Outline of Control (Indoor Unit)
Si39-504
100
Function
6.4
Thermostat Control While in Normal Operation
VRV multi systems are set at factory to thermostat control mode using the remote controller.
While in normal thermostat differential control mode (i.e., factory set mode), the thermostat
turns OFF when the system reaches a temperature of -1°C from the set temperature while in
cooling operation or of +1°C from that while in heating operation.
While in a single remote controller group control, the body thermostat is only used fro this
control.
Furthermore, while in heating operation, cassette-mounted indoor units conduct the thermostat
control by a value compensated by -2°C for the value detected with the body thermostat.
(Through field settings, the thermostat differential setting can be changed from 1°C to 0.5°C.
For details on the changing procedure, refer to information on page onward.)
6.5
Thermostat Control in Dry Operation
While in dry operation, the thermostat control is conducted according to a suction temperature
at the time of starting the dry operation.
Assuming that the suction air temperature at the time of starting the dry operation is Tro and the
suction air temperature in operation is Tr,
Furthermore, while in dry operation mode, fans operate at L flow rate, stops for a period of six
minutes while the thermostat is OFF, and then return to operation at L flow rate. (This control is
used to prevent a rise in indoor temperature while in thermostat OFF mode.)
Cooling operation:
Heating operation:
Normal
operation
Thermostat OFF
Tr < Set temperature -1
ºC
Normal
operation
Thermostat OFF
Tr > Set tempe1
º
C
Tr: Temperature detected with the suction
air thermistor (R1T)
when Tro
≤
24.5
º
C:
when Tro > 24.5
º
C:
In dry operation
In dry operation
Tr < Tro - 1
º
C
Tr < Tro - 1.5
º
C
Thermostat OFF
Thermostat OFF
Tro: Suction air temperature at the
time of starting the dry operation
Tr: Temperature detected with the
suction air thermistor (R1T)
Summary of Contents for VRV II RXYQ5MATL
Page 53: ...Specifications Si39 504 42 Specifications...
Page 115: ...Outline of Control Indoor Unit Si39 504 104 Function...
Page 161: ...Field Setting Si39 504 150 Test Operation...
Page 172: ...Si39 504 Troubleshooting by Remote Controller Troubleshooting 161...
Page 266: ...Si39 504 Piping Diagrams Appendix 255 RXYQ8MA 10MA 12MAYL E TL E 3D048033A...
Page 267: ...Piping Diagrams Si39 504 256 Appendix RXYQ14MA 16MAYL E TL E 3D048034A...
Page 271: ...Wiring Diagrams for Reference Si39 504 260 Appendix RXYQ8MA 10MA 12MAYL E 3D047088C...
Page 272: ...Si39 504 Wiring Diagrams for Reference Appendix 261 RXYQ14MA 16MAYL E 3D047089C...
Page 273: ...Wiring Diagrams for Reference Si39 504 262 Appendix 2 1 2 RXYQ MATL E RXYQ5MATL E 3D049059A...
Page 274: ...Si39 504 Wiring Diagrams for Reference Appendix 263 RXYQ8MA 10MA 12MATL E 3D049060A...
Page 275: ...Wiring Diagrams for Reference Si39 504 264 Appendix RXYQ14MA 16MATL E 3D049061A...
Page 283: ...Wiring Diagrams for Reference Si39 504 272 Appendix FXCQ40M 50M 80M 125MVE 3D039557A...
Page 285: ...Wiring Diagrams for Reference Si39 504 274 Appendix FXKQ25M 32M 40M 63MVE 3D039564B...
Page 289: ...Wiring Diagrams for Reference Si39 504 278 Appendix FXMQ40M 50M 63M 80M 100M 125MVE 3D039620B...
Page 290: ...Si39 504 Wiring Diagrams for Reference Appendix 279 FXMQ200M 250MVE 3D039621B...
Page 291: ...Wiring Diagrams for Reference Si39 504 280 Appendix FXHQ32M 63M 100MVE 3D039801D...
Page 292: ...Si39 504 Wiring Diagrams for Reference Appendix 281 FXAQ20M 25M 32MVE 40M 50M 63MVE 3D034206C...
Page 309: ...Selection of Pipe Size Joints and Header Si39 504 298 Appendix Note 1...
Page 315: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 504 304 Appendix...