Specifications
Si39-504
18
Specifications
Notes:
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
3 Indoor temp. : 20°CDB / outdoor temp. : 7°CDB, 6°CWB / Equivalent piping length : 7.5m, level difference :
0m.
4 Sound level : Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height
of 1.5m. The Sound level of “Combination Unit” is a supposed value. During actual operation, these
values are normally somewhat higher as a result of ambient conditions.
5 The units with anti-corrosion treatment will be available as standard. Please specify the suffix “E” as
RXYQ5MAYLE, TLE.
Model Name (Combination Unit)
RXYQ38MAYL(E)
RXYQ38MATL(E)
RXYQ40MAYL(E)
RXYQ40MATL(E)
Model Name (Independent Unit)
RXYQ10MAYL(E)+RXYQ12MAYL(E)+RXYQ16MAYL(E)
RXYQ10MATL(E)+RXYQ12MATL(E)+RXYQ16MATL(E)
RXYQ10MAYL(E)+RXYQ14MAYL(E)+RXYQ16MAYL(E)
RXYQ10MATL(E)+RXYQ14MATL(E)+RXYQ16MATL(E)
1 Cooling Capacity (19.5°CWB)
kcal / h
92,900
98,000
Btu / h
368,000
389,000
kW
108
114
2 Cooling Capacity (19.0°CWB)
kW
107
113
3 Heating Capacity
kcal / h
102,000
109,000
Btu / h
406,000
433,000
kW
119
127
Casing Color
Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1)
Dimensions: (H×W×D)
mm
(1600×930×765)+(1600×1240×765)+(1600×1240×765)
(1600×930×765)+(1600×1240×765)+(1600×1240×765)
Heat Exchanger
Cross Fin Coil
Cross Fin Coil
Comp.
Type
Hermetically Sealed Scroll Type
Hermetically Sealed Scroll Type
Piston Displacement
m³/h
(13.72+10.53)×2+(13.72+10.53+10.53)
(13.72+10.53)+(13.72+10.53+10.53)×2
Number of Revolutions
r.p.m
(6480, 2900)×2+(6480, 2900×2)
(6480, 2900), (6480, 2900×2)×2
Motor Output×Number
of Units
kW
(1.6+4.5)+(2.8+4.5)+(2.7+4.5+4.5)
(1.6+4.5)+(1.1+4.5+4.5)+(2.7+4.5+4.5)
Starting Method
Direct on line (Inverter Drive)
Direct on line (Inverter Drive)
Fan
Type
Propeller Fan
Propeller Fan
Motor Output
kW
0.75×3
0.75×3
Air Flow Rate
m³/min
180+210+210
180+210+210
Drive
Direct Drive
Direct Drive
Connecting
Pipes
Liquid Pipe
mm
φ
19.1 (Brazing Connection)
φ
19.1 (Brazing Connection)
Gas Pipe
mm
φ
41.3 (Brazing Connection)
φ
41.3 (Brazing Connection)
Product Mass (Machine Weight)
kg
230+268+312
230+312+312
4 Sound Level
dBA
64
64
Safety Devices
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
High Pressure Switch, Fan Driver Overload Protector, Over
Current Relay, Inverter Overload Protector,
Fusible Plugs
Defrost Method
Deicer
Deicer
Capacity Control
%
4~100
4~100
Refrigerant
Refrigerant Name
R-410A
R-410A
Charge kg
8.6+10.4+12.4
8.6+11.6+12.4
Control
Electronic Expansion Valve
Electronic Expansion Valve
Refrigerator Oil
Refer to the nameplate of compressor
Refer to the nameplate of compressor
Standard Accessories
Installation Manual, Operation Manual, Connection Pipes,
Clamps
Installation Manual, Operation Manual, Connection Pipes,
Clamps
Drawing No.
YL(E)
C : 4D049803, 4D049804, 4D049806
C : 4D049803, 4D049805, 4D049806
TL(E)
C : 4D049809, 4D049810, 4D049812
C : 4D049809, 4D049811, 4D049812
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
Summary of Contents for VRV II RXYQ5MATL
Page 53: ...Specifications Si39 504 42 Specifications...
Page 115: ...Outline of Control Indoor Unit Si39 504 104 Function...
Page 161: ...Field Setting Si39 504 150 Test Operation...
Page 172: ...Si39 504 Troubleshooting by Remote Controller Troubleshooting 161...
Page 266: ...Si39 504 Piping Diagrams Appendix 255 RXYQ8MA 10MA 12MAYL E TL E 3D048033A...
Page 267: ...Piping Diagrams Si39 504 256 Appendix RXYQ14MA 16MAYL E TL E 3D048034A...
Page 271: ...Wiring Diagrams for Reference Si39 504 260 Appendix RXYQ8MA 10MA 12MAYL E 3D047088C...
Page 272: ...Si39 504 Wiring Diagrams for Reference Appendix 261 RXYQ14MA 16MAYL E 3D047089C...
Page 273: ...Wiring Diagrams for Reference Si39 504 262 Appendix 2 1 2 RXYQ MATL E RXYQ5MATL E 3D049059A...
Page 274: ...Si39 504 Wiring Diagrams for Reference Appendix 263 RXYQ8MA 10MA 12MATL E 3D049060A...
Page 275: ...Wiring Diagrams for Reference Si39 504 264 Appendix RXYQ14MA 16MATL E 3D049061A...
Page 283: ...Wiring Diagrams for Reference Si39 504 272 Appendix FXCQ40M 50M 80M 125MVE 3D039557A...
Page 285: ...Wiring Diagrams for Reference Si39 504 274 Appendix FXKQ25M 32M 40M 63MVE 3D039564B...
Page 289: ...Wiring Diagrams for Reference Si39 504 278 Appendix FXMQ40M 50M 63M 80M 100M 125MVE 3D039620B...
Page 290: ...Si39 504 Wiring Diagrams for Reference Appendix 279 FXMQ200M 250MVE 3D039621B...
Page 291: ...Wiring Diagrams for Reference Si39 504 280 Appendix FXHQ32M 63M 100MVE 3D039801D...
Page 292: ...Si39 504 Wiring Diagrams for Reference Appendix 281 FXAQ20M 25M 32MVE 40M 50M 63MVE 3D034206C...
Page 309: ...Selection of Pipe Size Joints and Header Si39 504 298 Appendix Note 1...
Page 315: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 504 304 Appendix...