Heat Recovery series (RQ(C)EQ)

Example of connection

(Connection of 8 indoor units)

Indoor

unit

side

Outdoor

unit

side

12

BS

Unit

Suction gas pipe

HP/LP gas pipe

Liquid pipe

(Suction) gas pipe

Liquid pipe

Piping from outdoor unit to BS unit

Piping from BS unit to indoor unit or 

Piping from Refrigerant branch kit to

indoor unit used as cooling only

(Bold):3 pipes

(Thin):2 pipes

(*1) “        ” Indicate the Outdoor unit multi

                  connection piping kit.

(*2) In case of multi outdoor system, re-read

       “outdoor unit” to “the first Outdoor unit

       multi connection piping kit” as seen from

       the indoor unit.

Branch with REFNET joint

Branch with REFNET joint and header

Branch with REFNET header

Multi

outdoor

system

(RQCEQ)

Maximum

allowable

length

Allowable

height

difference

Allowable length after the branch

Between outdoor unit (*2)

and indoor unit

Between first outdoor unit multi

connection piping kit and outdoor unit

(in case of multi system)

Between outdoor and indoor units

Between indoor and indoor units

Between outdoor and outdoor units

Actual pipe

length

Equivalent

length

Actual and

Equivalent

pipe length

Actual pipe

length

Difference in height

Difference in height

Difference in height

Total extension length

Pipe length between outdoor unit (*2) and indoor unit 

 120m

Example  8  : a + b + c + d + e + s 

 120m

Example  6  : a + b +    

 120m,  8  : a + m + n + p 

 120m

Example  8  : a + o 

 120m

Total piping length from outdoor unit (*2) to all indoor unit 

 300m

Actual pipe length from first outdoor unit multi connection piping kit to outdoor unit 

 10m

Equivalent pipe length from first outdoor unit multi connection piping kit to outdoor unit 

 13m

Actual pipe length from first refrigerant branch kit (either REFNET joint or REFNET header) to indoor unit 

 40m

Example  8  : b + c + d + e + s 

 40m

Difference in height between outdoor unit and indoor unit (H1) 

 50m (Max 40m if the outdoor unit is below)

Difference in height between adjacent indoor units (H2) 

 15m

Difference in height between adjacent outdoor units (H3) 

 5m

Outdoor unit

 10m

(Equivalent length 

 13m)

u + s 

 10m

(Equivalent length 

 13m)

u + t 

 10m

(Equivalent length 

 13m)

Example  6  : b +   

 40m, 8: m + n + p 

 40m

Example  8  : o 

 40m

B1 ~ B4

: BS Unit

1 ~ 6 

Indoor unit (Cool/Heat selection possible)

7 ,  8

: Indoor unit (Cooling only)

B1 ~ B5

: BS Unit

1 ~ 4 ,  7 ,  8

Indoor unit (Cool/Heat selection possible)

5 ,  6

: Indoor unit (Cooling only)

B1 ~ B4

: BS Unit

1 ~ 6

: Indoor unit (Cool/Heat selection possible)

7 ,  8

: Indoor unit (Cooling only)

r

t

s

u

1

2

Outdoor unit multi connection piping kit and

Refrigerant branch kit selection

 Refrigerant branch kit must be used to 

prescribed kit.

 Use this table for kit selection.

How to select the REFNET joint

How to select the REFNET header

When using REFNET joint at the first branch counted from the outdoor unit side,

choose from the following table in accordance with the outdoor unit capacity type.

(Example : REFNET joint A)

Choose from the following table in accordance with the total capacity index of all

the indoor units connected below the REFNET header.

250 type indoor unit can not be connected below the REFNET header.

How to select the outdoor unit multi connection piping kit

(This is required when the system is multi outdoor unit system.)

Choose from the following table in accordance with the number of outdoor units.

Choose the REFNET joints other than the first branch from the following table in accordance

with the total capacity index of all the indoor units connected below the REFNET joint.

Outdoor unit capacity type

Q280 type

Q360~712 type

Q744 type ~

Indoor unit total capacity index

x < 200

200 

 x < 290

290 

 x < 640

640 

 x

Refrigerant branch kit name

KHRP25A33T

KHRKHRP25M72TP

KHRKHRP25M73TP

3 pipes

KHRP25A22T

KHRP25A33T

KHRKHRP25M72TP

KHRKHRP25M73TP

2 pipes

KHRP26A22T

KHRP26A33T

KHRP26A72T

Refrigerant branch kit name

Indoor unit total capacity index

x < 200

200 

 x < 290

290 

 x < 640

640 

 x

Number of outdoor unit

2 units

3 units

4 units

Connecting piping kit name

BHFP26P36C

BHFP26P63C

BHFP26P84C

3 pipes

KHRP25M33H

KHRKHRP25M72HP

KHRKHRP25M73HP

2 pipes

KHRP26M22H or KHRP26M33H

KHRP26M33H

KHRP26M72H

KHRKHRP26M73HP

Refrigerant branch kit name

Example for indoor units

connected downstream

Example REFNET joint C : Indoor units  5  +  6  +  7  +  8

Example REFNET joint B : Indoor units  7  +  8

Example REFNET header : Indoor units  1  +  2  +  3  +  4  +  5  +  6

Example REFNET header :

