ESIE15-13C
Function Details
Function and Control
39
3.2.7 Compressor Step
The compressor operation frequency is controlled in order to keep a constant evaporation
temperature in cooling and a constant condensing temperature in heating.
Cooling
∆
t cool = Remote controller set temperature - Indoor return air temperature.
Depending on
∆
t cool and the cooling load, the target evaporating temperature will be a value
between 2°C and 20°C.
Heating
∆
t heat = Indoor return air temperature - Remote controller set temperature.
Depending on
∆
t heat and the heating load, the target condensing temperature will be a value
between 42°C and 54°C. (for RZQG100-140L: 42°C and 50°C)
: Maximum frequency in cooling
Compressor frequency
RZQG71L7V1
RZQG71L7Y1
RZQSG100-
125L7V1
RZQSG100-
125L7Y1
RZQ100-
140L7V1/Y1
RZQSG71L2V1
2YC63SXD
2YC63PXD
2YC63SXD
2YC63PXD
2YC90AXD/CXD
2YC63DXD
Motor
pole
6 poles
4 poles
6 poles
4 poles
6 poles
6 poles
1
57
38
57
38
54
57
2
61.5
41
63
42
58.5
61.5
3
66
44
69
46
64.5
66
4
72
48
78
52
70.5
72
5
78
52
87
58
78
78
6
85.5
57
97.5
65
85.5
85.5
7
93
62
109.5
73
94.5
93
8
102
68
124.5
83
103.5
100.5
9
109.5
73
139.5
93
111
109.5
10
118.5
79
156
104
118.5
118.5
11
127.5
85
168
112
127.5
127.5
12
136.5
91
183
122
138
136.5
13
145.5
97
192
128
148.5
145.5
14
151.5
101
204
136
162
154.5
15
154.5
103
216
144
174
163.5
16
174
116
228
152
189
174
17
183
122
237
158
204
183
18
192
128
246
164
220.5
192
19
201
134
255
170
234
201
20
211.5
141
265.5
177
249
211.5
21
222
148
282
188
261
222
22
232.5
155
297
198
274.5
232.5
23
243
162
309
206
289.5
—
24
253.5
169
327
218
327
—
25
265.5
177
—
—
—
—
26
277.5
185
—
—
—
—
27
289.5
193
—
—
—
—
Summary of Contents for RZQG71L9V1
Page 2: ......
Page 6: ...ESIE15 13C iv Table of Contents...
Page 14: ...Introduction ESIE15 13C xii...
Page 18: ...Outlook Outdoor Units ESIE15 13C 4 General Information 2 Outlook Outdoor Units...
Page 22: ...Operating range ESIE15 13C 8 General Information...
Page 108: ...Emergency Operation ESIE15 13C 94 Field Setting...