Field Setting
Si39-504
132
Test Operation
No.
Setting item display
Setting condition display
Setting item
MODE
H1P
TEST
H2P
C/H selection
Low
noise
H6P
Demand
H7P
IND
H3P
Master
H4P
Slave
H5P
∗
Factory set
1
Cool / Heat
Unified address
8
7
7
7
7
7
8
Address
0
8777777
∗
Binary number
1
8777778
(6 digits)
~
31
8788888
2
Low noise/demand
address
8
7
7
7
7
8
7
Address
0
8777777
∗
Binary number
1
8777778
(6 digits)
~
31
8788888
5
Indoor forced fan H
8
7
7
7
8
7
8
Normal operation
8777778
∗
Indoor forced fan H
8777787
6
Indoor forced
operation
8
7
7
7
8
8
7
Normal operation
8777778
∗
Indoor forced operation
8777787
8
Te setting
8
7
7
8
7
7
7
High
8777877
Normal (factory setting)
8777787
∗
Low
8777778
9
Tc setting
8
7
7
8
7
7
8
High
8777877
Normal (factory setting)
8777787
∗
Low
8777778
10
Defrost changeover
setting
8
7
7
8
7
8
7
Quick defrost
8777877
Normal (factory setting)
8777787
∗
Slow defrost
8777778
11
Sequential operation
setting
8
7
7
8
7
8
8
OFF
8777778
ON
8777787
∗
12
External low noise/
demand setting
8
7
7
8
8
7
7
External low noise/demand:
NO
8777778
∗
External low noise/demand:
YES
8777787
13 Airnet address
8
7
7
8
8
7
8
Address
0
8777777
∗
Binary number
1
8777778
(6 digits)
~
63
8888888
16
Setting of hot water
heater
8
7
8
7
7
7
7
OFF
8777778
∗
ON
8777787
18
High static pressure
setting
8
7
8
7
7
8
7
High static pressure setting:
OFF
8777778
∗
High static pressure setting:
ON
8777787
19
Emergency
operation
(STD compressor is
inhibited to operate.)
8
7
8
7
7
8
8
OFF
8777777
∗
STD 1, 2 operation: Inhibited
8777778
STD 2 operation: Inhibited
8777787
20
Additional refrigerant
charging operation
setting
8
7
8
7
8
7
7
Refrigerant charging: OFF
8777778
∗
Refrigerant charging: ON
8777787
21
Refrigerant
recovery/vacuuming
mode setting
8
7
8
7
8
7
8
Refrigerant recovery / vacuuming: OFF
8777778
∗
Refrigerant recovery / vacuuming: ON
8777787
22
Night-time low noise
setting
8
7
8
7
8
8
7
OFF
8777777
∗
Level 1 (outdoor fan with 8 step or lower)
8777778
Level 2 (outdoor fan with 7 step or lower)
8777787
Level 3 (outdoor fan with 6 step or lower)
8777788
Summary of Contents for VRV II RXYQ5MATL
Page 53: ...Specifications Si39 504 42 Specifications...
Page 115: ...Outline of Control Indoor Unit Si39 504 104 Function...
Page 161: ...Field Setting Si39 504 150 Test Operation...
Page 172: ...Si39 504 Troubleshooting by Remote Controller Troubleshooting 161...
Page 266: ...Si39 504 Piping Diagrams Appendix 255 RXYQ8MA 10MA 12MAYL E TL E 3D048033A...
Page 267: ...Piping Diagrams Si39 504 256 Appendix RXYQ14MA 16MAYL E TL E 3D048034A...
Page 271: ...Wiring Diagrams for Reference Si39 504 260 Appendix RXYQ8MA 10MA 12MAYL E 3D047088C...
Page 272: ...Si39 504 Wiring Diagrams for Reference Appendix 261 RXYQ14MA 16MAYL E 3D047089C...
Page 273: ...Wiring Diagrams for Reference Si39 504 262 Appendix 2 1 2 RXYQ MATL E RXYQ5MATL E 3D049059A...
Page 274: ...Si39 504 Wiring Diagrams for Reference Appendix 263 RXYQ8MA 10MA 12MATL E 3D049060A...
Page 275: ...Wiring Diagrams for Reference Si39 504 264 Appendix RXYQ14MA 16MATL E 3D049061A...
Page 283: ...Wiring Diagrams for Reference Si39 504 272 Appendix FXCQ40M 50M 80M 125MVE 3D039557A...
Page 285: ...Wiring Diagrams for Reference Si39 504 274 Appendix FXKQ25M 32M 40M 63MVE 3D039564B...
Page 289: ...Wiring Diagrams for Reference Si39 504 278 Appendix FXMQ40M 50M 63M 80M 100M 125MVE 3D039620B...
Page 290: ...Si39 504 Wiring Diagrams for Reference Appendix 279 FXMQ200M 250MVE 3D039621B...
Page 291: ...Wiring Diagrams for Reference Si39 504 280 Appendix FXHQ32M 63M 100MVE 3D039801D...
Page 292: ...Si39 504 Wiring Diagrams for Reference Appendix 281 FXAQ20M 25M 32MVE 40M 50M 63MVE 3D034206C...
Page 309: ...Selection of Pipe Size Joints and Header Si39 504 298 Appendix Note 1...
Page 315: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 504 304 Appendix...