Si39-303
Product Outline
General Information
7
Connectable indoor unit
Indoor unit capacity
Use the above tables to determine the capacities of indoor units to be connected. Make sure the
total capacity of indoor units connected to each outdoor unit is within the specified value (kW).
!
The total capacity of connected indoor units must be within a range of 50 to 130% of the
rated capacity of the outdoor unit.
!
In some models, it is not possible to connect the maximum number of connectable indoor
units. Select models so the total capacity of connected indoor units conforms to the
specification.
Type
Model Name
Power Supply
Ceiling mounted
cassette type
(Double flow)
FXCQ
20M
25M
32M
40M
50M
63M
80M
—
125M
—
—
VE
Ceiling mounted
cassette type
(Multi flow)
600×600
FXZQ
20M
25M
32M
40M
50M
—
—
—
—
—
—
Ceiling mounted
cassette type
(Multi flow)
FXFQ
—
25M
32M
40M
50M
63M
80M
100M 125M
—
—
Ceiling mounted
cassette corner
FXKQ
—
25M
32M
40M
—
63M
—
—
—
—
—
Ceiling mounted
built-in type
FXSQ
20M
25M
32M
40M
50M
63M
80M
100M 125M
—
—
Ceiling mounted
duct type
FXMQ
—
—
—
40M
50M
63M
80M
100M 125M 200M 250M
Ceiling
suspended type
FXHQ
—
—
32M
—
—
63M
—
100M
—
—
—
Wall mounted
type
FXAQ
20M
25M
32M
40M
50M
63M
—
—
—
—
—
Floor standing
type
FXLQ
20M
25M
32M
40M
50M
63M
—
—
—
—
—
Concealed Floor
standing type
FXNQ
20M
25M
32M
40M
50M
63M
—
—
—
—
—
New refrigerant model code
P20
type
P25
type
P32
type
P40
type
P50
type
P63
type
P80
type
P100
type
P125
type
P200
type
P250
type
Selecting model capacity
2.2
kW
2.8
kW
3.5
kW
4.5
kW
5.6
kW
7.0
kW
9.0
kW
11.2
kW
14.0
kW
22.4
kW
28.0
kW
Equivalent output
0.8HP
1HP
1.25HP
1.6HP
2.0HP
2.5HP
3.2HP
4HP
5HP
8HP
10HP
Summary of Contents for VRV II Series
Page 6: ...Si39 303 iv Table of Contents...
Page 31: ...Si39 303 Installation General Information 25 Flaring Procedure...
Page 124: ...Appendix Si39 303 118 General Information 3P114237A...
Page 141: ...Si39 303 Appendix General Information 135 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 4D040338A...
Page 142: ...Appendix Si39 303 136 General Information RXYQ14MY1B RXYQ16MY1B 4D040339A...
Page 144: ...Appendix Si39 303 138 General Information 7 11 Wiring Diagrams 7 11 1 Outdoor Unit RXYQ5MY1B...
Page 145: ...Si39 303 Appendix General Information 139 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 3D038582...
Page 146: ...Appendix Si39 303 140 General Information RXYQ14MY1B RXYQ16MY1B 3D038058...
Page 147: ...Si39 303 Appendix General Information 141 7 11 2 Field Wiring RXYQ5 16MY1B 3D040746...
Page 148: ...Appendix Si39 303 142 General Information RXYQ18 32MY1B 3D040747...
Page 149: ...Si39 303 Appendix General Information 143 RXYQ34 48MY1B 3D040748...
Page 158: ...Appendix Si39 303 152 General Information...
Page 180: ...Refrigerant Piping Si39 303 174 Installation Manual...
Page 226: ...Troubleshooting Si39 303 220 Operation Manual...