Indoor units  1  +  2  +  3  +  4  +  5  +  6  +  7  +  8

Outdoor unit

REFNET joint (A~G)

First outdoor unit multi connection piping kit

Outdoor unit

Outdoor unit

REFNET joint (A, B)

REFNET header

REFNET header

Equivalent pipe length between outdoor unit (*2) and indoor unit 

 150m (Note 1)

(Assume equivalent pipe length of REFNET joint to be 0.5m, that of REFNET header to be 1m, that of BSVQ100·160, BSQ100·160, and

 BS1Q10·16 to be 4m, that of BSVQ250,

BSQ250, and BS1Q25 to be 6m for calculation purposes.)

(In case of BSV4Q100PV1 and BSV6Q100PV1 (combined type BS unit), calculate at 4m per 1 unit.)

(In case of BS4Q14AV1 and BS6Q14AV1 (combined type BS unit), calculate at 6m per 1 unit.)

(In case of BS8·10·12·16Q14AV1 (combined type BS unit), calculate at 10m per 1 unit.)

01_EN_3P226891-14T.fm  Page 12  Tuesday, September 30, 2014  7:48 PM

Summary of Contents for VRV III-Q RQYQ140PY1

Page 1: ...Manuale di installazione Condizionatore d aria a sistema VRVIII VRVIII Installatiehandleiding Airconditioner met VRVIII Systeem Manual de instala o Ar condicionado VRVIII System VRVIII Montaj elkitab...

Page 2: ...10 300 300 500 500 500 500 100 100 100 100 300 If installed as a single unit Pattern 1 Pattern 2 Pattern 1 Pattern 2 Pattern 3 If installed as a serial installation 1 4 3 4 3 4 3 4 3 1 2 1 1 1 200 30...

Page 3: ...4 7 6 8 2 3 4 7 8 9 6 1 1 2 3 4 5 2 1 2 10 9 8 7 5 6 3 4 11 12 8 12 13 1 2 3 4 5 6 7 8 A BC A F1 F2 F1 F2 Q1 Q2 B C 3 1 1 A5P A1P TO IN D UNIT TO OUT D UNIT TO MULTI UNIT F1 F2 F1 F2 F1 F2 TO IN D UN...

Page 4: ...figure 30 2 1 1 1 7 3 4 4 5 5 10 9 9 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 6 6 8 2 1 2 A1P A5P A5P 1 2 3 4 5 1 2 3 4 5 6 7 4 8 8 L1 L2 L3 N 1 2 3 4 5 4 4 6 3 4 5 6 7 8 10 11 9 1 2 1 3 2 5 6 4 1 2 3 6 4 5 1 2...

Page 5: ...1 figure 31 2 figure 32 figure 33 1 2 3 12 13 14 4 5 11 9 8 7 6 10 10 10 10 8 8 8 7 6 5 4 9 10 2 3 1 9 9 9 8 7 6 5 10 4 1 11 3 2 1 5 6 7 3 1 2 3 4 1 2 3 4 5 00_CV_3P226891 14T fm Page 5 Tuesday Septe...

Page 6: ...hese instructions properly may result in personal injury or loss of life CAUTION Failure to observe these instructions properly may result in property damage or personal injury which may be serious de...

Page 7: ...stem clean dry and tightly sealed Read the chapter REFRIGERANT PIPING carefully and follow these procedures correctly A Clean and dry Strict measures must be taken to keep impurities including fluid d...

Page 8: ...Y13 14 0 36 4 16 units RQCEQ360PY13 17 8 46 2 20 units RQCEQ460PY13 22 5 58 5 26 units RQCEQ500PY13 25 0 65 0 29 units RQCEQ540PY13 28 0 72 8 33 units RQCEQ636PY13 30 8 80 0 36 units RQCEQ712PY13 34 5...

Page 9: ...h the unit s operation If necessary install some kind of obstruction to block the wind 6 The space around the unit is adequate for servicing and the min imum space for air inlet and air outlet is avai...

Page 10: ...method and work more than 4 per sons Refer to figure 5 1 Fork 2 Hole large 3 Transportation clasp yellow 4 Fixed screws of transportation clasp Refer to figure 6 1 Belt sling 2 Board 3 Hole large Ref...

