Service Diagnosis
7.12 Outdoor Fan System Check
Check No.19
7.13 Main Circuit Short Check
Check No.20
Note:
Check to make sure that the voltage between (+) and (–) of the diode bridge (DB1) is approx.
0 V before checking.
Measure the resistance between the pins of the DB1 referring to the table below.
If the resistance is
or less than 1 k
, short circuit occurs on the main circuit.
(R15128)
YES
YES
NO
NO
Check the outdoor unit fan system.
Outdoor unit fan running?
Outdoor unit fan
system
functioning.
Go to
Check No. 16
.
Reconnect the connector.