Field Setting from Remote Controller
ESIE15-13C
70
Field Setting
Airflow Rate
Set the airflow when thermostat OFF by the combination of "Fan OFF at Thermostat OFF"
11(21)-2, "Fan speed heating thermostat OFF" 12(22)-3 and "Fan speed cooling thermostat
OFF" 12(22)-6.
A : 6 minutes OFF / 1 minute LL
B : 6 minutes OFF / 1 minute setting airflow
C : 6 minutes OFF / 1 minute L
Set the airflow by the combination of 3 modes as below.
Airflow Rate Setting during Heating (FCQG Only)
For the purpose of securing airflow range during heating, the number of revolutions of fan during
heating can be changed. Make the setting according to installation environment.
Mode No.
First Code No.
Second Code No.
Factory
setting
Field setting
11(21)
2
01
01
01
01
02
02
02
02
12(22)
3
01
01
02
02
01
01
02
02
12(22)
6
02
01
01
02
01
02
01
02
Cooling
When thermostat
OFF
Setting
LL
LL
Setting
A
B
A
B
Dry
When thermostat
OFF
C
C
C
C
C
C
C
C
Heating
When thermostat
OFF
LL
LL
Setting Setting
A
A
Setting Setting
When defrost hot
start
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Mode No.
First Code No.
Second Code No.
01
02
03
11 (21)
3
Standard
Slightly up
Up
Summary of Contents for RZQG71L9V1
Page 2: ......
Page 6: ...ESIE15 13C iv Table of Contents...
Page 14: ...Introduction ESIE15 13C xii...
Page 18: ...Outlook Outdoor Units ESIE15 13C 4 General Information 2 Outlook Outdoor Units...
Page 22: ...Operating range ESIE15 13C 8 General Information...
Page 108: ...Emergency Operation ESIE15 13C 94 Field Setting...