Si39-303
Field Wiring
Installation Manual
183
7.4
Examples
System example
Field line connection
L1, L2, L3, N-phase of the power cord should be clamped to the safety catch using the included
clamp material.
The green and yellow striped wrapped wires should be used for grounding.
1. Power supply
(200 V, Three-phase)
2. Branch switch, overcurrent breaker
3. Grounding wire
4. Earth leakage breaker
5. Section A
6. Attach insulation sleeves.
7. Power supply terminal block
8. Grounding wire
9. Retain the ground wires along with the power wires using the accessory clamps (1).
10. Retain the respective power wires - L1, L2, L3 and N phases - to the bracket individually using the
accessory clamps (1).
11. Grounding wire
12. When wiring, do not allow the ground wires to contact the compressor lead wires. If the wires contact each
other, adverse effects may occur to other units.
13. When connecting two wires to one terminal, ensure that the crimp-style terminals face with each other
back to back.
Moreover, make sure that the wire of the smaller gauge is located above.
At the same time, retain the power wires to the plastic bracket using the accessory clamps (1).
14. Terminal block
15. Crimp-style terminal
16. Wire gauge: Small
17. Wire gauge: Large
18. Plastic bracket
1.
Field power supply
2.
Main switch
3.
Earth leak detector
4.
Fuse
5.
Cool / heat selector
6.
Remote controller
power supply wiring (sheathed cable)
transmission wiring (sheathed cable)
1
2
3
3
4
4
5
6
1
2
3
5
4
6
7
14
13
15
16
17
18
8
9
10
11
12
L 1
L 2
L 3
N
Summary of Contents for VRV II Series
Page 6: ...Si39 303 iv Table of Contents...
Page 31: ...Si39 303 Installation General Information 25 Flaring Procedure...
Page 124: ...Appendix Si39 303 118 General Information 3P114237A...
Page 141: ...Si39 303 Appendix General Information 135 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 4D040338A...
Page 142: ...Appendix Si39 303 136 General Information RXYQ14MY1B RXYQ16MY1B 4D040339A...
Page 144: ...Appendix Si39 303 138 General Information 7 11 Wiring Diagrams 7 11 1 Outdoor Unit RXYQ5MY1B...
Page 145: ...Si39 303 Appendix General Information 139 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 3D038582...
Page 146: ...Appendix Si39 303 140 General Information RXYQ14MY1B RXYQ16MY1B 3D038058...
Page 147: ...Si39 303 Appendix General Information 141 7 11 2 Field Wiring RXYQ5 16MY1B 3D040746...
Page 148: ...Appendix Si39 303 142 General Information RXYQ18 32MY1B 3D040747...
Page 149: ...Si39 303 Appendix General Information 143 RXYQ34 48MY1B 3D040748...
Page 158: ...Appendix Si39 303 152 General Information...
Page 180: ...Refrigerant Piping Si39 303 174 Installation Manual...
Page 226: ...Troubleshooting Si39 303 220 Operation Manual...