Si39-303
Appendix
General Information
117
7.6
How to calculate the additional refrigerant to be charged
Additional refrigerant to be charged R (Kg)
R should be rounded off in units of 0.1Kg.
Note:
If a negative result is gotten for R from the formula at right, no refrigerant needs to be added.
Note:
The amount of refrigerant to be added to the unit should be written on the included “Added Refrigerant”
plate and attached to the rear side of the front cover. Refer next page.
*Example for refrigerant branch using refnet joint and refnet header for RXYQ34MY1B
R=
+
+
+
+
×0.35
Total length (m)
of liquid piping
size at ø22.2
×0.25
Total length (m)
of liquid piping
size at ø19.1
×0.17
Total length (m)
of liquid piping
size at ø15.9
×0.11
Total length (m)
of liquid piping
size at ø12.7
+
-
×0.054
Total length (m)
of liquid piping
size at ø9.5
×0.022
Total length (m)
of liquid piping
size at ø6.4
Model name
RXYQ5 ~ 16MY1B
RXYQ18 ~ 32MY1B
RXYQ34 ~ 48MY1B
Amount of refrigerant
0 kg
3 kg
6 kg
H1
H2
a
i
b
Outdoor unit
c
d
e
f
g
h
1
2
3
4
5
6
Indoor units (1-8)
Refnet header
k
j
7
8
H3
REFNET joint (A • B)
A
B
If the outdoor unit is
RXYQ34MY1B and the
piping lengths are as at
right
R=
a
b
j
c+d+e+f
g+h+j+k
+
30×0.25
a: ø19.1 × 30m
b: ø15.9 × 10m
c: ø 9.5 × 10m
d: ø 9.5 × 10m
e: ø 9.5 × 10m
f : ø 9.5 × 10m
g: ø 6.4 × 10m
h: ø 6.4 × 20m
i : ø12.7 × 10m
j : ø6.4 × 10m
k: ø6.4 × 9m
+
10×0.17
+
10×0.11
+
40×0.054
- 6 = 7.358
40×0.022
7.5
ò
Summary of Contents for VRV II Series
Page 6: ...Si39 303 iv Table of Contents...
Page 31: ...Si39 303 Installation General Information 25 Flaring Procedure...
Page 124: ...Appendix Si39 303 118 General Information 3P114237A...
Page 141: ...Si39 303 Appendix General Information 135 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 4D040338A...
Page 142: ...Appendix Si39 303 136 General Information RXYQ14MY1B RXYQ16MY1B 4D040339A...
Page 144: ...Appendix Si39 303 138 General Information 7 11 Wiring Diagrams 7 11 1 Outdoor Unit RXYQ5MY1B...
Page 145: ...Si39 303 Appendix General Information 139 RXYQ8MY1B RXYQ10MY1B RXYQ12MY1B 3D038582...
Page 146: ...Appendix Si39 303 140 General Information RXYQ14MY1B RXYQ16MY1B 3D038058...
Page 147: ...Si39 303 Appendix General Information 141 7 11 2 Field Wiring RXYQ5 16MY1B 3D040746...
Page 148: ...Appendix Si39 303 142 General Information RXYQ18 32MY1B 3D040747...
Page 149: ...Si39 303 Appendix General Information 143 RXYQ34 48MY1B 3D040748...
Page 158: ...Appendix Si39 303 152 General Information...
Page 180: ...Refrigerant Piping Si39 303 174 Installation Manual...
Page 226: ...Troubleshooting Si39 303 220 Operation Manual...