ESIE15-13C
Field Setting from Remote Controller
Field Setting
61
2. Field Setting from Remote Controller
Individual function of indoor unit can be changed from the remote controller. At the time of
installation or after service inspection / repair, make the local setting in accordance with the
following description.
Wrong setting may cause error.
(When optional accessory is mounted on the indoor unit, setting for the indoor unit may be
required to change. Refer to information in the option handbook.)
2.1
Wired Remote Controller
2.1.1 BRC1D528
1. When in the normal mode, press the “
” button for 4 seconds or more, and the Field Set
Mode is entered.
2. Select the desired Mode No. with the “
” button (2).
3. During group control, when setting by each indoor unit (mode No. 20, 22 and 23 have been
selected), press the “
” button (3) and select the Indoor Unit No to be set. (This
operation is unnecessary when setting by group.)
4. Press the “
” upper button (4) and select First Code No.
5. Press the “
” lower button (5) and select the Second Code No.
6. Press the “
” button (6) once and the present settings are Set.
7. Press the “
” button (7) to return to the Normal Mode.
(Example)
If during group setting and the time to clean air filter is set to Filter Contamination, Heavy, Set
Mode No. to “10” First Code No. to “0”, and Second Code No. to “02”.
3
4
5
6
1,7
2
Unit No.
Mode No.
Second
Code No.
First
Code No.
Field
Setting
Mode
Summary of Contents for RZQG71L9V1