Page 11: ...ipes The local interunit piping can be connected either forward or to the sides taken out through the bottom as shown in the figure 12 When passing out through the bottom use the knock hole in the bot...

Page 12: ...to use the accessory piping Make sure the onsite piping does not come into contact with other piping or the bottom frame or side panels of the unit Multi Systems RQEQ series cannot be used as an indep...

Page 13: ...ntil the split of the joint without wrapping any onsite piping around this area Over 500 mm of straight area can be maintained by connect ing at least 120 mm of onsite pipe straight to the joint Refer...

Page 14: ...ed with R410A How to select the REFNET joint When using REFNET joint at the first branch counted from the outdoor unit side Choose from the following table in accordance with the outdoor unit capacity...

Page 15: ...nt branching kit and indoor unit Section E Piping between refrigerant branching kit and indoor unit Section E Piping between outdoor unit and refrigerant branching kit Section A Piping between outdoor...

Page 16: ...liquid piping size at 6 4 Total length m of liquid piping size at 9 5 How to calculate the additional refrigerant to be charged Additional refrigerant to be charged R kg R should be rounded off in uni...

Page 17: ...ranch kit selection Refrigerant branch kit must be used to prescribed kit Use this table for kit selection How to select the REFNET joint How to select the REFNET header When using REFNET joint at the...

Page 18: ...from the following table in accordance with the total capacity of all the outdoor units connected upstream Indoor capacity index 56 kW 56 kW x 112 kW 112 kW x 160 kW 160 kW x 180 kW 180 kW x 224 kW 22...

Page 19: ...5 10m i 9 5 10m j 9 5 10m k 9 5 20m l 9 5 20m m 9 5 20m n 9 5 10m o 6 4 10m p 6 4 10m r 9 5 1m s 9 5 1m t 9 5 1m u 9 5 3m v 15 9 3m w 12 7 3m a b v w c n r u o p RQCEQ848PY13 112 8 915 8 9 kg Round of...

Page 20: ...t applying external pressure on the termi nal parts terminal for power wiring terminal for transmission wir ing and earth terminal 7 1 Power circuit safety device and cable requirements A power circui...

Page 21: ...tem only multi system or to COOL HEAT selector Heat Pump series RQ C YQ Refer to figure 21 1 1 Connection example for single system 2 Outdoor unit 3 COOL HEAT selector 4 To outdoor unit of other syste...

Page 22: ...then secure to prevent outside pressure being exerted on the ter minal board Use an appropriate screwdriver for tightening the terminal screws A screwdriver with a small head will strip the head and m...

Page 23: ...uum for an hour and make sure the pressure does not rise by monitoring with a vacuum gauge 9 PIPE INSULATION Insulation of pipes should be done after performing 8 AIR TIGHT TEST AND VACUUM DRYING Espe...

Page 24: ...e sure to use the correct tools The shutoff valve is not a back seat type If forced open it might break the valve body When using a service port use the charge hose After tightening the cap make sure...

Page 25: ...H2P will be lit on and the compressor will not operate In order to ensure uniform refrigerant distribution it may take up to around 10 minutes for the compressor to start up after the unit starting o...

Page 26: ...efrigerant is not need by calculation addi tional refrigerant charging operation will be need according to the installation conditions 11 2 2 Check operation Be sure to perform check operation after i...

Page 27: ...Suction gas side shutoff valve 7 HP LP gas side shutoff valve 8 Refrigerant charge port 9 Outdoor unit 10 To indoor unit 11 Field piping 2 If additional charging is required from the refrigerant tank...

Page 28: ...4 for longer than 5 seconds after connection of the refrigerant tank LED change indications then re start Use a refrigerant cylin der with sufficient amount of refrigerant The system stop operation fo...

Page 29: ...tops and a indoor remote controller indicates any defect repair the defect part according to Remote controller displays malfunction code Test operate again after the repair To test operate again press...

Page 30: ...eration manual of outdoor unit A3 Drain level error of BS unit Check the drain pump connected to BS unit E3 F4 F3 UF The shutoff valve of the outdoor unit is left closed Open the shutoff valve U1 The...

Page 31: ...of time before restarting the operation Once stopping the compressor will not restart in about 5 minutes even if the On Off button of the remote controller is pushed When the system operation is stopp...

Page 32: ...me of A B as a sin gle room or as the smallest room A Where there are no smaller room divisions B Where there is a room division but there is an opening between the rooms sufficiently large to permit...

Page 33: ...3P226891 14T EM14A007 1410 HT 00_CV_3P226891 14T fm Page 6 Tuesday September 16 2014 9 50 AM...

Reviews: