Troubleshooting by Indication on the Remote Controller
Si39-504
220
Troubleshooting
Troubleshooting
(V2822)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Is
indoor - outdoor
and outdoor - outdoor unit
transmission wiring
normal?
Supply 220~240 V.
Replace the fuse.
Fix the indoor/outdoor or
outdoor/outdoor unit
transmission wiring.
Push and hold the RESET
button on the outdoor unit PC
board for 5 seconds.
Replace the outdoor unit PC
Board (A1P).
YES
YES
NO
YES
Replace the indoor unit PC
Board.
Push and hold the RESET
button on the master outdoor
unit PC Board for 5 seconds.
Fix the indoor/outdoor or
outdoor/outdoor unit
transmission wiring.
YES
NO
NO
YES
Has
the indoor
or outdoor unit PC
board been replaced,
or has the indoor - outdoor
or outdoor - outdoor unit
transmission wiring
been
modified?
All
indoor unit
remote controllers of the
same refrigerant system
display
"U4".
NO
Outdoor
unit PC board
microcomputer monitor
(HAP) blinks.
NO
NO
NO
Operation
ready lamp (H2P) is
blinking.
Lamp does
not go off for 12 minutes
or more.
Is indoor
- outdoor and outdoor -
outdoor unit transmission
wiring normal?
YES
The fuse on
the outdoor unit's PC
board is burnt.
Replace the transformer.
replacement
Replace outdoor unit PC
board. (A1P)
NO
The
secondary voltage
of the transformer is
about 22 V.
NO
The
voltage between
terminals L1 and N of the
outdoor unit PC board
is 220~240 V.
∗
The unit will not operate for
up to 12 minutes.
Reset the power supply.
YES
YES
YES
NO
YES
Summary of Contents for VRV II RXYQ5MATL
Page 53: ...Specifications Si39 504 42 Specifications...
Page 115: ...Outline of Control Indoor Unit Si39 504 104 Function...
Page 161: ...Field Setting Si39 504 150 Test Operation...
Page 172: ...Si39 504 Troubleshooting by Remote Controller Troubleshooting 161...
Page 266: ...Si39 504 Piping Diagrams Appendix 255 RXYQ8MA 10MA 12MAYL E TL E 3D048033A...
Page 267: ...Piping Diagrams Si39 504 256 Appendix RXYQ14MA 16MAYL E TL E 3D048034A...
Page 271: ...Wiring Diagrams for Reference Si39 504 260 Appendix RXYQ8MA 10MA 12MAYL E 3D047088C...
Page 272: ...Si39 504 Wiring Diagrams for Reference Appendix 261 RXYQ14MA 16MAYL E 3D047089C...
Page 273: ...Wiring Diagrams for Reference Si39 504 262 Appendix 2 1 2 RXYQ MATL E RXYQ5MATL E 3D049059A...
Page 274: ...Si39 504 Wiring Diagrams for Reference Appendix 263 RXYQ8MA 10MA 12MATL E 3D049060A...
Page 275: ...Wiring Diagrams for Reference Si39 504 264 Appendix RXYQ14MA 16MATL E 3D049061A...
Page 283: ...Wiring Diagrams for Reference Si39 504 272 Appendix FXCQ40M 50M 80M 125MVE 3D039557A...
Page 285: ...Wiring Diagrams for Reference Si39 504 274 Appendix FXKQ25M 32M 40M 63MVE 3D039564B...
Page 289: ...Wiring Diagrams for Reference Si39 504 278 Appendix FXMQ40M 50M 63M 80M 100M 125MVE 3D039620B...
Page 290: ...Si39 504 Wiring Diagrams for Reference Appendix 279 FXMQ200M 250MVE 3D039621B...
Page 291: ...Wiring Diagrams for Reference Si39 504 280 Appendix FXHQ32M 63M 100MVE 3D039801D...
Page 292: ...Si39 504 Wiring Diagrams for Reference Appendix 281 FXAQ20M 25M 32MVE 40M 50M 63MVE 3D034206C...
Page 309: ...Selection of Pipe Size Joints and Header Si39 504 298 Appendix Note 1...
Page 315: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 504 304 Appendix...