5. Unpacking and Placing the Unit
!
Make sure the unit is installed level on a sufficiently strong base to prevent vibration and
noise.
!
Secure the unit to its base using foundation bolts. (Use four commercially available M12-
type foundation bolts, nuts, and washers.)
!
The foundation bolts should be inserted 20 mm.
!
Make sure the base under the unit extended more than 765mm behind the unit.
!
The height of the base should be at least 150mm from the floor.
!
The unit must be installed on a solid longitudinal foundation (steel beam frame
or concrete) as indicated in figure below.
1.Foundation bolt point (
φ
15 dia. : 4 positions)
2.Depth of product
3.Shape of indoor unit’s support leg and foundation bolt positions
Do not use stands to support the corners
Caution
1. Prepare a water drainage channel around the foundation to drain waste water from around
the unit.
2. If the unit is to be installed on a roof, check the strength of the roof and its drainage facilities
first.
3. If the unit is to be installed on a frame, install the waterproofing board within a distance of
150mm under the unit in order to prevent infiltration of water coming from under the unit.
[Precaution]
!
When installing on a roof, make sure the roof floor is strong enough and be sure to water-
proof all work.
!
Make sure the area around the machine drains properly by setting up drainage grooves
around the foundation.
(Drain water is sometimes discharged from the outdoor unit when it is running.)
!
Block all gaps in the holes for passing out piping and wiring using sealing material (locally
procured). (Small animals may enter the machine.)
Model
AB
Q5 type
635
497
Q8 · 10 type
930
792
Q12 · 14 · 16 type
1240
1102
20
722-737
80
80
765
A
B
1
2
3
Do not use stands to
support the corners.
Summary of Contents for VRV II Series
Page 6: ...Si39 303 iv Table of Contents...
Page 31: ...Si39 303 Installation General Information 25 Flaring Procedure...
Page 124: ...Appendix Si39 303 118 General Information 3P114237A...
Page 141: ...Si39 303 Appendix General Information 135 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 4D040338A...
Page 142: ...Appendix Si39 303 136 General Information RXYQ14MY1B RXYQ16MY1B 4D040339A...
Page 144: ...Appendix Si39 303 138 General Information 7 11 Wiring Diagrams 7 11 1 Outdoor Unit RXYQ5MY1B...
Page 145: ...Si39 303 Appendix General Information 139 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 3D038582...
Page 146: ...Appendix Si39 303 140 General Information RXYQ14MY1B RXYQ16MY1B 3D038058...
Page 147: ...Si39 303 Appendix General Information 141 7 11 2 Field Wiring RXYQ5 16MY1B 3D040746...
Page 148: ...Appendix Si39 303 142 General Information RXYQ18 32MY1B 3D040747...
Page 149: ...Si39 303 Appendix General Information 143 RXYQ34 48MY1B 3D040748...
Page 158: ...Appendix Si39 303 152 General Information...
Page 180: ...Refrigerant Piping Si39 303 174 Installation Manual...
Page 226: ...Troubleshooting Si39 303 220 Operation Manual...