Test Operation
Si39-303
86
General Information
c. Monitor mode
Setting item 0 Display contents of “Number of units for sequential start,
and others”
No.
Setting item
LED display
Data display
H1P
H2P
H3P
H4 P
H5P
H6P
H7P
0
Number of units for sequential
starting, and others
9 7 7 7 7 7 7
See below
1
C/H unified address
9 7 7 7 7 7 8
Lower 6 digits
2
Low noise/demand address
9 7 7 7 7 8 7
3
Not used
9 7 7 7 7 8 8
4Airnet address
9 7 7 7 8 7 7
5
Number of connected indoor units
9 7 7 7 8 7 8
6
Number of connected BS units
9 7 7 7 8 8 7
7
Number of connected zone units
(excluding outdoor and BS unit)
9 7 7 7 8 8 8
8
Number of outdoor units
9 7 7 8 7 7 7
9
Number of connected BS units
9 7 7 8 7 7 8
Lower 4 digits:
upper
10
Number of connected BS units
9 7 7 8 7 8 7
Lower 4 digits:
lower
11
Number of zone units (excluding
outdoor and BS unit)
9 7 7 8 7 8 8
Lower 6 digits
12
Number of terminal blocks
9 7 7 8 8 7 7
Lower 4 digits:
upper
13
Number of terminal blocks
9 7 7 8 8 7 8
Lower 4 digits:
lower
Number of units for sequential
start
1 unit
9 7 7 7 7 7 7
2 units
9 7 9 7 7 7 7
3 units
9 7 8 7 7 7 7
EMG operation /backup
operation setting
ON
9 7 7 8 7 7 7
OFF
9 7 7 7 7 7 7
Defrost select setting
Short
9 7 7 7 8 7 7
Medium
9 7 7 7 9 7 7
Long
9 7 7 7 7 7 7
Te setting
H
9 7 7 7 7 8 7
M
9 7 7 7 7 9 7
L
9 7 7 7 7 7 7
Tc setting
H
9 7 7 7 7 7 8
M
9 7 7 7 7 7 9
L
9 7 7 7 7 7 7
<Selection of setting item>
<Confirmation on setting contents>
To enter the monitor mode, push the
MODE button (BS1) when in
“Setting mode 1”.
Push the SET button (BS2) and set
the LED display to a setting item.
Push the RETURN button (BS3) to
display different data of set items.
Push the RETURN button (BS3) and
switches to the initial status of
“Monitor mode”.
∗
Push the MODE button (BS1) and
returns to “Setting mode 1”.
(V2765)
Summary of Contents for VRV II Series
Page 6: ...Si39 303 iv Table of Contents...
Page 31: ...Si39 303 Installation General Information 25 Flaring Procedure...
Page 124: ...Appendix Si39 303 118 General Information 3P114237A...
Page 141: ...Si39 303 Appendix General Information 135 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 4D040338A...
Page 142: ...Appendix Si39 303 136 General Information RXYQ14MY1B RXYQ16MY1B 4D040339A...
Page 144: ...Appendix Si39 303 138 General Information 7 11 Wiring Diagrams 7 11 1 Outdoor Unit RXYQ5MY1B...
Page 145: ...Si39 303 Appendix General Information 139 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 3D038582...
Page 146: ...Appendix Si39 303 140 General Information RXYQ14MY1B RXYQ16MY1B 3D038058...
Page 147: ...Si39 303 Appendix General Information 141 7 11 2 Field Wiring RXYQ5 16MY1B 3D040746...
Page 148: ...Appendix Si39 303 142 General Information RXYQ18 32MY1B 3D040747...
Page 149: ...Si39 303 Appendix General Information 143 RXYQ34 48MY1B 3D040748...
Page 158: ...Appendix Si39 303 152 General Information...
Page 180: ...Refrigerant Piping Si39 303 174 Installation Manual...
Page 226: ...Troubleshooting Si39 303 220 Operation Manual...