Function Details
ESIE15-13C
42
Function and Control
3.2.12 High Pressure Protection Control
In order to prevent abnormal high pressures in the system and hence avoiding activation of the
high pressure safety device the below control function will be activated.
3.2.13 Heating Control at High Outdoor Air Temperature
Under the condition of heating overload, control the outdoor unit fan in order to secure the
difference of elevation pressure and the pressure ratio of the compressor.
(Cooling)
(Heating)
Normal operation
Hp > 3.57 MPa
Hp < 3.42 MPa
Hp > 3.53 MPa
Hp < 3.52 MPa
Hp < 3.42 MPa
Hp > 3.67 MPa
Compressor operation
frequency –1 step/10 sec.
Compressor operation
fre1 step/1 min.
Normal operation
Compressor operation
frequency B Hz
Compressor stop
Abnormal stop (E3 indication)
Compressor operation
fre1 step/5 min.
Compressor operation
frequency A Hz
Compressor stop
Abnormal stop (E3 indication)
OR
• HPS activates
• Hp > 3.92 MPa
for 1 minute
• Hp < 3.24 MPa
• 30 sec elapsed
15 times or less
stopping in 300
minutes
• Hp > 3.92 MPa
• HPS activates
• Stopped 16 times in
300 minutes
• Stopped 16 times
in 300 minutes
&
OR
RZQG71L
RZQG100-140L
A Hz
118.5 Hz
94.5 Hz
B Hz
57 Hz
94.5 Hz
Normal
• Hp-Lp < 0.39 MPa
• Hp > 3.43 MPa
OR
&
• &
• Hp < 2.75 MPa
OR
• Hp-Lp > 0.69 MPa
• OR
•&
• Lp < 0.12 MPa
(
(
(
(
(
(
Outdoor unit fan
-1 step/30 sec.
Outdoor unit fan
+1 step/30 sec.
• Hp-Lp > 0.59 MPa
• Hp < 3.33 MPa
• Hp < 3.24 MPa
• Outdoor unit fan = 8 step
Summary of Contents for RZQG71L9V1
Page 2: ......
Page 6: ...ESIE15 13C iv Table of Contents...
Page 14: ...Introduction ESIE15 13C xii...
Page 18: ...Outlook Outdoor Units ESIE15 13C 4 General Information 2 Outlook Outdoor Units...
Page 22: ...Operating range ESIE15 13C 8 General Information...
Page 108: ...Emergency Operation ESIE15 13C 94 Field Setting...