m a b v w c n r u o p RQCEQ848PY13 112 8 915 8 9 kg Round of...

Page 20: ...t applying external pressure on the termi nal parts terminal for power wiring terminal for transmission wir ing and earth terminal 7 1 Power circuit safety device and cable requirements A power circui...

Page 21: ...tem only multi system or to COOL HEAT selector Heat Pump series RQ C YQ Refer to figure 21 1 1 Connection example for single system 2 Outdoor unit 3 COOL HEAT selector 4 To outdoor unit of other syste...

Page 22: ...then secure to prevent outside pressure being exerted on the ter minal board Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will strip the head and m...

Page 23: ...uum for an hour and make sure the pressure does not rise by monitoring with a vacuum gauge 9 PIPE INSULATION Insulation of pipes should be done after performing 8 AIR TIGHT TEST AND VACUUM DRYING Espe...

Page 24: ...e sure to use the correct tools The shutoff valve is not a back seat type If forced open it might break the valve body When using a service port use the charge hose After tightening the cap make sure...

Page 25: ...H2P will be lit on and the compressor will not operate In order to ensure uniform refrigerant distribution it may take up to around 10 minutes for the compressor to start up after the unit starting o...

Page 26: ...efrigerant is not need by calculation addi tional refrigerant charging operation will be need according to the installation conditions 11 2 2 Check operation Be sure to perform check operation after i...

Page 27: ...Suction gas side shutoff valve 7 HP LP gas side shutoff valve 8 Refrigerant charge port 9 Outdoor unit 10 To indoor unit 11 Field piping 2 If additional charging is required from the refrigerant tank...

Page 28: ...4 for longer than 5 seconds after connection of the refrigerant tank LED change indications then re start Use a refrigerant cylin der with sufficient amount of refrigerant The system stop operation fo...

Page 29: ...tops and a indoor remote controller indicates any defect repair the defect part according to Remote controller displays malfunction code Test operate again after the repair To test operate again press...

Page 30: ...eration manual of outdoor unit A3 Drain level error of BS unit Check the drain pump connected to BS unit E3 F4 F3 UF The shutoff valve of the outdoor unit is left closed Open the shutoff valve U1 The...

Page 31: ...of time before restarting the operation Once stopping the compressor will not restart in about 5 minutes even if the On Off button of the remote controller is pushed When the system operation is stopp...

Page 32: ...me of A B as a sin gle room or as the smallest room A Where there are no smaller room divisions B Where there is a room division but there is an opening between the rooms sufficiently large to permit...

Page 33: ...3P226891 14T EM14A007 1410 HT 00_CV_3P226891 14T fm Page 6 Tuesday September 16 2014 9 50 AM...

Reviews: