SiUS12-928_B
Troubleshooting for Outdoor Unit
Service Diagnosis
182
Troubleshooting
Check No.01
Refer to P.191
H9
: Outdoor temperature thermistor
J3
: Discharge pipe thermistor
J6
: Outdoor heat exchanger thermistor
J8
: Liquid pipe thermistor
J9
: Gas pipe thermistor
P4
: Radiation fin thermistor
Note:
In case of
P4
for 24/32 class models
Replace the outdoor unit PCB.
Note:
For 3MXS24JVJU
The short thermistors which locate near the connectors [S92] and [S93] each are indispensable for
control. When you check the liquid pipe thermistors or the gas pipe thermistors, check the short
thermistor also.
(R17366)
Caution
NO
YES
YES
NO
NO
YES
Turn on the power again.
Normal?
Reconnect the connectors
or thermistors.
J3
error: The discharge
pipe temperature is
lower than the heat
exchanger temperature.
Replace the defective
thermistor
(s).
∗
Outdoor temperature
thermistor
∗
Discharge pipe thermistor
∗
Outdoor heat exchanger
thermistor
∗
Liquid pipe thermistor
∗
Gas pipe thermistor
∗
Radiation fin thermistor
Cooling: Outdoor heat
exchanger
thermistor
Heating: Indoor heat
exchanger
thermistor
Replace the indoor heat
exchanger thermistor.
Replace the outdoor unit
PCB.
Error displayed
again on remote
controller?
Indoor heat
exchanger thermistor
functioning?
Check No. 01
Check the thermistor resistance
value.
Check No. 01
Check the indoor heat exchanger
thermistor resistance value in
heating operation.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
[S92], [S93]
Short thermistor
(R17392)