Si39-303
Test Operation
General Information
73
Air Flow
Adjustment -
Ceiling Height
Make the following setting according to the ceiling height. The setting position No. is set to “01”
at the factory.
!
In the Case of FXAQ, FXHQ
!
In the Case of FXFQ25~80
!
In the Case of FXFQ100~125
Air Flow Direction
Setting
Set the air flow direction of indoor units as given in the table below. (Set when optional air outlet
blocking pad has been installed.) The second code No. is factory set to “01.”
Setting Table
Setting of Air
Flow Direction
Adjustment
Only the model FXKQ has the function.
When only the front-flow is used, sets yes/no of the swing flap operation of down-flow.
Setting Table
Mode No.
Setting Switch
No.
Setting Position
No.
Setting
13(23)
0
01
Wall-mounted type : Standard
02
Wall-mounted type : Slight increase
03
Wall-mounted type : Normal increase
Mode
No.
First
code
No.
Second
code
No.
Setting
Ceiling height
4-way Outlets
3-way Outlets
2-way Outlets
13 (23)
0
01
Standard (N)
Lower than 2.7 m Lower than 3.0 m Lower than 3.5 m
02
High Ceiling (H)
Lower than 3.0 m Lower than 3.3 m Lower than 3.8 m
03
Higher Ceiling (S) Lower than 3.5 m Lower than 3.5 m
—
Mode
No.
First
code
No.
Second
code
No.
Setting
Ceiling height
4-way Outlets
3-way Outlets
2-way Outlets
13 (23)
0
01
Standard (N)
Lower than 3.2 m Lower than 3.6 m Lower than 4.2 m
02
High Ceiling (H)
Lower than 3.6 m Lower than 4.0 m Lower than 4.2 m
03
Higher Ceiling (S) Lower than 4.2 m Lower than 4.2 m
—
Mode No.
First Code No.
Second Code
No.
Setting
13 (23)
1
01
F : 4-direction air flow
02
T : 3-direction air flow
03
W : 2-direction air flow
Setting
Mode No.
First Code No.
Second Code No.
Down-flow operation: Yes
13 (23)
3
01
Down-flow operation: No
02
Summary of Contents for VRV II Series
Page 6: ...Si39 303 iv Table of Contents...
Page 31: ...Si39 303 Installation General Information 25 Flaring Procedure...
Page 124: ...Appendix Si39 303 118 General Information 3P114237A...
Page 141: ...Si39 303 Appendix General Information 135 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 4D040338A...
Page 142: ...Appendix Si39 303 136 General Information RXYQ14MY1B RXYQ16MY1B 4D040339A...
Page 144: ...Appendix Si39 303 138 General Information 7 11 Wiring Diagrams 7 11 1 Outdoor Unit RXYQ5MY1B...
Page 145: ...Si39 303 Appendix General Information 139 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 3D038582...
Page 146: ...Appendix Si39 303 140 General Information RXYQ14MY1B RXYQ16MY1B 3D038058...
Page 147: ...Si39 303 Appendix General Information 141 7 11 2 Field Wiring RXYQ5 16MY1B 3D040746...
Page 148: ...Appendix Si39 303 142 General Information RXYQ18 32MY1B 3D040747...
Page 149: ...Si39 303 Appendix General Information 143 RXYQ34 48MY1B 3D040748...
Page 158: ...Appendix Si39 303 152 General Information...
Page 180: ...Refrigerant Piping Si39 303 174 Installation Manual...
Page 226: ...Troubleshooting Si39 303 220 Operation Manual...