Si39-303
Installation
General Information
21
(The nature and amount of the extraneous material inside the pipe can be checked during flushing by
placing a rag lightly over the end of the pipe. In the unlikely case that even a small quantity of moisture is
found then the inside of the pipe should be dried out thoroughly.)
Action:
1. Flush the inside of the pipe with nitrogen gas. (Until such time as the moisture disappears.)
2. Carry out a thorough vacuum drying operation. (See page 31)
Close the main valve on the nitrogen cylinder.
Repeat the above operation for unit B.
When the liquid pipe operations have been completed then do the same with the gas pipes.
Choice of
Materials for
Refrigerant
Piping
a) Refrigerant piping
!
The piping used must meet the requirements of the JIS standard or equivalent. (Size, material,
thickness, etc.)
Specification:
Oxidized phosphorous seamless copper pipe
!
Long pipe lengths or coiled pipe (copper pipe with heat insulation coating) should be used to avoid the
necessity for frequent brazing.
(* Make sure the thickness and material shall be selected in accordance with following table.)
!
Size of Refrigerant Piping
*The thickness and material shall be selected in accordance with local code.
b) Brazed joints and special branches
1. General use (L bend joint, socket joint, T joint, etc.)
!
Joints must meet the requirements of the relevant JIS standard. (Size, materials, thickness, etc.)
2. Special branches
!
The Daikin outdoor unit multi connection kit, REFNET joint, REFNET header or Reducing socket should
be used.
Example: R410A RXYQ-M Series
Refer detail of DAIKIN REFNET joint and REFNET header on page 126.
Outside Diameter (mm)
Material
φ
6.4
0
φ
9.5
0
φ
12.7
0
φ
15.9
0
φ
19.1
1/2H
φ
22.2
1/2H
φ
25.4
1/2H
φ
28.6
1/2H
φ
31.8
1/2H
φ
34.9
1/2H
φ
38.1
1/2H
φ
41.3
1/2H
Summary of Contents for VRV II Series
Page 6: ...Si39 303 iv Table of Contents...
Page 31: ...Si39 303 Installation General Information 25 Flaring Procedure...
Page 124: ...Appendix Si39 303 118 General Information 3P114237A...
Page 141: ...Si39 303 Appendix General Information 135 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 4D040338A...
Page 142: ...Appendix Si39 303 136 General Information RXYQ14MY1B RXYQ16MY1B 4D040339A...
Page 144: ...Appendix Si39 303 138 General Information 7 11 Wiring Diagrams 7 11 1 Outdoor Unit RXYQ5MY1B...
Page 145: ...Si39 303 Appendix General Information 139 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 3D038582...
Page 146: ...Appendix Si39 303 140 General Information RXYQ14MY1B RXYQ16MY1B 3D038058...
Page 147: ...Si39 303 Appendix General Information 141 7 11 2 Field Wiring RXYQ5 16MY1B 3D040746...
Page 148: ...Appendix Si39 303 142 General Information RXYQ18 32MY1B 3D040747...
Page 149: ...Si39 303 Appendix General Information 143 RXYQ34 48MY1B 3D040748...
Page 158: ...Appendix Si39 303 152 General Information...
Page 180: ...Refrigerant Piping Si39 303 174 Installation Manual...
Page 226: ...Troubleshooting Si39 303 220 Operation Manual...