Troubleshooting for Outdoor Unit
Service Diagnosis
162
6.4
Unspecified Voltage (between Indoor Unit and Outdoor
Unit) / Anti-icing Function in Other Rooms
Remote
Controller
Display
UA
,
UH
Outdoor Unit LED
Display
A
5
1
3
2
3
3
3
4
3
Method of
Malfunction
Detection
A wrong connection is detected by checking the combination of indoor and outdoor units on the
microcomputer.
Malfunction
Decision
Conditions
Anti-icing function in other rooms
Unspecified internal and/or external voltages
Mismatching of indoor and outdoor units
Supposed
Causes
Anti-icing function in other rooms
Wrong models interconnected
Wrong indoor unit PCB or outdoor unit PCB mounted
Troubleshooting
Note:
Refer to “Anti-icing function” on page 163 for detail.
(R15723)
Caution
NO
YES
NO
YES
NO
YES
Check the model combination.
Check the combination of all
connected models.
Error displayed while
operating?
Power
supply voltage as
specified?
Matched compatibly?
The anti-icing function is
activated in other rooms.
Refer to
A5
.
Correct the power supply
voltage.
Match the compatible models.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.