Field Setting from Remote Controller
ESIE15-13C
74
Field Setting
2.5
Quiet (Low Noise) Operation
Purpose
Lower the operation sound of the outdoor unit.
Setting
Silent Operation can be activated by:
1. Automatic control (By field setting from remote controller)
2. External activation (from optional PCB KRP58M)
2.5.1 Quiet (Low Noise) Operation by Automatic Control
Table
Silent operation can be set by field setting from the wired remote controller:
Method
When setting mode 16(26)-0-02, quiet (low noise) operation will be carried out by presuming the
current time in accordance with the outside temperature.
Automatic mode will start when the outdoor temperature is = average max of last 10 days -5°C
and will be conducted for 10 hours.
The maximum outdoor temperature is supposed to occur at 14:00h.
As the time judgement is made in accordance with the outdoor temperature, the above
mentioned timing is an estimation only.
Capacity Priority
Setting
When setting mode 16(26)-0-04, the low noise operation will be stopped when the heating or
cooling load increases. In that case, the operation will return to normal operation. The unit will
return to low-noise operation when the heating or cooling load decreases again.
Graph
Description
Mode
No.
First
Code
No.
Second Code No.
01
02
03
04
05
Silent
Operation
16(26)
0
OFF
Low noise
activation
—
Low noise
+ capacity
priority
—
Low noise
start &
stop time
1
—
—
22h00 ~
06h00
22h00 ~
08h00
20h00 ~
08h00
Maximum
ambient
temperature
+8 hours
Start night
quiet
operation
+10 hours
End night
quiet
operation
Trend line indicating fluctuation of
outdoor ambient temperature in 24
hours.
Summary of Contents for RZQG71L9V1
Page 2: ......
Page 6: ...ESIE15 13C iv Table of Contents...
Page 14: ...Introduction ESIE15 13C xii...
Page 18: ...Outlook Outdoor Units ESIE15 13C 4 General Information 2 Outlook Outdoor Units...
Page 22: ...Operating range ESIE15 13C 8 General Information...
Page 108: ...Emergency Operation ESIE15 13C 94 Field Setting...