Specifications
Si39-504
38
Specifications
Floor Standing Type
Notes:
1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference : 0m.
2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp. : 35°CDB / Equivalent piping length : 7.5m, level
difference: 0m.
3 Indoor temp. : 20°CDB / outdoor temp. : 7°CDB, 6°CWB / Equivalent piping length : 7.5m, level difference :
0m. (Heat pump only)
4 Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
5 Anechoic chamber conversion value, measured at a point 1.5 m in front of the unit at a height of 1.5 m.
During actual operation, these values are normally somewhat higher as a result of ambient conditions.
Model
FXLQ20MVE
FXLQ25MVE
FXLQ32MVE
1 Cooling Capacity (19.5°CWB)
kcal/h
2,000
2,500
3,200
Btu/h
7,800
9,900
12,600
kW
2.3
2.9
3.7
2 Cooling Capacity (19.0°CWB)
kW
2.2
2.8
3.6
3 Heating Capacity
kcal/h
2,200
2,800
3,400
Btu/h
8,500
10,900
13,600
kW
2.5
3.2
4.0
Casing Color
Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1)
Ivory White (5Y7.5/1)
Dimensions: (H×W×D)
mm
600×1,000×222
600×1,000×222
600×1,140×222
Coil (Cross
Fin Coil)
Rows×Stages×Fin Pitch
mm
3×14×1.5
3×14×1.5
3×14×1.5
Face Area
m²
0.159
0.159
0.200
Fan
Model
D14B20
D14B20
2D14B13
Type
Sirocco Fan
Sirocco Fan
Sirocco Fan
Motor Output × Number
of Units
W
15×1
15×1
25×1
Air Flow Rate (H/L)
m³/min
7/6
7/6
8/6
cfm
247/212
247/212
282/212
Drive
Direct Drive
Direct Drive
Direct Drive
Temperature Control
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Microprocessor Thermostat for
Cooling and Heating
Sound Absorbing Thermal Insulation Material
Glass Fiber/ Urethane Foam
Glass Fiber/ Urethane Foam
Glass Fiber/ Urethane Foam
Air Filter
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Resin Net (with Mold Resistant)
Piping
Connections
Liquid Pipes
mm
φ
6.4 (Flare Connection)
φ
6.4 (Flare Connection)
φ
6.4 (Flare Connection)
Gas Pipes
mm
φ
12.7 (Flare Connection)
φ
12.7 (Flare Connection)
φ
12.7 (Flare Connection)
Drain Pipe
mm
φ
21 O.D (Vinyl Chloride)
φ
21 O.D (Vinyl Chloride)
φ
21 O.D (Vinyl Chloride)
Machine Weight (Mass)
kg
25
25
30
5 Sound Level (H/L) (220V)
dBA
35/32
35/32
35/32
Safety Devices
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Refrigerant Control
Electronic Expansion Valve
Electronic Expansion Valve
Electronic Expansion Valve
Connectable Outdoor Unit
R-410A M(A) Series
R-410A M(A) Series
R-410A M(A) Series
Standard Accessories
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
Operation Manual, Installation
Manual, Insulation for Fitting, Drain
Hose, Clamps, Screws, Washers,
Level Adjustment Screw.
Drawing No.
C : 3D038816
Conversion Formulae
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
Summary of Contents for VRV II RXYQ5MATL
Page 53: ...Specifications Si39 504 42 Specifications...
Page 115: ...Outline of Control Indoor Unit Si39 504 104 Function...
Page 161: ...Field Setting Si39 504 150 Test Operation...
Page 172: ...Si39 504 Troubleshooting by Remote Controller Troubleshooting 161...
Page 266: ...Si39 504 Piping Diagrams Appendix 255 RXYQ8MA 10MA 12MAYL E TL E 3D048033A...
Page 267: ...Piping Diagrams Si39 504 256 Appendix RXYQ14MA 16MAYL E TL E 3D048034A...
Page 271: ...Wiring Diagrams for Reference Si39 504 260 Appendix RXYQ8MA 10MA 12MAYL E 3D047088C...
Page 272: ...Si39 504 Wiring Diagrams for Reference Appendix 261 RXYQ14MA 16MAYL E 3D047089C...
Page 273: ...Wiring Diagrams for Reference Si39 504 262 Appendix 2 1 2 RXYQ MATL E RXYQ5MATL E 3D049059A...
Page 274: ...Si39 504 Wiring Diagrams for Reference Appendix 263 RXYQ8MA 10MA 12MATL E 3D049060A...
Page 275: ...Wiring Diagrams for Reference Si39 504 264 Appendix RXYQ14MA 16MATL E 3D049061A...
Page 283: ...Wiring Diagrams for Reference Si39 504 272 Appendix FXCQ40M 50M 80M 125MVE 3D039557A...
Page 285: ...Wiring Diagrams for Reference Si39 504 274 Appendix FXKQ25M 32M 40M 63MVE 3D039564B...
Page 289: ...Wiring Diagrams for Reference Si39 504 278 Appendix FXMQ40M 50M 63M 80M 100M 125MVE 3D039620B...
Page 290: ...Si39 504 Wiring Diagrams for Reference Appendix 279 FXMQ200M 250MVE 3D039621B...
Page 291: ...Wiring Diagrams for Reference Si39 504 280 Appendix FXHQ32M 63M 100MVE 3D039801D...
Page 292: ...Si39 504 Wiring Diagrams for Reference Appendix 281 FXAQ20M 25M 32MVE 40M 50M 63MVE 3D034206C...
Page 309: ...Selection of Pipe Size Joints and Header Si39 504 298 Appendix Note 1...
Page 315: ...Method of Replacing The Inverter s Power Transistors and Diode Modules Si39 504 304 Appendix...