Field Setting from Outdoor Unit PCB
ESIE15-13C
86
Field Setting
Setting of Refrigerant Recovery Mode
When a refrigerant recovery unit is connected onsite to recover refrigerant, fully open the
expansion valve of the outdoor unit to help the recovery.
(1) Stop operation.
(2) Turn ON refrigerant recovery mode by performing the following steps.
(3) Connect a refrigerant recovery unit to perform refrigerant recovery.
(4) Upon completion of refrigerant recovery, turn OFF refrigerant recovery mode by taking the
following steps or turning OFF the power of outdoor unit.
Note:
*1: If you become unsure how many times you have pushed the button, push the MODE (BS1)
button once to return to "Setting mode 1" and start the operating procedure all over again.
h
: OFF
l
: BLINK
k
: ON
Operating procedure
H1P H2P H3P H4P H5P H6P H7P
Press the MODE (BS1) button of "Setting mode 1" for 5 seconds or more
and set to "Setting mode 2."
k h h h h h h
Press the SET (BS2) button 28 times to set the LED display as shown in
the table on the right. (*1)
k h k k k h h
Press the RETURN (BS3) button once. (Present settings are displayed.)
k h h h h h l
Press the SET (BS2) button once to set the LED display as shown in the
table on the right.
k h h h h l h
Press the RETURN (BS3) button once to make a decision.
k h h h h k h
When the RETURN (BS3) button is pressed once again, the electronic
expansion valve opens fully.
k h h h h h h
Operating procedure
H1P H2P H3P H4P H5P H6P H7P
Press the SET (BS2) button 28 times to set the LED display as shown in
the table on the right. (*1)
k h k k k h h
Press the RETURN (BS3) button once. (Present settings are displayed.)
k h h h h l h
Press the SET (BS2) button once to set the LED display as shown in the
table on the right.
k h h h h h l
Press the RETURN (BS3) button once to make a decision.
k h h h h h k
When the RETURN (BS3) button is pressed once again, the electronic
expansion valve fully opens.
k h h h h h h
Summary of Contents for RZQG71L9V1
Page 2: ......
Page 6: ...ESIE15 13C iv Table of Contents...
Page 14: ...Introduction ESIE15 13C xii...
Page 18: ...Outlook Outdoor Units ESIE15 13C 4 General Information 2 Outlook Outdoor Units...
Page 22: ...Operating range ESIE15 13C 8 General Information...
Page 108: ...Emergency Operation ESIE15 13C 94 Field Setting...