Function Details
ESIE15-13C
46
Function and Control
3.2.19 Low Outdoor Air Temperature Control in Cooling Operation
Controls compressor and outdoor unit fan under low outdoor air temperature condition to secure
pressure difference between high and low pressure.
Hp: High pressure
Lp: Low pressure
Ta: Outdoor air temperature
Tfin: Inverter fin temperature
Frequency Restriction
Normal operation
Outdoor unit fan: Stop
Compression ratio < 2.1
Compressor operation frequency
restriction (refer to the followings)
Hp-Lp < 0.93MPa
Hp-Lp < 0.78MPa
Hp-Lp < 0.78MPa
Compression ratio < 1.8
Compression ratio <
1.8
Hp < 1.86MPa
Tfin < 66°C
OR
OR
OR
&
&
&
Compression ratio > 2.4
Hp-Lp > 1.08MPa
Ta > 27°C
OR
OR
Hp < 1.57MPa
Ta < 25°C
Hp < 1.57MPa
Hp < 2.94MPa
Hp-Lp > 0.88MPa
Compression ratio > 2.0
Hp > 1.66MPa
&
OR
Tfin ≥
81°C
Hp-Lp > 0.98MPa
Compression ratio > 2.2
Hp > 2.25MPa
&
OR
Outdoor unit fan
-1 step/90 sec.
Outdoor unit fan
+1 step/90 sec.
Outdoor unit fan
Step 1
Lower limit frequency
Step 11
RZQG71L
Upper limit frequency
Step 17
Lower limit frequency
Step 11
RZQG100-140L
Upper limit frequency
Step 17
No frequency
restriction
Ta
≤
25°C
Ta > 27°C
Summary of Contents for RZQG71L9V1
Page 2: ......
Page 6: ...ESIE15 13C iv Table of Contents...
Page 14: ...Introduction ESIE15 13C xii...
Page 18: ...Outlook Outdoor Units ESIE15 13C 4 General Information 2 Outlook Outdoor Units...
Page 22: ...Operating range ESIE15 13C 8 General Information...
Page 108: ...Emergency Operation ESIE15 13C 94 Field Setting...