Troubleshooting for Outdoor Unit
SiUS12-928_B
179
Service Diagnosis
6.16 CT or Related Abnormality
Remote
Controller
Display
H8
Outdoor Unit LED
Display
A
j
1
i
2
i
3
h
4
h
Method of
Malfunction
Detection
A CT or related error is detected by checking the compressor running frequency and CT-detected
input current.
Malfunction
Decision
Conditions
The compressor running frequency is more than
A
Hz and input current is less than
B
A.
If the error repeats, the system is shut down.
Reset condition: Continuous run for about 60 minutes without any other error
Supposed
Causes
Defective power module
Broken or disconnected wiring
Defective reactor
Defective outdoor unit PCB
A
(Hz)
B
(A)
18 class
55
1.25
24/32 class
32
0.5