Function Details
ESIE15-13C
38
Function and Control
3.2.6 Room Thermostat Control
Based on the difference between the set temperature by remote controller and indoor unit
suction air temperature, the thermo. is turned on and off.
∆
T = Indoor suction air temperature – temperature set by remote controller (Cooling)
∆
T = Temperature set by remote controller – indoor suction air temperature (Heating)
Thermostat ON Condition
∆
T > +0.5°C
Thermostat OFF Condition
or
•&
• ∆T ≤ – 0.5°C continues for 1 minute
• 5 minutes or more after start up
• ∆T ≤ – 2°C (Cooling)
• ∆T ≤ – 2.5°C (Heating)
When changed suddenly from ∆T ≥ +1.5°C to ∆T ≥ -0.5°C
Summary of Contents for RZQG71L9V1
Page 2: ......
Page 6: ...ESIE15 13C iv Table of Contents...
Page 14: ...Introduction ESIE15 13C xii...
Page 18: ...Outlook Outdoor Units ESIE15 13C 4 General Information 2 Outlook Outdoor Units...
Page 22: ...Operating range ESIE15 13C 8 General Information...
Page 108: ...Emergency Operation ESIE15 13C 94 Field Setting...